ET 200SP by SIEMENS

BaseUnit Type C1, BU20-P6+A2+4B -6ES7193-6BP20-0BC1

INR 1
DATASHEET
In stock

Description

SIMATIC ET 200SP, BaseUnit Type C1, BU20-P6+A2+4B BU type C1, Push-in terminals, with 2 AUX terminals, bridged to the left, WxH: 20 mmx117 mm

Product type designation BU type C1

HW functional status FS10 and higher

Supply voltage

Rated value (DC) See manual

● For P1 and P2 bus 24 V

● For AUX bus 24 V; Equal potential group to P1/P2 bus or PE

● for process terminals 24 V

Rated value (AC) See manual

● For P1 and P2 bus 230 V

● For AUX bus 230 V; Equal potential group to P1/P2 bus or PE

● for process terminals 230 V

Mains filter

● Integrated No

Current carrying capacity

up to 60 °C, max. 10 A

For P1 and P2 bus, max. 10 A

For AUX bus, max. 10 A

For process terminals, max. 5 A; 10 A for process terminals 5 and 6

Hardware configuration

Automatic encoding Yes

Slots

● Number of slots 1; Type C1

Potential separation

between backplane bus and supply voltage Yes

between process terminals and supply voltage Yes

between power bus and supply voltage No

Isolation

Isolation tested with 3 100 V DC

Standards, approvals, certificates

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 0.873 kg

— global warming potential, (during production) [CO2 eq] 0.866 kg

— global warming potential, (during operation) [CO2 eq] 0 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.0011 kg

Ambient conditions

Ambient temperature during operation

● horizontal installation, min. -30 °C

● horizontal installation, max. 60 °C

● vertical installation, min. -30 °C

● vertical installation, max. 50 °C

Altitude during operation relating to sea level

● Installation altitude above sea level, max. 2 000 m; On request: Installation altitudes greater than 2 000 m

Absolute humidity

● dew point, min. -60 °C; suitable for dry room applications

Accessories

Color coding labels

● for process terminals CC51

● for AUX terminals CC84 to CC86

● for add-on terminals does not exist

Connection method

Terminals

● Terminal type Push-in terminal

● system-integrated shield connection Yes; Optional

● Conductor cross-section, min. 0.14 mm²; AWG 26

● Conductor cross-section, max. 2.5 mm²; AWG 14

● Number of process terminals to I/O module 16; Pro slot

● Number of terminals to AUX bus 0

● Number of add-on terminals 0

● Number of terminals with connection to P1 and P2 bus 2; Pro slot

Dimensions

Width 20 mm

Height 117 mm

Depth 35 mm

Weights

Weight, approx. 47 g