CPU1515SP PC2 F - IndOS-6ES7677-2SB43-0GB1

INR 1
DATA SHEET
In stock

Description

SIMATIC ET 200SP Open Controller, CPU 1515SP PC2 F, 8 GB RAM (basic device 6ES7677-2DB40-0AA0), 128 GB CFast with SIMATIC Industrial OS V3.x and S7-1500 Failsafe Software Controller CPU 1505SP F V3x preinstalled; interfaces: 1x slot CFast, 1x slot SD/MMC, 1x connection for ET 200SP BusAdapter PROFINET, 1x 10/100/1000 Mbps Ethernet, 2x USB 3.0, 2x USB 2.0, 1x DisplayPort; documentation on CFast, restore image on SIOS

Product type designation CPU1515SP PC2 F - IndOS

Firmware version V31.1

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode Yes; only with PROFINET; with minimum OB 6x cycle of 500 µs

● SysLog Yes

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V20 (FW V31.1) / V18 (FW V30.0) or higher

Installed software

● Visualization No

● Control S7-1500 Software Controller CPU 1505SP F

Configuration control

via dataset Yes

Control elements

Mode selector switch 1

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Mains buffering

● Mains/voltage failure stored energy time 5 ms

Input current

Current consumption (rated value) 1.8 A; Full processor load, incl. ET 200SP modules and using USB

Current consumption (in no-load operation), typ. 0.5 A

Current consumption, max. 2.9 A

I²t 0.426 A²·s; with starting current inrush

Power

Active power input, max. 43 W; incl. ET 200SP modules and using USB

Infeed power to the backplane bus 8.75 W

Power loss

Power loss, typ. 16 W

Processor

Processor type Intel Atom E3940, 1.6 GHz, 4 cores

Storage

Type of memory DDR3L

Main memory 8 GB RAM

CFast memory card Yes; 128 GB flash memory

SIMATIC memory card required No

Work memory

● integrated (for program) 3 Mbyte

● integrated (for data) 7.5 Mbyte

● integrated (for CPU function library of CPU Runtime) 20 Mbyte

Load memory

● integrated (on PC mass storage) 320 Mbyte

Backup

● with UPS Yes; all memory areas declared retentive

● with non-volatile memory Yes

CPU-blocks

Number of elements (total) 8 000; In addition to blocks such as DBs, FBs and FCs, UDTs, global constants, etc. are also regarded as elements

DB

● Number, max. 7 999; Number range: 1 to 65535

● Size, max. 5 Mbyte

FB

● Number, max. 7 998; Number range: 1 to 65535

● Size, max. 1 024 kbyte

FC

● Number, max. 7 999; Number range: 1 to 65535

● Size, max. 1 024 kbyte

OB

● Size, max. 1 024 kbyte

● Number of free cycle OBs 100

● Number of time alarm OBs 20

● Number of delay alarm OBs 20

● Number of cyclic interrupt OBs 20

● Number of process alarm OBs 50

● Number of DPV1 alarm OBs 3

● Number of isochronous mode OBs 1

● Number of technology synchronous alarm OBs 2

● Number of startup OBs 100

● Number of asynchronous error OBs 4

● Number of synchronous error OBs 2

● Number of diagnostic alarm OBs 1

Nesting depth

● per priority class 24; Up to 8 possible for F-blocks

Counters, timers and their retentivity

S7 counter

● Number 2 048

Retentivity

— can be set Yes

IEC counter

● Number Any (only limited by the main memory)

Retentivity

— can be set Yes

S7 timer

● Number 2 048

Retentivity

— adjustable Yes

IEC timer

● Number Any (only limited by the main memory)

Retentivity

— can be set Yes

Data areas and their retentivity

Retentive data area (incl. timers, counters, flags), max. 410 kbyte; For storage in NVRAM; for storage in mass storage 5 242 020 bytes

