CPU 1511C-1 PN, 300KB Prog., 1,5MB Data - 6ES7511-1CL03-0AB0

INR 1
DATASHEET
In stock

Description

SIMATIC S7-1500 compact CPU CPU 1511C-1 PN, central processing unit with 300 KB work memory for program and 1.5 MB for data, 16 digital inputs, 16 digital outputs, 5 analog inputs, 2 analog outputs, 6 high-speed counters, 4 high-speed outputs for PTO/PWM/frequency output 1st interface: PROFINET IRT with 2-port switch, 6 ns bit performance, including front connector push-in, SIMATIC Memory Card required

General information

Product type designation CPU 1511C-1 PN

HW functional status FS01

Firmware version V4.1

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode Yes; with minimal OB 6x cycle of 500 μs (distributed)

● SysLog Yes

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V21 (FW V4.1) / V19 (FW V3.1) or higher; configurable with older TIA Portal versions as 6ES7511-1CK01-0AB0

Configuration control

via dataset Yes

Display

Screen diagonal [cm] 3.45 cm

Control elements

Number of keys 8

Mode buttons 2

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V; 20.4 V DC, for supplying the digital inputs/outputs

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Mains buffering

● Mains/voltage failure stored energy time 5 ms; Refers to the power supply on the CPU section

● Repeat rate, min. 1/s

Input current

Current consumption (rated value) 0.62 A; without DI/DO load

Current consumption, max. 0.9 A; without DI/DO load

Inrush current, max. 1.22 A; Rated value

I²t 0.6 A²·s

Digital inputs

● from load voltage L+ (without load), max. 20 mA; per group

Digital outputs

● from load voltage L+, max. 30 mA; Per group, without load

Encoder supply

Number of outputs 1; One common 24 V encoder supply

24 V encoder supply

● 24 V Yes; L+ (-0.8 V)

● Short-circuit protection Yes

● Output current, max. 1 A

Power

Infeed power to the backplane bus 10 W

Power consumption from the backplane bus (balanced) 8.5 W

Power loss

Power loss, typ. 5 W

Storage

Number of slots for SIMATIC memory card 1

SIMATIC memory card required Yes

Work memory

● integrated (for program) 300 kbyte

● integrated (for data) 1.5 Mbyte

Load memory

● Plug-in (SIMATIC Memory Card), max. 32 Gbyte

Backup

● maintenance-free Yes

CPU processing times

for bit operations, typ. 6 ns

for word operations, typ. 7 ns

for fixed point arithmetic, typ. 9 ns

for floating point arithmetic, typ. 37 ns

CPU-blocks

Number of elements (total) 4 000; Blocks (OB, FB, FC, DB) and UDTs

DB

● Number range 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999

● Size, max. 1.5 Mbyte; For DBs with absolute addressing, the max. size is 64 KB

FB

● Number range 0 ... 65 535

● Size, max. 300 kbyte

FC

● Number range 0 ... 65 535

● Size, max. 300 kbyte

OB

● Size, max. 300 kbyte

● Number of free cycle OBs 100

● Number of time alarm OBs 20

● Number of delay alarm OBs 20

● Number of cyclic interrupt OBs 20; With minimum OB 3x cycle of 250 µs

● Number of process alarm OBs 50

● Number of DPV1 alarm OBs 3

● Number of isochronous mode OBs 1

● Number of startup OBs 100

● Number of asynchronous error OBs 4

● Number of synchronous error OBs 2

● Number of diagnostic alarm OBs 1

Nesting depth

● per priority class 24

Counters, timers and their retentivity

S7 counter

● Number 2 048

Retentivity

— can be set Yes

IEC counter

● Number Any (only limited by the main memory)

Retentivity

— can be set Yes

S7 timer

● Number 2 048

Retentivity

— adjustable Yes

IEC timer

● Number Any (only limited by the main memory)

Retentivity

— can be set Yes

Data areas and their retentivity

Retentive data area (incl. timers, counters, flags), max. 216 kbyte; in total; for bit memories, timers, counters, DBs, and technology data (axes)

