Description
SIMATIC S7-1500 compact CPU, CPU 1512C-1 PN, central processing unit with work memory: 400 KB for program and 2 MB for data, 32 digital inputs, 32 digital outputs, 5 analog inputs, 2 analog outputs, 6 high-speed counters, 4 fast outputs for PTO/PWM/frequency output, 1st interface: PROFINET IRT with 2-port switch, 6 ns bit performance, including front connector push-in, SIMATIC Memory Card required
General information
Product type designation CPU 1512C-1 PN
HW functional status FS01
Firmware version V4.1
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes; with minimal OB 6x cycle of 500 μs (distributed)
● SysLog Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V21 (FW V4.1) / V19 (FW V3.1) or higher; configurable with older TIA Portal versions as 6ES7512-1CK01-0AB0
Configuration control
via dataset Yes
Display
Screen diagonal [cm] 3.45 cm
Control elements
Number of keys 8
Mode buttons 2
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V; 20.4 V DC, for supplying the digital inputs/outputs
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Mains buffering
● Mains/voltage failure stored energy time 5 ms; Refers to the power supply on the CPU section
● Repeat rate, min. 1/s
Input current
Current consumption (rated value) 0.66 A; without DI/DO load
Current consumption, max. 1 A; without DI/DO load
Inrush current, max. 1.22 A; Rated value
I²t 0.6 A²·s
Digital inputs
● from load voltage L+ (without load), max. 20 mA; per group
Digital outputs
● from load voltage L+, max. 30 mA; Per group, without load
Encoder supply
Number of outputs 2; One common 24 V encoder supply per 16 digital inputs
24 V encoder supply
● 24 V Yes; L+ (-0.8 V)
● Short-circuit protection Yes
● Output current, max. 1 A
Power
Infeed power to the backplane bus 10 W
Power consumption from the backplane bus (balanced) 9 W
Power loss
Power loss, typ. 6 W
Storage
Number of slots for SIMATIC memory card 1
SIMATIC memory card required Yes
Work memory
● integrated (for program) 400 kbyte
● integrated (for data) 2 Mbyte
Load memory
● Plug-in (SIMATIC Memory Card), max. 32 Gbyte
Backup
● maintenance-free Yes
CPU processing times
for bit operations, typ. 6 ns
for word operations, typ. 7 ns
for fixed point arithmetic, typ. 9 ns
for floating point arithmetic, typ. 37 ns
CPU-blocks
Number of elements (total) 4 000; Blocks (OB, FB, FC, DB) and UDTs
DB
● Number range 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999
● Size, max. 2 Mbyte; For DBs with absolute addressing, the max. size is 64 KB
FB
● Number range 0 ... 65 535
● Size, max. 400 kbyte
FC
● Number range 0 ... 65 535
● Size, max. 400 kbyte
OB
● Size, max. 400 kbyte
● Number of free cycle OBs 100
● Number of time alarm OBs 20
● Number of delay alarm OBs 20
● Number of cyclic interrupt OBs 20; With minimum OB 3x cycle of 250 µs
● Number of process alarm OBs 50
● Number of DPV1 alarm OBs 3
● Number of isochronous mode OBs 1
● Number of startup OBs 100
● Number of asynchronous error OBs 4
● Number of synchronous error OBs 2
● Number of diagnostic alarm OBs 1
Nesting depth
● per priority class 24
Counters, timers and their retentivity
S7 counter
● Number 2 048
Retentivity
— can be set Yes
IEC counter
● Number Any (only limited by the main memory)
Retentivity
— can be set Yes
S7 timer
● Number 2 048
Retentivity
— adjustable Yes
IEC timer
● Number Any (only limited by the main memory)
Retentivity
— can be set Yes
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 216 kbyte; in total; for bit memories, timers, counters, DBs, and technology data (axes)
Extended retentive data area (incl. timers, counters, flags), max. 2 Mbyte; When using PS 6 0W 24/48/60 V DC HF
Flag
● Size, max. 16 kbyte
● Number of clock memories 8; 8 clock memory bit, grouped into one clock memory byte
Data blocks
● Retentivity adjustable Yes
● Retentivity preset No
Local data
● per priority class, max. 64 kbyte; max. 16 KB per block
Address area
Number of IO modules 2 048; max. number of modules / submodules
I/O address area
● Inputs 32 kbyte; All inputs are in the process image
● Outputs 32 kbyte; All outputs are in the process image
per integrated IO subsystem
— Inputs (volume) 8 kbyte
— Outputs (volume) 8 kbyte
per CM/CP
— Inputs (volume) 8 kbyte
— Outputs (volume) 8 kbyte
Subprocess images
● Number of subprocess images, max. 32
Hardware configuration
Number of distributed IO systems 32; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link)
Number of DP masters
● via CM 6; A maximum of 6 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total
Number of IO Controllers
● integrated 1
● Via CM 6; A maximum of 6 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total
Rack
● Modules per rack, max. 32; CPU + 31 modules
● Number of lines, max. 1
PtP CM
● Number of PtP CMs the number of connectable PtP CMs is only limited by the number of available slots
Time of day
Clock
● Type Hardware clock
● Backup time 6 wk; At 40 °C ambient temperature, typically
● Deviation per day, max. 10 s; Typ.: 2 s
Operating hours counter
● Number 64
Clock synchronization
● supported Yes
● to DP, master Yes; via PROFIBUS CM / CP
● on DP, device Yes; via PROFIBUS CM / CP
● in AS, master Yes
● in AS, device Yes
● on Ethernet via NTP Yes
Specifications
| - | - |
|---|---|
| - | - |