Flag

● Size, max. 16 kbyte

● Number of clock memories 8; 8 clock memory bit, grouped into one clock memory byte

Data blocks

● Retentivity adjustable Yes

● Retentivity preset No

Local data

● per priority class, max. 64 kbyte; max. 16 KB per block

Address area

Number of IO modules 8 192

I/O address area

● Inputs 32 kbyte; All inputs are in the process image

● Outputs 32 kbyte; All outputs are in the process image

Subprocess images

● Number of subprocess images, max. 32

Hardware configuration

Integrated power supply Yes

Number of distributed IO systems 20

Number of DP masters

● via CM 1

Number of IO Controllers

● via PC interfaces 1

Rack

● Modules per rack, max. 82; CPU + 64 modules + server module (mounting width max. 1 m) + 16 ET 200AL modules

● Quantity of operable ET 200SP modules, max. 64

● Quantity of operable ET 200AL modules, max. 16

● Number of lines, max. 1

PtP CM

● Number of PtP CMs the number of connectable PtP CMs is only limited by the number of available slots

Time of day

Clock

● Type Hardware clock

● Hardware clock (real-time) Yes; Resolution: 1 s

● Backup time 6 wk; At 40 °C ambient temperature, typically

● Deviation per day, max. 10 s; Typ.: 2 s

Clock synchronization

● supported Yes

● to DP, master Yes; Via CM DP module

● on Ethernet via NTP Yes

● on Windows clock, device Yes

Interfaces

Number of industrial Ethernet interfaces 2

Number of PROFINET interfaces 1

Number of PROFIBUS interfaces 1; Via CM DP module

Number of RS 485 interfaces 1; Via CM DP module

Number of USB interfaces 4; 2x USB 2.0, 2x USB 3.0 on front side

Number of SD card slots 1

Video interfaces

● Graphics interface 1x DisplayPort

1. Interface

Interface type PROFINET

automatic detection of transmission rate Yes

Autonegotiation Yes

Autocrossing Yes

Number of connections 88

Interface types

● RJ 45 (Ethernet) Yes; Via BusAdapter BA 2x RJ45

— Transmission rate, max. 100 Mbit/s

— Industrial Ethernet status LED Yes

● Number of ports 2

● integrated switch Yes

● BusAdapter (PROFINET) Yes; compatible BusAdapters: BA 2x RJ45, BA 2x M12, BA 2x FC, BA 2x LC, BA LC/RJ45, BA LC/FC, BA 2x SCRJ, BA SCRJ/RJ45, BA SCRJ/FC

Protocols

● IP protocol Yes; IPv4

● PROFINET IO Controller Yes

● PROFINET IO Device Yes

● SIMATIC communication Yes

● Open IE communication Yes; Optionally also encrypted

● Web server Yes

● Media redundancy Yes

PROFINET IO Controller

Services

— Isochronous mode Yes

— Direct data exchange Yes; Requirement: IRT and isochronous mode (MRPD optional)

— shortest clock pulse 500 µs

— IRT Yes

— Dynamic Frame Packing (DFP) No

— PROFIenergy Yes

— Prioritized startup Yes; Max. 32 PROFINET devices

— Number of connectable IO Devices, max. 128

— Of which IO devices with IRT, max. 64

— of which in line, max. 64

— Number of connectable IO Devices for RT, max. 128

— of which in line, max. 128

— Number of IO Devices that can be simultaneously activated/deactivated, max. 8

— IO Devices changing during operation (partner ports), supported Yes

— Number of IO Devices per tool, max. 8

— Updating times The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data

— PROFINET Security Class 1

Update time for IRT

— for send cycle of 500 µs 500 µs to 8 ms

— for send cycle of 1 ms 1 ms to 16 ms

— for send cycle of 2 ms 2 ms to 32 ms

— for send cycle of 4 ms 4 ms to 64 ms

— With IRT and parameterization of “odd” send cycles Update time = set “odd” send clock (any multiple of 125 µs: 625 µs ... 3 875 µs) minimum cycle time start from 500 µs