Extended retentive data area (incl. timers, counters, flags), max. 1.5 Mbyte; When using PS 6 0W 24/48/60 V DC HF

Flag

● Size, max. 16 kbyte

● Number of clock memories 8; 8 clock memory bit, grouped into one clock memory byte

Data blocks

● Retentivity adjustable Yes

● Retentivity preset No

Local data

● per priority class, max. 64 kbyte; max. 16 KB per block

Address area

Number of IO modules 2 048; max. number of modules / submodules

I/O address area

● Inputs 32 kbyte; All inputs are in the process image

● Outputs 32 kbyte; All outputs are in the process image

per integrated IO subsystem

— Inputs (volume) 8 kbyte

— Outputs (volume) 8 kbyte

per CM/CP

— Inputs (volume) 8 kbyte

— Outputs (volume) 8 kbyte

Subprocess images

● Number of subprocess images, max. 32

Hardware configuration

Number of distributed IO systems 32; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link)

Number of DP masters

● via CM 4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total

Number of IO Controllers

● integrated 1

● Via CM 4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total

Rack

● Modules per rack, max. 32; CPU + 31 modules

● Number of lines, max. 1

PtP CM

● Number of PtP CMs the number of connectable PtP CMs is only limited by the number of available slots

Time of day

Clock

● Type Hardware clock

● Backup time 6 wk; At 40 °C ambient temperature, typically

● Deviation per day, max. 10 s; Typ.: 2 s

Operating hours counter

● Number 64

Clock synchronization

● supported Yes

● to DP, master Yes; via PROFIBUS CM / CP

● on DP, device Yes; via PROFIBUS CM / CP

● in AS, master Yes

● in AS, device Yes

● on Ethernet via NTP Yes

Digital inputs

integrated channels (DI) 16

Digital inputs, parameterizable Yes

Sourcing/sinking input P-reading

Input characteristic curve in accordance with IEC 61131, type 3 Yes

Digital input functions, parameterizable

● Gate start/stop Yes

● Capture Yes

● Synchronization Yes

Input voltage

● Type of input voltage DC

● Rated value (DC) 24 V

● for signal “0” -3 to +5V

● for signal “1” +11 to +30V

Input current

● for signal “1”, typ. 2.5 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable Yes; none / 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms

— at “0” to “1”, min. 4 µs; for parameterization “none”

— at “0” to “1”, max. 20 ms

— at “1” to “0”, min. 4 µs; for parameterization “none”

— at “1” to “0”, max. 20 ms

for interrupt inputs

— parameterizable Yes; Same as for standard inputs

for technological functions

— parameterizable Yes; Same as for standard inputs

Cable length

● shielded, max. 1 000 m; 600 m for technological functions; depending on input frequency, encoder and cable quality; max. 50 m at 100 kHz

● unshielded, max. 600 m; for technological functions: No

Digital outputs

Type of digital output Transistor

integrated channels (DO) 16

Current-sourcing Yes; Push-pull output

Short-circuit protection Yes; electronic/thermal

● Response threshold, typ. 1.6 A with standard output, 0.5 A with high-speed output; see manual for details

Limitation of inductive shutdown voltage to connector X11: -0.8 V

Controlling a digital input Yes

Accuracy of pulse duration Up to ±100 ppm ±2 μs at high-speed output; see manual for details

minimum pulse duration 2 µs; With High Speed output

Digital output functions, parameterizable

● Switching tripped by comparison values Yes; As output signal of a high-speed counter

● PWM output Yes

— Number, max. 4

— Cycle duration, parameterizable Yes

— ON period, min. 0 %

— ON period, max. 100 %

— Resolution of the duty cycle 0.0036 %; For S7 analog format, min. 40 ns

● Frequency output Yes

Switching capacity of the outputs

● with resistive load, max. 0.5 A; 0.1 A with high-speed output, i.e. when using a high-speed output; see manual for details

● on lamp load, max. 5 W; 1 W with high-speed output, i.e. when using a high-speed output; see manual for details

Load resistance range

● lower limit 48 Ω; 240 ohms with high-speed output, i.e. when using a high-speed output; see manual for details

