S7-1200 G1 by SIEMENS

Analog Input SM 1231, 4AI 16bit - 6ES7231-5ND32-0XB0

INR 1
DATASHEET
In stock

Description

SIMATIC S7-1200, Analog input, SM 1231, 4 AI, +/-10 V, +/-5 V, +/-2.5 V, +/-1.25 or 0-20 mA/4-20 mA, 15 bit+sign bit

General information

Product type designation SM 1231, AI 4x16 bit

Supply voltage

Rated value (DC) 24 V

Input current

Current consumption, typ. 65 mA

from backplane bus 5 V DC, typ. 80 mA

Power loss

Power loss, typ. 1.8 W

Analog inputs

Number of analog inputs 4; Current or voltage differential inputs

permissible input voltage for voltage input (destruction limit), max. ±35 V

permissible input current for current input (destruction limit), max. 40 mA

Cycle time (all channels) max. 100 µs

Input ranges

● Voltage Yes; ±10V, ±5V, ±2.5V or ±1.25V

● Current Yes; 4 to 20 mA, 0 to 20 mA

● Thermocouple No

● Resistance thermometer No

● Resistance No

Input ranges (rated values), voltages

● -1.25 V to +1.25 V Yes

● -10 V to +10 V Yes

— Input resistance (-10 V to +10 V) ≥1 MOhm

● -2.5 V to +2.5 V Yes

— Input resistance (-2.5 V to +2.5 V) ≥1 MOhm

● -5 V to +5 V Yes

— Input resistance (-5 V to +5 V) ≥1 MOhm

Input ranges (rated values), currents

● 0 to 20 mA Yes

● 4 mA to 20 mA Yes

Analog value generation for the inputs

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign), max. 15 bit; + sign

● Integration time, parameterizable Yes

● Interference voltage suppression for interference frequency f1 in Hz 40 dB, DC to 60 V for interference frequency 50 / 60 Hz

Smoothing of measured values

● Parameterizable Yes

● Step: None Yes

● Step: low Yes

● Step: Medium Yes

● Step: High Yes

Errors/accuracies

Temperature error (relative to input range), (+/-) 25 °C ±0.1% / ±0.3% total measurement range

Basic error limit (operational limit at 25 °C)

● Voltage, relative to input range, (+/-) 0.1 %

● Current, relative to input range, (+/-) 0.1 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

● Common mode voltage, max. 12 V

Interrupts/diagnostics/status information

Alarms Yes

Diagnostics function Yes

Alarms

● Diagnostic alarm Yes

Diagnoses

● Monitoring the supply voltage Yes

● Wire break Yes

Diagnostics indication LED

● for status of the inputs Yes

● for maintenance Yes

Degree and class of protection

IP degree of protection IP20

Standards, approvals, certificates

CE mark Yes

CSA approval Yes

UL approval Yes

cULus Yes

FM approval Yes

RCM (formerly C-TICK) Yes

KC approval Yes

Marine approval Yes

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 43.1 kg

— global warming potential, (during production) [CO2 eq] 7.62 kg

— global warming potential, (during operation) [CO2 eq] 36 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.544 kg

Specifications

--
--