ET 200SP by SIEMENS

BaseUnit Type U0, BU20-P16+A0+2B, PU 1 -6ES7193-6BP00-0BU0

INR 1
DATASHEET
In stock

Description

SIMATIC ET 200SP, BaseUnit BU20-P16+A0+2B, BU-TYPE U0, Packaging Unit: 1 Pieces, Push-in terminals, w/o AUX-terminals, bridged to left BU, WxH: 20mm x 117mm

General information

Product type designation BU type U0

HW functional status from FS11

Supply voltage

Rated value (DC) See manual

● For P1 and P2 bus 120 V

● For AUX bus 120 V; Equal potential group to P1/P2 bus or PE

● for process terminals 120 V

Rated value (AC) See manual

● For P1 and P2 bus 277 V

● For AUX bus 277 V; Equal potential group to P1/P2 bus or PE

● for process terminals 277 V; 480 V (L1 - L2 - L3); 277 V (L, N)

Mains filter

● integrated No

Current carrying capacity

up to 60 °C, max. 10 A

For P1 and P2 bus, max. 10 A

For AUX bus, max. 10 A

For process terminals, max. 10 A; Point of contact, derating depends on the module

Hardware configuration

Automatic encoding Yes

Formation of potential groups

● New potential group No

● Potential group continued from the left Yes

Slots

● Number of slots 1

Potential separation

between backplane bus and supply voltage Yes

between process terminals and supply voltage Yes; Not applicable for process terminals 15 and 16

between power bus and supply voltage No

Isolation

Isolation tested with 3 100 V DC

Standards, approvals, certificates

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 0.873 kg

— global warming potential, (during production) [CO2 eq] 0.866 kg

— global warming potential, (during operation) [CO2 eq] 0 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.0011 kg

Ambient conditions

Ambient temperature during operation

● horizontal installation, min. -30 °C

● horizontal installation, max. 60 °C

● vertical installation, min. -30 °C

● vertical installation, max. 50 °C

Altitude during operation relating to sea level

● Installation altitude above sea level, max. 3 000 m

Absolute humidity

● dew point, min. -60 °C; suitable for dry room applications

Connection method

Terminals

● Terminal type Push-in terminal

● system-integrated shield connection Yes; Optional

● Conductor cross-section, min. 0.14 mm²; 0.2 mm² without wire end ferrule

● Conductor cross-section, max. 2.5 mm²; 1.5 mm² with wire end ferrule

● Number of process terminals to I/O module 16

● Number of terminals to AUX bus 0

● Number of add-on terminals 0

● Number of terminals with connection to P1 and P2 bus 2

Dimensions

Width 20 mm

Height 117 mm

Depth 35 mm

Weights

Weight, approx. 50 g

Specifications

....