● upper limit 12 kΩ

Output voltage

● Type of output voltage DC

● for signal “0”, max. 1 V; With high-speed output, i.e. when using a high-speed output; see manual for details

● for signal “1”, min. 23.2 V; L+ (-0.8 V)

Output current

● for signal “1” rated value 0.5 A; 0.1 A with high-speed output, i.e. when using a high-speed output, observe derating; see manual for details

● for signal “1” permissible range, min. 2 mA

● for signal “1” permissible range, max. 0.6 A; 0.12 A with high-speed output, i.e. when using a high-speed output, observe derating; see manual for details

● for signal “0” residual current, max. 0.5 mA

Output delay with resistive load

● “0” to “1”, max. 200 µs

● “1” to “0”, max. 500 µs; Load-dependent

for technological functions

— “0” to “1”, max. 5 µs; Depending on the output used, see additional description in manual

— “1” to “0”, max. 5 µs; Depending on the output used, see additional description in manual

Parallel switching of two outputs

● for logic links Yes; for technological functions: No

● for uprating No

● for redundant control of a load Yes; for technological functions: No

Switching frequency

● with resistive load, max. 100 kHz; For high-speed output, 100 Hz for standard output

● with inductive load, max. 0.5 Hz; Acc. to IEC 60947-5-1, DC-13; observe derating curve

● on lamp load, max. 10 Hz

Total current of the outputs

● Current per channel, max. 0.5 A; see additional description in the manual

● Current per group, max. 8 A; see additional description in the manual

● Current per power supply, max. 4 A; 2 power supplies for each group, current per power supply max. 4 A, see additional description in manual

for technological functions

— Current per channel, max. 0.5 A; see additional description in the manual

Relay outputs

● Number of relay outputs 0

Cable length

● shielded, max. 1 000 m; 600 m for technological functions; depending on output frequency, load, and cable quality; max. 50 m at 100 kHz

● unshielded, max. 600 m; for technological functions: No

Analog inputs

Number of analog inputs 5; 4x for U/I, 1x for R/RTD

● For current measurement 4; max.

● For voltage measurement 4; max.

● For resistance/resistance thermometer measurement 1

integrated channels (AI) 5

permissible input voltage for voltage input (destruction limit), max. 28.8 V

permissible input current for current input (destruction limit), max. 40 mA

Cycle time (all channels), min. 1 ms; Dependent on the parameterized interference frequency suppression; for details, see conversion procedure in manual

Technical unit for temperature measurement adjustable Yes; °C/°F/K

Input ranges (rated values), voltages

● 0 to +10 V Yes; Physical measuring range: ± 10 V

— Input resistance (0 to 10 V) 100 kΩ

● 1 V to 5 V Yes; Physical measuring range: ± 10 V

— Input resistance (1 V to 5 V) 100 kΩ

● -10 V to +10 V Yes

— Input resistance (-10 V to +10 V) 100 kΩ

● -5 V to +5 V Yes; Physical measuring range: ± 10 V

— Input resistance (-5 V to +5 V) 100 kΩ

Input ranges (rated values), currents

● 0 to 20 mA Yes; Physical measuring range: ± 20 mA

— Input resistance (0 to 20 mA) 50 Ω; Plus approx. 55 ohm for overvoltage protection by PTC

● -20 mA to +20 mA Yes

— Input resistance (-20 mA to +20 mA) 50 Ω; Plus approx. 55 ohm for overvoltage protection by PTC

● 4 mA to 20 mA Yes; Physical measuring range: ± 20 mA

— Input resistance (4 mA to 20 mA) 50 Ω; Plus approx. 55 ohm for overvoltage protection by PTC

Input ranges (rated values), resistance thermometer

● Ni 100 Yes; Standard/climate

— Input resistance (Ni 100) 10 MΩ

● Pt 100 Yes; Standard/climate

— Input resistance (Pt 100) 10 MΩ

Input ranges (rated values), resistors

● 0 to 150 ohms Yes; Physical measuring range: 0 ... 600 ohms

— Input resistance (0 to 150 ohms) 10 MΩ

● 0 to 300 ohms Yes; Physical measuring range: 0 ... 600 ohms

— Input resistance (0 to 300 ohms) 10 MΩ

● 0 to 600 ohms Yes

— Input resistance (0 to 600 ohms) 10 MΩ

Cable length

● shielded, max. 800 m; for U/I, 200 m for R/RTD

Analog outputs

integrated channels (AO) 2

Voltage output, short-circuit protection Yes

Cycle time (all channels), min. 1 ms; Dependent on the parameterized interference frequency suppression; for details, see conversion procedure in manual

