S7-1200 G1 by SIEMENS

CPU 1211C, AC/DC/Relay, 6DI/4DO/2AI - 6ES7211-1BE40-0XB0

INR 1
DATASHEET
In stock

Description

SIMATIC S7-1200, CPU 1211C, compact CPU, AC/DC/relay, onboard I/O: 6 DI 24 V DC; 4 DO relay 2 A; 2 AI 0-10 V DC, power supply: AC 85-264 V AC at 47-63 Hz, program/data memory 75 KB

General information

Product type designation CPU 1211C AC/DC/relay

Firmware version V4.7

Engineering with

● Programming package STEP 7 V20 or higher

Supply voltage

Rated value (AC)

● 120 V AC Yes

● 230 V AC Yes

permissible range, lower limit (AC) 85 V

permissible range, upper limit (AC) 264 V

Line frequency

● permissible range, lower limit 47 Hz

● permissible range, upper limit 63 Hz

Input current

Current consumption (rated value) 60 mA at 120 V AC; 30 mA at 240 V AC

Current consumption, max. 180 mA at 120 V AC; 90 mA at 240 V AC

Inrush current, max. 20 A; at 264 V

I²t 0.8 A²·s

Output current

for backplane bus (5 V DC), max. 750 mA; Max. 5 V DC for CM

Encoder supply

24 V encoder supply

● 24 V 20.4 to 28.8V

Power loss

Power loss, typ. 10 W

Storage

Work memory

● Integrated 75 kbyte

Load memory

● Integrated 1 Mbyte

● Plug-in (SIMATIC Memory Card), max. with SIMATIC memory card

Backup

● present Yes

● maintenance-free Yes

● Without battery Yes

CPU processing times

for bit operations, typ. 0.08 µs; / instruction

for word operations, typ. 1.7 µs; / instruction

for floating point arithmetic, typ. 2.3 µs; / instruction

CPU-blocks

Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

OB

● Number, max. Limited only by RAM for code

Data areas and their retentivity

Retentive data area (incl. timers, counters, flags), max. 14 kbyte

Flag

● Size, max. 4 kbyte; Size of bit memory address area

Local data

● per priority class, max. 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

Address area

Process image

● Inputs, adjustable 1 kbyte

● Outputs, adjustable 1 kbyte

Hardware configuration

Number of modules per system, max. 3 communication modules, 1 signal board

● number of expansion boards (SB, CB, BB) 1

● number of signal modules (SM) 0

● number of communications modules (CM) 3

Time of day

Clock

● Hardware clock (real-time) Yes

● Backup time 480 h; Typical

● Deviation per day, max. ±60 s/month at 25 °C

Digital inputs

Number of digital inputs 6; Integrated

● of which inputs usable for technological functions 6; HSC (High Speed Counting)

Sourcing/sinking input Yes

Number of simultaneously controllable inputs

all mounting positions

— up to 40 °C, max. 6

Input voltage

● Rated value (DC) 24 V

● for signal “0” 5 V DC at 1 mA

● for signal “1” 15 V DC at 2.5 mA

Input current

● for signal “1”, typ. 4 mA; nominal

Input delay (for rated value of input voltage)

for standard inputs

— Parameterizable 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms

— at “0” to “1”, min. 0.2 ms

— at “0” to “1”, max. 12.8 ms

for interrupt inputs

— Parameterizable Yes

for technological functions

— Parameterizable Single phase : 3 @ 100 kHz, differential: 3 @ 80 kHz

Cable length

● shielded, max. 500 m; 50 m for technological functions

● unshielded, max. 300 m; for technological functions: No

Digital outputs

Number of digital outputs 4; Relays

Switching capacity of the outputs

● with resistive load, max. 2 A

● on lamp load, max. 30 W with DC, 200 W with AC

Output delay with resistive load

● “0” to “1”, max. 10 ms; max.

● “1” to “0”, max. 10 ms; max.

Relay outputs

● Number of relay outputs 4

● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000

Cable length

● shielded, max. 500 m

● unshielded, max. 150 m

Analog inputs

Number of analog inputs 2

Input ranges

● Voltage Yes

Input ranges (rated values), voltages

● 0 to +10 V Yes

— Input resistance (0 to 10 V) ≥100k ohms

Cable length

● shielded, max. 100 m; twisted and shielded

Analog outputs

Number of analog outputs 0

Analog value generation for the inputs

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign), max. 10 bit

● Integration time, parameterizable Yes

● Conversion time (per channel) 625 µs

Encoder

Connectable encoders

● 2-wire sensor Yes

Interfaces

Number of PROFINET interfaces 1

1. Interface

Interface type PROFINET

Isolated Yes

automatic detection of transmission rate Yes

Autonegotiation Yes

Autocrossing Yes

Interface types

● RJ 45 (Ethernet) Yes

● Number of ports 1

● integrated switch No

Protocols

● PROFINET IO Controller Yes

● PROFINET IO device Yes

● SIMATIC communication Yes

● Open IE communication Yes; Optionally also encrypted

● Web server Yes

● Media redundancy No

PROFINET IO Controller

● Transmission rate, max. 100 Mbit/s

Services

— PG/OP communication Yes; encryption with TLS V1.3 pre-selected

— Isochronous mode No

— IRT No

— PROFIenergy No

— Prioritized startup Yes

— Number of IO devices with prioritized startup, max. 16

— Number of connectable IO Devices, max. 16

— Number of connectable IO Devices for RT, max. 16

— of which in line, max. 16

— Number of IO Devices that can be simultaneously activated/deactivated, max. 8

— Updating time The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

PROFINET IO Device

Services

— PG/OP communication Yes; encryption with TLS V1.3 pre-selected

— Isochronous mode No

— IRT No

— Dynamic Frame Packing (DFP) No

— PROFIenergy Yes

— Prioritized startup Yes

— Shared device Yes

— Number of IO Controllers with shared device, max. 2

— Asset management record Yes

Specifications

--
--