S7-1200 G1 by SIEMENS

CPU 1212C, DC/DC/Relay, 8DI/6DO/2AI - 6ES7212-1HE40-0XB0

INR 1
DATASHEET
In stock

Description

SIMATIC S7-1200, CPU 1212C, compact CPU, DC/DC/relay, onboard I/O: 8 DI 24 V DC; 6 DO relay 2 A; 2 AI 0-10 V DC, power supply: DC 20.4-28.8 V DC, program/data memory 100 KB

General information

Product type designation CPU 1212C DC/DC/relay

Firmware version V4.7

Engineering with

● Programming package STEP 7 V20 or higher

Supply voltage

Rated value (DC)

● 24 V DC Yes

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Load voltage L+

● Rated value (DC) 24 V

● permissible range, lower limit (DC) 20.4 V

● permissible range, upper limit (DC) 28.8 V

Input current

Current consumption (rated value) 400 mA; CPU only

Current consumption, max. 1 200 mA; CPU with all expansion modules

Inrush current, max. 12 A; at 28.8 V

I²t 0.8 A²·s

Output current

for backplane bus (5 V DC), max. 1 000 mA; Max. 5 V DC for SM and CM

Encoder supply

24 V encoder supply

● 24 V L+ minus 4 V DC min.

Power loss

Power loss, typ. 9 W

Storage

Work memory

● integrated 100 kbyte

Load memory

● Integrated 2 Mbyte

● Plug-in (SIMATIC Memory Card), max. with SIMATIC memory card

Backup

● present Yes

● maintenance-free Yes

● without battery Yes

CPU processing times

for bit operations, typ. 0.08 µs; / instruction

for word operations, typ. 1.7 µs; / instruction

for floating point arithmetic, typ. 2.3 µs; / instruction

CPU-blocks

Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

OB

● Number, max. Limited only by RAM for code

Data areas and their retentivity

Retentive data area (incl. timers, counters, flags), max. 14 kbyte

Flag

● Size, max. 4 kbyte; Size of bit memory address area

Local data

● per priority class, max. 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

Address area

Process image

● Inputs, adjustable 1 kbyte

● Outputs, adjustable 1 kbyte

Hardware configuration

Number of modules per system, max. 3 comm. modules, 1 signal board, 2 signal modules

● number of expansion boards (SB, CB, BB) 1

● number of signal modules (SM) 2

● number of communications modules (CM) 3

Time of day

Clock

● Hardware clock (real-time) Yes

● Backup time 480 h; Typical

● Deviation per day, max. ±60 s/month at 25 °C

Digital inputs

Number of digital inputs 8; Integrated

● of which inputs usable for technological functions 6; HSC (High Speed Counting)

Sourcing/sinking input Yes

Number of simultaneously controllable inputs

all mounting positions

— up to 40 °C, max. 8

Input voltage

● Rated value (DC) 24 V

● for signal “0” 5 V DC at 1 mA

● for signal “1” 15 V DC at 2.5 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms

— at “0” to “1”, min. 0.2 ms

— at “0” to “1”, max. 12.8 ms

for interrupt inputs

— Parameterizable Yes

for technological functions

— Parameterizable Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz

Cable length

● shielded, max. 500 m; 50 m for technological functions

● unshielded, max. 300 m; for technological functions: No

Digital outputs

Number of digital outputs 6; Relays

Switching capacity of the outputs

● with resistive load, max. 2 A

● on lamp load, max. 30 W with DC, 200 W with AC

Output delay with resistive load

● “0” to “1”, max. 10 ms; max.

● “1” to “0”, max. 10 ms; max.

Relay outputs

● Number of relay outputs 6

● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000

Cable length

● shielded, max. 500 m

● unshielded, max. 150 m