Output ranges, voltage

● 0 to 10 V Yes

● 1 V to 5 V Yes

● -10 V to +10 V Yes

Output ranges, current

● 0 to 20 mA Yes

● -20 mA to +20 mA Yes

● 4 mA to 20 mA Yes

Load impedance (in rated range of output)

● with voltage outputs, min. 1 kΩ

● with voltage outputs, capacitive load, max. 100 nF

● with current outputs, max. 500 Ω

● with current outputs, inductive load, max. 1 mH

Cable length

● shielded, max. 200 m

Analog value generation for the inputs

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign), max. 16 bit

● Integration time, parameterizable Yes; 2.5 / 16.67 / 20 / 100 ms, acts on all channels

● Interference voltage suppression for interference frequency f1 in Hz 400 / 60 / 50 / 10

Smoothing of measured values

● Parameterizable Yes

● Step: None Yes

● Step: low Yes

● Step: Medium Yes

● Step: High Yes

Analog value generation for the outputs

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign), max. 16 bit

Settling time

● for resistive load 1.5 ms

● for capacitive load 2.5 ms

● for inductive load 2.5 ms

Encoder

Connection of signal encoders

● for voltage measurement Yes

● for current measurement as 4-wire transducer Yes

● for resistance measurement with two-wire connection Yes

● for resistance measurement with three-wire connection Yes

● for resistance measurement with four-wire connection Yes

Connectable encoders

● 2-wire sensor Yes

— permissible quiescent current (2-wire sensor), max. 1.5 mA

Encoder signals, incremental encoder (asymmetrical)

● Input voltage 24 V

● Input frequency, max. 100 kHz

● Counting frequency, max. 400 kHz; with quadruple evaluation

● Signal filter, parameterizable Yes

● Incremental encoder with A/B tracks, 90° phase offset Yes

● Incremental encoder with A/B tracks, 90° phase offset and zero track Yes

● pulse encoder Yes

● pulse encoder with direction Yes

● pulse encoder with one impulse signal per count direction Yes

Errors/accuracies

Linearity error (relative to input range), (+/-) 0.1 %

Temperature error (relative to input range), (+/-) 0.005 %/K

Crosstalk between the inputs, max. -60 dB

Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 %

Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) 0.02 %

Linearity error (relative to output range), (+/-) 0.15 %

Temperature error (relative to output range), (+/-) 0.005 %/K

Crosstalk between the outputs, max. -80 dB

Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) 0.05 %

Operational error limit in overall temperature range

● Voltage, relative to input range, (+/-) 0.3 %

● Current, relative to input range, (+/-) 0.3 %

● Resistance, relative to input range, (+/-) 0.3 %

● Resistance thermometer, relative to input range, (+/-) Pt100 Standard: ±2 K, Pt100 Climate: ±1 K, Ni100 Standard: ±1.2 K, Ni100 Climate: ±1 K

● Voltage, relative to output range, (+/-) 0.3 %

● Current, relative to output range, (+/-) 0.3 %

Basic error limit (operational limit at 25 °C)

● Voltage, relative to input range, (+/-) 0.2 %

● Current, relative to input range, (+/-) 0.2 %

● Resistance, relative to input range, (+/-) 0.2 %

● Resistance thermometer, relative to input range, (+/-) Pt100 Standard: ±1 K, Pt100 Climate: ±0.5 K, Ni100 Standard: ±0.6 K, Ni100 Climate: ±0.5 K

● Voltage, relative to output range, (+/-) 0.2 %

● Current, relative to output range, (+/-) 0.2 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

● Series mode interference (peak value of interference < rated value of input range), min. 30 dB

