Description
SIMATIC S7-1500R, CPU 1513R-1PN, central processing unit with work memory 600 KB for program and 2.5 MB for data, 1st interface: PROFINET RT with 2-port switch, SIMATIC Memory Card required
Product type designation CPU 1513R-1 PN
HW functional status from FS04
Firmware version V4.1
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● SysLog Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V21 (FW V4.1) / V18 (FW V3.0); with older TIA Portal versions configurable as 6ES7513-1RL00-0AB0
Redundancy
● stand-alone operation Yes
Display
Screen diagonal [cm] 3.45 cm
Control elements
Number of keys 8
Mode buttons 2
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Mains buffering
● Mains/voltage failure stored energy time 5 ms
● Repeat rate, min. 1/s
Input current
Current consumption (rated value) 0.56 A
Current consumption, max. 0.87 A
Inrush current, max. 1.15 A; Rated value
I²t 0.5 A²·s
Power
Infeed power to the backplane bus 10 W
Power consumption from the backplane bus (balanced) 5.5 W
Power loss
Power loss, typ. 3.4 W
Storage
Number of slots for SIMATIC memory card 1
SIMATIC memory card required Yes
Work memory
● integrated (for program) 600 kbyte
● integrated (for data) 2.5 Mbyte
Load memory
● Plug-in (SIMATIC Memory Card), max. 32 Gbyte
Backup
● maintenance-free Yes
CPU processing times
for bit operations, typ. 20 ns
for word operations, typ. 24 ns
for fixed point arithmetic, typ. 32 ns
for floating point arithmetic, typ. 128 ns
CPU-blocks
Number of elements (total) 4 000; Blocks (OB, FB, FC, DB) and UDTs
DB
● Number range 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999
● Size, max. 2.5 Mbyte; For non-optimized block accesses, the max. size of the DB is 64 KB
FB
● Number range 0 ... 65 535
● Size, max. 600 kbyte
FC
● Number range 0 ... 65 535
● Size, max. 600 kbyte
OB
● Size, max. 600 kbyte
● Number of free cycle OBs 100
● Number of time alarm OBs 20
● Number of delay alarm OBs 20
● Number of cyclic interrupt OBs 20; with minimum OB 3x cycle of 10 ms
● Number of process alarm OBs 50
● Number of DPV1 alarm OBs 3
● Number of startup OBs 100
● Number of asynchronous error OBs 4
● Number of synchronous error OBs 2
● Number of diagnostic alarm OBs 1
Nesting depth
● per priority class 24
Counters, timers and their retentivity
S7 counter
● Number 2 048
Retentivity
— can be set Yes
IEC counter
● Number Any (only limited by the main memory)
Retentivity
— can be set Yes
S7 timer
● Number 2 048
Retentivity
— adjustable Yes
IEC timer
● Number Any (only limited by the main memory)
Retentivity
— can be set Yes
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 216 kbyte; in total; for bit memories, timers, counters, DBs, and technology data (axes)
Extended retentive data area (incl. timers, counters, flags), max. 2.5 Mbyte
Flag
● Size, max. 16 kbyte
● Number of clock memories 8; 8 clock memory bit, grouped into one clock memory byte
Data blocks
● Retentivity adjustable Yes
● Retentivity preset No
Local data
● per priority class, max. 64 kbyte; max. 16 KB per block
Address area
Number of IO modules 2 048; max. number of modules / submodules
I/O address area
● Inputs 32 kbyte; All inputs are in the process image
● Outputs 32 kbyte; All outputs are in the process image
per integrated IO subsystem
— Inputs (volume) 8 kbyte
— Outputs (volume) 8 kbyte
Subprocess images
● Number of subprocess images, max. 31
Hardware configuration
Number of distributed IO systems 16; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET, but also by the connection of I/O via IE/PB-Links.
Number of IO Controllers
● integrated 1
Rack
● Modules per rack, max. 5; CPU + 2 PS + 2 CP
Time of day
Clock
● Type Hardware clock
● Backup time 6 wk; At 40 °C ambient temperature, typically
● Deviation per day, max. 10 s; Typ.: 2 s
Operating hours counter
● Number 64
Clock synchronization
● supported Yes
● on Ethernet via NTP Yes
Interfaces
Number of PROFINET interfaces 1
1. Interface
Interface types
● RJ 45 (Ethernet) Yes; X1
● Number of ports 2
● integrated switch Yes
Protocols
● IP protocol Yes; IPv4
● PROFINET IO Controller Yes
● PROFINET IO Device No
● SIMATIC communication Yes; Only Server
● Open IE communication Yes; Optionally also encrypted
● Web server Yes
● Media redundancy Yes
PROFINET IO Controller
Services
— Isochronous mode No
— IRT No
— Dynamic Frame Packing (DFP) Yes
— PROFIenergy Yes; per user program
— Prioritized startup No
— Number of connectable IO Devices, max. 64
— Updating times The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data
Update time for RT
— for send cycle of 1 ms 1 ms to 512 ms
Interface types
RJ 45 (Ethernet)
● 100 Mbps Yes
● Autonegotiation Yes
● Autocrossing Yes
● Industrial Ethernet status LED Yes
Protocols
PROFIsafe No
Number of connections
● Number of connections, max. 128; via integrated interfaces of the CPU and connected CPs
● Number of connections reserved for ES/HMI/web 10
● Number of connections via integrated interfaces 88
● Number of S7 routing paths 16
Redundancy mode
● PROFINET system redundancy (S2) Yes
● PROFINET system redundancy (R1) No
Media redundancy
— Media redundancy Yes; only via 1st interface (X1)
— MRP Yes; MRP Automanager according to IEC 62439-2 Edition 2.0
— MRP interconnection, supported Yes; as MRP ring node according to IEC 62439-2 Edition 3.0
— MRPD No
— Switchover time on line break, typ. 200 ms; PROFINET MRP
— Number of stations in the ring, max. 50; Only 16 are recommended, however
SIMATIC communication
● PG/OP communication Yes; encryption with TLS V1.3 pre-selected
● S7 routing Yes
● S7 communication, as server Yes
● S7 communication, as client No
Open IE communication
● TCP/IP Yes
— Data length, max. 64 kbyte
— several passive connections per port, supported Yes
● ISO-on-TCP (RFC1006) Yes
— Data length, max. 64 kbyte
● UDP Yes
— Data length, max. 2 kbyte; 1 472 bytes for UDP broadcast
— UDP multicast Yes; max. 78 multicast circuits
● DHCP No
● DNS Yes
● SNMP Yes
● DCP Yes
● LLDP Yes
● Encryption Yes; Optional
Web server
● HTTP No
● HTTPS Yes; standard pages
● web API Yes
— Number of sessions, max. 50
— number of simultaneous HTTP calls, max. 4
— HTTP request body, max. 131 072 byte
Specifications
| - | - |
|---|---|
| - | - |