Description
SIMATIC S7-1200, CPU 1212FC, compact CPU, DC/DC/relay, onboard I/O: 8 DI 24 V DC; 6 DO relay 2 A; 2 AI 0-10 V DC, power supply: DC 20.4-28.8 V DC, program/data memory 150 KB
General information
Product type designation CPU 1212FC DC/DC/relay
Firmware version V4.7
Engineering with
● Programming package STEP 7 V20 or higher
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
Current consumption (rated value) 400 mA; CPU only
Current consumption, max. 1 200 mA; CPU with all expansion modules
Inrush current, max. 12 A; at 28.8 V
I²t 0.8 A²·s
Output current
for backplane bus (5 V DC), max. 1 000 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V L+ minus 4 V DC min.
Power loss
Power loss, typ. 9 W
Storage
Work memory
● Integrated 150 kbyte
Load memory
● Integrated 2 Mbyte
● Plug-in (SIMATIC Memory Card), max. with SIMATIC memory card
Backup
● present Yes
● maintenance-free Yes
● without battery Yes
CPU processing times
for bit operations, typ. 0.08 µs; / instruction
for word operations, typ. 1.7 µs; / instruction
for floating point arithmetic, typ. 2.3 µs; / instruction
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 14 kbyte
Flag
● Size, max. 4 kbyte; Size of bit memory address area
Local data
● per priority class, max. 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB
Address area
Process image
● Inputs, adjustable 1 kbyte
● Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 2 signal modules
● number of expansion boards (SB, CB, BB) 1
● number of signal modules (SM) 2
● number of communications modules (CM) 3
Time of day
Clock
● Hardware clock (real-time) Yes
● Backup time 480 h; Typical
● Deviation per day, max. ±60 s/month at 25 °C
Digital inputs
Number of digital inputs 8; Integrated
● of which inputs usable for technological functions 6; HSC (High Speed Counting)
Sourcing/sinking input Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 8
Input voltage
● Rated value (DC) 24 V
● for signal “0” 5 V DC at 1 mA
● for signal “1” 15 V DC at 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— Parameterizable 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
— at “0” to “1”, min. 0.2 ms
— at “0” to “1”, max. 12.8 ms
for interrupt inputs
— parameterizable Yes
for technological functions
— Parameterizable Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz
Cable length
● shielded, max. 500 m; 50 m for technological functions
● unshielded, max. 300 m; for technological functions: No
Digital outputs
Number of digital outputs 6; Relays
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 30 W with DC, 200 W with AC
Output delay with resistive load
● “0” to “1”, max. 10 ms; max.
● “1” to “0”, max. 10 ms; max.
Relay outputs
● Number of relay outputs 6
● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000
Cable length
● shielded, max. 500 m
● unshielded, max. 150 m
Analog inputs
Number of analog inputs 2
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
— Input resistance (0 to 10 V) ≥100k ohms
Cable length
● shielded, max. 100 m; twisted and shielded
Analog outputs
Number of analog outputs 0
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 10 bit
● Integration time, parameterizable Yes
● Conversion time (per channel) 625 µs
Encoder
Connectable encoders
● 2-wire sensor Yes
Interfaces
Number of PROFINET interfaces 1
1. Interface
Interface type PROFINET
Isolated Yes
automatic detection of transmission rate Yes
Autonegotiation Yes
Autocrossing Yes
Interface types
● Number of ports 1
● integrated switch No
Protocols
● PROFINET IO Controller Yes
● PROFINET IO Device Yes
● SIMATIC communication Yes
● Open IE communication Yes; Optionally also encrypted
● Web server Yes
● Media redundancy No
PROFINET IO Controller
● Transmission rate, max. 100 Mbit/s
Services
— PG/OP communication Yes; encryption with TLS V1.3 pre-selected
— Isochronous mode No
— IRT No
— PROFIenergy No
— Prioritized startup Yes
— Number of IO devices with prioritized startup, max. 16
— Number of connectable IO Devices, max. 16
— Number of connectable IO Devices for RT, max. 16
— of which in line, max. 16
— Number of IO Devices that can be simultaneously activated/deactivated, max. 8
— Updating time The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.
PROFINET IO Device
Services
— PG/OP communication Yes; encryption with TLS V1.3 pre-selected
— Isochronous mode No
— IRT No
— Dynamic Frame Packing (DFP) No
— PROFIenergy Yes
— Prioritized startup Yes
— Shared device Yes
— Number of IO Controllers with shared device, max. 2
— Asset management record Yes
Protocols
PROFINET IO Yes
PROFIsafe Yes
PROFIBUS Yes; CM 1243-5 (master) or CM 1242-5 (slave) required
OPC UA Yes; OPC UA Server
AS-Interface Yes; CM 1243-2 required
Protocols (Ethernet)
● TCP/IP Yes
● DHCP No
● SNMP Yes
● DCP Yes
● LLDP Yes
Redundancy mode
● PROFINET system redundancy (S2) No
● PROFINET system redundancy (R1) No
Media redundancy
— MRP No
— MRP interconnection, supported No
— MRPD No
SIMATIC communication
● S7 routing Yes
Open IE communication
● TCP/IP Yes
— Data length, max. 8 kbyte
● ISO-on-TCP (RFC1006) Yes
— Data length, max. 8 kbyte
● UDP Yes
— Data length, max. 1 472 byte
Web server
● supported Yes
● User-defined websites Yes
OPC UA
● Runtime license required Yes; “Basic” license required
● OPC UA Server Yes; data access (read, write, subscribe), method call, runtime license required
— Application authentication Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256
— User authentication “anonymous” or by user name & password
— Number of sessions, max. 10
— Number of subscriptions per session, max. 5
— Sampling interval, min. 100 ms
— Publishing interval, min. 200 ms
— Number of server methods, max. 20
— Number of monitored items, recommended max. 1 000
— Number of server interfaces, max. 2
— Number of nodes for user-defined server interfaces, max. 2 000
Further protocols
● MODBUS Yes
Communication functions
S7 communication
● supported Yes
● as server Yes
● As client Yes
● User data per job, max. See online help (S7 communication, user data size)
Number of connections
● overall PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 68 max
Test commissioning functions
Status/control
● Status/control variable Yes
● Variables inputs/outputs, bit memories, DBs, peripheral I/Os (without fail-safe), times, counters
Forcing
● Forcing Yes; peripheral inputs/outputs (without fail-safe)
Diagnostic buffer
● present Yes
Traces
● Number of configurable Traces 2
● Memory size per trace, max. 512 kbyte
Interrupts/diagnostics/status information
Diagnostics indication LED
● RUN/STOP LED Yes
● ERROR LED Yes
● MAINT LED Yes