Update time for RT

— for send cycle of 500 µs 500 µs to 256 ms

— for send cycle of 1 ms 1 ms to 512 ms

— for send cycle of 2 ms 2 ms to 512 ms

— for send cycle of 4 ms 4 ms to 512 ms

Address area

— Inputs, max. 8 kbyte

— Outputs, max. 8 kbyte

PROFINET IO Device

Services

— Isochronous mode No

— IRT Yes

— Dynamic Frame Packing (DFP) No

— PROFIenergy Yes; per user program

— Prioritized startup Yes

— Shared device Yes

— Number of IO Controllers with shared device, max. 4

— activation/deactivation of I-devices Yes; per user program

— Asset management record Yes; per user program

— PROFINET Security Class SNMP Configuration and DCP Read Only

2. Interface

Interface type Integrated Ethernet interface

automatic detection of transmission rate Yes

Autonegotiation Yes

Autocrossing Yes

Interface types

● RJ 45 (Ethernet) Yes; Integrated

— Transmission rate, max. 1 000 Mbit/s

— Industrial Ethernet status LED No

● Number of ports 1

3. Interface

Interface type PROFIBUS with CM DP

Number of connections 44

Interface types

● RS 485 Yes

Protocols

● PROFIBUS DP master Yes

● PROFIBUS DP device Yes

● SIMATIC communication Yes

PROFIBUS DP master

● max. number of DP devices 125

Services

— Equidistance No

— Isochronous mode No

Address area

— Inputs, max. 8 kbyte

— Outputs, max. 8 kbyte

Interface types

RS 485

● Transmission rate, max. 12 Mbit/s

Protocols

PROFIsafe Yes

Number of connections

● Number of connections, max. 88

● Number of connections reserved for ES/HMI/web 10

● Number of S7 routing paths 16

Redundancy mode

● PROFINET system redundancy (S2) No

● PROFINET system redundancy (R1) No

Media redundancy

— Media redundancy Yes; only via BusAdapter

— MRP Yes; MRP Automanager according to IEC 62439-2 Edition 2.0, MRP Manager; MRP Client

— MRP interconnection, supported Yes; as MRP ring node according to IEC 62439-2 Edition 3.0

— MRPD Yes; Requirement: IRT

— Switchover time on line break, typ. 200 ms; For MRP, bumpless for MRPD

— Number of stations in the ring, max. 50

SIMATIC communication

● PG/OP communication Yes; encryption with TLS V1.3 pre-selected

● S7 routing Yes

● S7 communication, as server Yes

● S7 communication, as client Yes

● User data per job, max. 64 kbyte; BSEND/BRCV: 64 KB; PUT/GET: 960 bytes

Open IE communication

● TCP/IP Yes

— Data length, max. 64 kbyte

● ISO-on-TCP (RFC1006) Yes

— Data length, max. 64 kbyte

● UDP Yes

— Data length, max. 2 kbyte; 1 472 bytes for UDP broadcast

— UDP multicast Yes; Max. 5 multicast circuits

● DHCP Yes

● DNS Yes

● SNMP Yes

● DCP Yes

● LLDP Yes

● encryption Yes; Optional

Web server

● HTTP Yes; Standard and user pages

● HTTPS Yes; Standard and user pages

● web API

— Number of sessions, max. 50

— number of simultaneous HTTP calls, max. 4

— HTTP request body, max. 131 072 byte

OPC UA

● Runtime license required Yes; “Small” license required

● OPC UA Client Yes; Data access (read, write), method call

— Application authentication Yes

— Security policies Yes; Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256

— User authentication Yes; “anonymous” or by user name & password

— Number of connections, max. 10

— Number of nodes of the client interfaces, recommended max. 2 000

— Number of elements for one call of OPC_UA_NodeGetHandleList/OPC_UA_ReadList/OPC_UA_WriteList, max. 300

