Description

SIMATIC S7-200 SMART, CPU ST20, standard CPU, DC/DC/DC, onboard I/O: 12 DI 24 V DC; 8 DQ 24 V DC; power supply: DC 20.4 - 28.8 V DC, program/data memory 20 KB web server support

General information

Product type designation CPU ST20 DC/DC/DC

Engineering with

● Programming package STEP 7 Micro/WIN SMART

Installation type/mounting

Rail mounting Yes; Standard - DIN rail

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

Current consumption, max. 720 mA; 24 V DC

Inrush current, max. 11.7 A; at 28.8 V

Output current

Current output, max. 300 mA; 24 V DC Sensor Power

for backplane bus (5 V DC), max. 1.4 A; max. 5 V DC for EM bus

Power loss

Power loss, max. 20 W

Storage

Type of memory DDR

Flash Yes

RAM Yes

Memory available for user data 8 kbyte

Memory size 12 kbyte; Program memory

Micro Memory Card Yes; microSDHC Card (optional)

Backup

● present Yes; Maintenance free, RTC requires 7 days.

CPU processing times

for bit operations, typ. 150 ns; / instruction

for word operations, typ. 1.2 µs; / instruction

for floating point arithmetic, typ. 3.6 µs; / instruction

Address area

I/O address area

● Inputs 144 byte; 256 bit of digital inputs & 56 words of analog inputs

● Outputs 144 byte; 256 bit of digital outputs & 56 words of analog outputs

Time of day

Clock

● Type Hardware clock, no battery backup

● Hardware clock (real-time) Yes

● Backup time 7 d

● Deviation per day, max. 120 s; within 120s/month at 25 °C

Digital inputs

Number of digital inputs 12

● of which inputs usable for technological functions 6; HSC (High Speed Counting)

Sourcing/sinking input Yes

Number of simultaneously controllable inputs

all mounting positions

— up to 40 °C, max. 12

Input voltage

● Type of input voltage DC

● Rated value (DC) 24 V

● for signal “0” I0.0 to I0.3 < 1 V DC; I0.4 to I2.7 < 5 V DC

● for signal “1” I0.0 to I0.3 > 4V; I0.4 to I2.7 > 15V

Input current

● for signal “0”, max. (permissible quiescent current) 1 mA

● for signal “1”, typ. 4 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

— at “0” to “1”, min. 0.2 ms

— at “0” to “1”, max. 12.8 ms

for interrupt inputs

— parameterizable Yes

for technological functions

— parameterizable Yes; 6 Single phase: 4 HSCs at 200 kHz; 2 HSCs at 30 kHz 4 A/B phase: 2 HSCs at 100 kHz; 2 HSCs at 20 kHz

Cable length

● shielded, max. 500 m; 50 m for technological functions

● unshielded, max. 300 m; for technological functions: No

Digital outputs

Number of digital outputs 8

● of which high-speed outputs 3; 100 kHz Pulse Train Output

Switching capacity of the outputs

● with resistive load, max. 0.5 A

● on lamp load, max. 5 W

Output voltage

● for signal “1”, min. 20 V DC

Output current

● for signal “1” rated value 0.5 A

● for signal “0” residual current, max. 10 µA

Output delay with resistive load

● “0” to “1”, max. 3 µs; of the standard outputs, max. 3 µs; of the pulse outputs, max. (Q a.0 to Q a.3) 1 µs

● “1” to “0”, max. 200 µs; of the standard outputs, max. 200 µs; of the pulse outputs, max. (Q a.0 to Q a.3) 50 µs

Switching frequency

● of the pulse outputs, with resistive load, max. 100 kHz

Relay outputs

● Number of relay outputs 0

Cable length

● shielded, max. 500 m

● unshielded, max. 150 m

Interfaces

Number of industrial Ethernet interfaces 1

Number of RS 485 interfaces 1

1. Interface

Interface type PROFINET

Isolated Yes; Transformer isolated, 1,500V AC

automatic detection of transmission rate Yes; 10/100 Mbit/s

Autonegotiation Yes

Autocrossing Yes

Interface types

● RJ 45 (Ethernet) Yes

Protocols

● PROFINET IO Controller Yes; Since V2.4

● PROFINET IO Device Yes; I-Device since V2.5

PROFINET IO Controller

● Transmission rate, max. 100 Mbit/s

Services

— Number of connectable IO Devices, max. 8

— Updating time 4 ms; The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

Address area

— Inputs, max. 128 byte; Per device

— Outputs, max. 128 byte; Per device

2. Interface

Interface type RS 485 (max. 187.5 kbps)

Interface types

● RS 485 Yes

PROFIBUS DP master

Services

— S7 communication Yes

Protocols

Supports protocol for PROFINET IO Yes; RT Controller (since FW V2.4) & I-Device (since FW V2.5)

PROFIBUS Yes; Via CM DP module

Protocols (Ethernet)

● TCP/IP Yes

Communication functions

S7 communication

● supported Yes

● as server Yes

● As client Yes

Test commissioning functions

Status/control

● Status/control variable Yes

Forcing

● Forcing Yes

Integrated Functions

Counter

● Number of counters 6

PID controller Yes; PID closed-loop control function: Continuous controller outputs, binary controller outputs, automatic/manual mode, max. 8 loops

Number of pulse outputs 3