Description
SIMATIC S7-1200F, CPU 1215 FC, compact CPU, DC/DC/relay, 2 PROFINET ports, onboard I/O: 14 DI 24 V DC; 10 DO relay 2 A, 2 AI 0-10 V DC, 2 AO 0-20 mA DC, power supply: DC 20.4-28.8 V DC, program/data memory 250 KB
General information
Product type designation CPU 1215FC DC/DC/relay
Firmware version V4.7
Engineering with
● Programming package STEP 7 V20 or higher
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
Current consumption (rated value) 500 mA; CPU only
Current consumption, max. 1 500 mA; CPU with all expansion modules
Inrush current, max. 12 A; at 28.8 V DC
I²t 0.5 A²·s
Output current
for backplane bus (5 V DC), max. 1 600 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V L+ minus 4 V DC min.
Power loss
Power loss, typ. 12 W
Storage
Work memory
● Integrated 250 kbyte
Load memory
● Integrated 4 Mbyte
● Plug-in (SIMATIC Memory Card), max. with SIMATIC memory card
Backup
● present Yes
● maintenance-free Yes
● without battery Yes
CPU processing times
for bit operations, typ. 0.08 µs; / instruction
for word operations, typ. 1.7 µs; / instruction
for floating point arithmetic, typ. 2.3 µs; / instruction
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 14 kbyte
Flag
● Size, max. 8 kbyte; Size of bit memory address area
Local data
● per priority class, max. 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB
Address area
Process image
● Inputs, adjustable 1 kbyte
● Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules
● number of expansion boards (SB, CB, BB) 1
● number of signal modules (SM) 8
● number of communications modules (CM) 3
Time of day
Clock
● Hardware clock (real-time) Yes
● Backup time 480 h; Typical
● Deviation per day, max. ±60 s/month at 25 °C
Digital inputs
Number of digital inputs 14; Integrated
● of which inputs usable for technological functions 6; HSC (High Speed Counting)
Sourcing/sinking input Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 14
Input voltage
● Rated value (DC) 24 V
● for signal “0” 5 V DC at 1 mA
● for signal “1” 15 V DC at 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
— at “0” to “1”, min. 0.2 ms
— at “0” to “1”, max. 12.8 ms
for interrupt inputs
— parameterizable Yes
for technological functions
— parameterizable Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz
Cable length
● shielded, max. 500 m; 50 m for technological functions
● unshielded, max. 300 m; for technological functions: No
Digital outputs
Number of digital outputs 10; Relays
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 30 W with DC, 200 W with AC
Output delay with resistive load
● “0” to “1”, max. 10 ms; max.
● “1” to “0”, max. 10 ms; max.
Relay outputs
● Number of relay outputs 10
● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000
Cable length
● shielded, max. 500 m
● unshielded, max. 150 m
Analog inputs
Number of analog inputs 2
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
— Input resistance (0 to 10 V) ≥100k ohms
Cable length
● shielded, max. 100 m; twisted and shielded
Analog outputs
Number of analog outputs 2
Output ranges, current
● 0 to 20 mA Yes
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 10 bit
● Integration time, parameterizable Yes
● Conversion time (per channel) 625 µs
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 10 bit
Encoder
Connectable encoders
● 2-wire sensor Yes
Interfaces
Number of PROFINET interfaces 1
1. Interface
Interface type PROFINET
Isolated Yes
automatic detection of transmission rate Yes
Autonegotiation Yes
Autocrossing Yes
Interface types
● RJ 45 (Ethernet) Yes
● Number of ports 2
● integrated switch Yes
Protocols
● PROFINET IO Controller Yes
● PROFINET IO Device Yes
● SIMATIC communication Yes
● Open IE communication Yes; Optionally also encrypted
● Web server Yes
● Media redundancy Yes
PROFINET IO Controller
● Transmission rate, max. 100 Mbit/s
Services
— PG/OP communication Yes; encryption with TLS V1.3 pre-selected
— Isochronous mode No
— IRT No
— PROFIenergy No
— Prioritized startup Yes
— Number of IO devices with prioritized startup, max. 16
— Number of connectable IO Devices, max. 16
— Number of connectable IO Devices for RT, max. 16
— of which in line, max. 16
— Number of IO Devices that can be simultaneously activated/deactivated, max. 8
— Updating time