S7-1200 G1 by SIEMENS

Digital I/O SM 1223, 8 DI / 8 DO-6ES7223-1BH32-0XB0

INR 1
Learn more
In stock

Description

SIMATIC S7-1200, Digital I/O SM 1223, 8 DI/8 DO, 8 DI 24 V DC, Sink/Source, 8 DO, transistor 0.5 A

General information

Product type designation SM 1223, DI 8x24 V DC, DQ 8x24 V DC

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from backplane bus 5 V DC, max. 145 mA

Digital inputs

● from load voltage L+ (without load), max. 4 mA; per channel

Output voltage

Power supply to the transmitters

● present Yes

Power loss

Power loss, typ. 2.5 W

Digital inputs

Number of digital inputs 8

● in groups of 2

Input characteristic curve in accordance with IEC 61131, type 1 Yes

Number of simultaneously controllable inputs

all mounting positions

— up to 40 °C, max. 8

horizontal installation

— up to 40 °C, max. 8

— up to 50 °C, max. 8

vertical installation

— up to 40 °C, max. 8

Input voltage

● Rated value (DC) 24 V

● for signal “0” 5 V DC at 1 mA

● for signal “1” 15 V DC at 2.5 mA

Input current

● for signal “0”, max. (permissible quiescent current) 1 mA

● for signal “1”, min. 2.5 mA

● for signal “1”, typ. 4 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

for interrupt inputs

— parameterizable Yes

Cable length

● shielded, max. 500 m

● unshielded, max. 300 m

Digital outputs

Number of digital outputs 8

● in groups of 1

Short-circuit protection No; to be provided externally

Limitation of inductive shutdown voltage to L+ (-48 V)

Switching capacity of the outputs

● with resistive load, max. 0.5 A

● on lamp load, max. 5 W

Output voltage

● Rated value (DC) 24 V

● for signal “0”, max. 0.1 V; with 10 kOhm load

● for signal “1”, min. 20 V DC

Output current

● for signal “1” rated value 0.5 A

● for signal “1” permissible range, max. 0.5 A

● for signal “0” residual current, max. 10 µA

Output delay with resistive load

● “0” to “1”, max. 50 µs

● “1” to “0”, max. 200 µs

Total current of the outputs (per group)

horizontal installation

— up to 50 °C, max. 4 A; Current per mass

Cable length

● shielded, max. 500 m

● unshielded, max. 150 m

Interrupts/diagnostics/status information

Alarms

● Diagnostic alarm Yes

Diagnostics indication LED

● for status of the inputs Yes

● for status of the outputs Yes

Potential separation

Potential separation digital inputs

● between the channels, in groups of 2

Potential separation digital outputs

● between the channels, in groups of 1

● between the channels and backplane bus 500 V AC