● Common mode voltage, max. 10 V

● Common mode interference, min. 60 dB; at 400 Hz: 50 dB

Interfaces

Number of PROFINET interfaces 1

1. Interface

Interface types

● RJ 45 (Ethernet) Yes; X1

● Number of ports 2

● integrated switch Yes

Protocols

● IP protocol Yes; IPv4

● PROFINET IO Controller Yes

● PROFINET IO Device Yes

● SIMATIC communication Yes

● Open IE communication Yes; Optionally also encrypted

● Web server Yes

● Media redundancy Yes

PROFINET IO Controller

Services

— Isochronous mode Yes

— Direct data exchange Yes; Requirement: IRT and isochronous mode (MRPD optional)

— IRT Yes

— Dynamic Frame Packing (DFP) Yes

— PROFIenergy Yes; per user program

— Prioritized startup Yes; Max. 32 PROFINET devices

— Number of connectable IO Devices, max. 128; In total, up to 512 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET

— Of which IO devices with IRT, max. 64

— Number of connectable IO Devices for RT, max. 128

— of which in line, max. 128

— Number of IO Devices that can be simultaneously activated/deactivated, max. 8; in total across all interfaces

— Number of IO Devices per tool, max. 8

— Updating times The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data

Update time for IRT

— for send cycle of 250 µs 250 μs to 4 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 500 µs of the isochronous OB is decisive

— for send cycle of 500 µs 500 µs to 8 ms

— for send cycle of 1 ms 1 ms to 16 ms

— for send cycle of 2 ms 2 ms to 32 ms

— for send cycle of 4 ms 4 ms to 64 ms

— With IRT and parameterization of “odd” send cycles Update time = set “odd” send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs)

Update time for RT

— for send cycle of 250 µs 250 µs to 128 ms

— for send cycle of 500 µs 500 µs to 256 ms

— for send cycle of 1 ms 1 ms to 512 ms

— for send cycle of 2 ms 2 ms to 512 ms

— for send cycle of 4 ms 4 ms to 512 ms

PROFINET IO Device

Services

— Isochronous mode No

— IRT Yes

— Dynamic Frame Packing (DFP) No

— PROFIenergy Yes; per user program

— Prioritized startup Yes

— Shared device Yes

— Number of IO Controllers with shared device, max. 4

— activation/deactivation of I-devices Yes; per user program

— Asset management record Yes; per user program

Interface types

RJ 45 (Ethernet)

● 100 Mbps Yes

● Autonegotiation Yes

● Autocrossing Yes

● Industrial Ethernet status LED Yes

Protocols

Number of connections

● Number of connections, max. 128; via integrated interfaces of the CPU and connected CPs / CMs

● Number of connections reserved for ES/HMI/web 10

● Number of connections via integrated interfaces 88

● Number of S7 routing paths 16

Redundancy mode

● PROFINET system redundancy (S2) No

● PROFINET system redundancy (R1) No

● H-Sync forwarding Yes

Media redundancy

— Media redundancy only via 1st interface (X1)

— MRP Yes; MRP Automanager according to IEC 62439-2 Edition 2.0, MRP Manager; MRP Client

— MRP interconnection, supported Yes; as MRP ring node according to IEC 62439-2 Edition 3.0

— MRPD Yes; Requirement: IRT

— Switchover time on line break, typ. 200 ms; For MRP, bumpless for MRPD

— Number of stations in the ring, max. 50

SIMATIC communication

● PG/OP communication Yes; encryption with TLS V1.3 pre-selected

● S7 routing Yes

● Data record routing Yes

● S7 communication, as server Yes

● S7 communication, as client Yes

● User data per job, max. See online help (S7 communication, user data size)