— Number of elements for one call of OPC_UA_NameSpaceGetIndexList, max. 20

— Number of elements for one call of OPC_UA_MethodGetHandleList, max. 100

— Number of simultaneous calls of the client instructions for session management, per connection, max. 1

— Number of simultaneous calls of the client instructions for data access, per connection, max. 5

— Number of registerable nodes, max. 5 000

— Number of registerable method calls of OPC_UA_MethodCall, max. 100

— Number of inputs/outputs when calling OPC_UA_MethodCall, max. 20

● OPC UA Server Yes; Data access (read, write, subscribe), method call, custom address space

— Application authentication Yes

— Security policies Yes; Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256

— User authentication Yes

— GDS support (certificate management) Yes

— Number of sessions, max. 48

— Number of accessible variables, max. 100 000

— Number of registerable nodes, max. 20 000

— Number of subscriptions per session, max. 50

— Sampling interval, min. 100 ms

— Publishing interval, min. 200 ms

— Number of server methods, max. 50

— Number of inputs/outputs per server method, max. 20

— Number of monitored items, recommended max. 2 000; for 1 s sampling interval and 1 s send interval

— Number of server interfaces, max. 10

— Number of nodes for user-defined server interfaces, max. 5 000

● Alarms and Conditions Yes

— Number of program alarms 200

— Number of alarms for system diagnostics 100

Further protocols

● MODBUS Yes; MODBUS TCP

S7 message functions

Number of login stations for message functions, max. 32

Program alarms Yes

Number of configurable program messages, max. 10 000

Number of simultaneously active program alarms 1 000

● Number of program alarms 1 000

● Number of alarms for system diagnostics 200

● Number of alarms for motion technology objects 160

Test commissioning functions

Joint commission (Team Engineering) Yes; Parallel online access possible for up to 10 engineering systems

Status block Yes; up to 8 simultaneously

Single step Yes

Number of breakpoints 8

Profiling No

Status/control

● Status/control variable Yes

● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

● Number of variables, max.

— of which status variables, max. 200; per job

— of which control variables, max. 200; per job

Forcing

● Forcing Yes

● Forcing, variables Peripheral inputs/outputs

● Number of variables, max. 200

Diagnostic buffer

● present Yes

● Number of entries, max. 1 000

— of which powerfail-proof 300

Traces

● Number of configurable Traces 4

● Memory size per trace, max. 512 kbyte

Interrupts/diagnostics/status information

Diagnostics indication LED

● RUN/STOP LED Yes

● ERROR LED Yes

● MAINT LED Yes

Supported technology objects

Motion Control Yes; Note: The number of technology objects affects the cycle time of the PLC program; selection guide via the TIA Selection Tool or SIZER

● Number of available Motion Control resources for technology objects 2 400

● Required Motion Control resources

— per speed-controlled axis 40

— per positioning axis 80

— per synchronous axis 160

— per external encoder 80

— per output cam 20

— per cam track 160

— per probe 40

● Positioning axis

— Number of positioning axes at motion control cycle of 4 ms (typical value) 30

— Number of positioning axes at motion control cycle of 8 ms (typical value) 30

Controller

● PID_Compact Yes; Universal PID controller with integrated optimization

● PID_3Step Yes; PID controller with integrated optimization for valves

● PID-Temp Yes; PID controller with integrated optimization for temperature

Counting and measuring

● High-speed counter Yes

Standards, approvals, certificates

CE mark Yes

CSA approval Yes

cULus Yes

FM approval Yes

RCM (formerly C-TICK) Yes

Highest safety class achievable in safety mode

● Performance level according to ISO 13849-1 PLe

● SIL acc. to IEC 61508 Up to SIL 3

Probability of failure (for service life of 20 years and repair time of 100 hours)

— Low demand mode: PFDavg in accordance with SIL3 < 2.00E-05

— High demand/continuous mode: PFH in accordance with SIL3 < 1.00E-09