Open IE communication

● TCP/IP Yes

— Data length, max. 64 kbyte

— several passive connections per port, supported Yes

● ISO-on-TCP (RFC1006) Yes

— Data length, max. 64 kbyte

● UDP Yes

— Data length, max. 2 kbyte; 1 472 bytes for UDP broadcast

— UDP multicast Yes; max. 78 multicast circuits

● DHCP Yes

● DNS Yes

● SNMP Yes

● DCP Yes

● LLDP Yes

● Encryption Yes; Optional

Web server

● HTTP Yes; Standard and user pages

● HTTPS Yes; Standard and user pages

● web API

— Number of sessions, max. 50

— number of simultaneous HTTP calls, max. 4

— HTTP request body, max. 131 072 byte

OPC UA

● Runtime license required Yes; “Small” license required

● OPC UA Client Yes; Data Access (registered Read/Write), Method Call

— Application authentication Yes

— Security policies Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256

— User authentication “anonymous” or by user name & password

— Number of connections, max. 4

— Number of nodes of the client interfaces, recommended max. 1 000

— Number of elements for one call of OPC_UA_NodeGetHandleList/OPC_UA_ReadList/OPC_UA_WriteList, max. 300

— Number of elements for one call of OPC_UA_NameSpaceGetIndexList, max. 20

— Number of elements for one call of OPC_UA_MethodGetHandleList, max. 100

— Number of simultaneous calls of the client instructions for session management, per connection, max. 1

— Number of simultaneous calls of the client instructions for data access, per connection, max. 5; for OPC_UA_MethodCall 50 in total (no limit per connection)

— Number of registerable nodes, max. 5 000

— Number of registerable method calls of OPC_UA_MethodCall, max. 100

— Number of inputs/outputs when calling OPC_UA_MethodCall, max. 20

● OPC UA Server Yes; data access (read, write, subscribe), method call, alarms & condition (A&C), custom address space, role-based access control

— Application authentication Yes

— Security policies available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256, Aes128Sha256RsaOaep, Aes256Sha256RsaPss

— User authentication “anonymous” or by user name & password

— GDS support (certificate management) Yes

— Number of sessions, max. 32

— Number of accessible variables, max. 50 000

— Number of registerable nodes, max. 10 000

— Number of subscriptions per session, max. 50

— Sampling interval, min. 100 ms

— Publishing interval, min. 200 ms

— Number of server methods, max. 500; max. 25 concurrently running jobs each for asynchronous instructions OPC_UA_ServerMethodPre and OPC_UA_ServerMethodPost

— Number of inputs/outputs per server method, max. 20

— Number of monitored items, recommended max. 4 000; for 1 s sampling interval and 1 s send interval

— Number of server interfaces, max. 10 of each “Server interfaces” / “Companion specification” type and 20 of the type “Reference namespace”

— Number of nodes for user-defined server interfaces, max. 15 000

● Alarms and Conditions Yes

— Number of program alarms 100

— Number of alarms for system diagnostics 50

Further protocols

● MODBUS Yes; MODBUS TCP

S7 message functions

Number of login stations for message functions, max. 32

number of subscriptions, max. 250

number of tags/attributes for subscriptions, max. 2 000

Program alarms Yes

Number of configurable program messages, max. 5 000; Program messages are generated by the “Program_Alarm” block, ProDiag or GRAPH

Number of loadable program messages in RUN, max. 5 000

Number of simultaneously active program alarms

● Number of program alarms 600

● Number of alarms for system diagnostics 100

● Number of alarms for motion technology objects 160

Test commissioning functions

Joint commission (Team Engineering) Yes; Parallel online access possible for up to 5 engineering systems

Status block Yes; Up to 8 simultaneously (in total across all ES clients)

Single step No

Number of breakpoints 8

Profiling Yes

Status/control

● Status/control variable Yes

● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

● Number of variables, max.

— of which status variables, max. 200; per job

— of which control variables, max. 200; per job

Forcing

● Forcing Yes

● Forcing, variables Peripheral inputs/outputs

● Number of variables, max. 200

Diagnostic buffer

● present Yes

● Number of entries, max. 1 000

— of which powerfail-proof 500

Traces

● Number of configurable Traces 4

● Memory size per trace, max. 512 kbyte

Interrupts/diagnostics/status information

Alarms

● Diagnostic alarm Yes

● Hardware interrupt Yes

Diagnoses

● Monitoring the supply voltage Yes

● Wire break Yes; for analog inputs/outputs, see description in manual

● Short-circuit Yes; for analog outputs, see description in manual

● A/B transition error at incremental encoder Yes

Specifications

--
--