S7-200 SMART by siemens

Digital I/O SM DR32,16DI/16DO, RELAIS-6ES7288-2DR32-0AA0

INR 1
Learn more
In stock

Description

SIMATIC S7-200 SMART, Digital I/O SM DR32, 16DI/16DO, 16 DI 24 V DC, Sink/Source, 16 DO, relay 2 A

General information

Product type designation SM DR32, DI 16x24 V DC, DQ 16x relay/2A

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

Current consumption, typ. 165 mA; Current for 24 V DC input power

from backplane bus 5 V DC, typ. 165 mA; For 5 V DC from CPU module

Digital inputs

Number of digital inputs 16

● in groups of 2

Parallel switching of inputs Yes

Input characteristic curve in accordance with IEC 61131, type 1 Yes

Number of simultaneously controllable inputs

horizontal installation

— up to 50 °C, max. 16

vertical installation

— up to 40 °C, max. 16

Input voltage

● Type of input voltage DC

● Rated value (DC) 24 V

● for signal “0” < 5 V DC

● for signal “1” +15 to +30 V

Input current

● for signal “0”, max. (permissible quiescent current) 1 mA

● for signal “1”, min. 2.5 mA

● for signal “1”, max. 5 mA

● for signal “1”, typ. 4 mA

Input delay (for rated value of input voltage)

for standard inputs

— at “0” to “1”, max. 200 µs

— at “1” to “0”, max. 200 µs

Cable length

● shielded, max. 500 m

● unshielded, max. 300 m

Digital outputs

Number of digital outputs 16

Short-circuit protection No

Output current

● for signal “1” rated value 2 A

Output delay with resistive load

● “0” to “1”, max. 10 ms

● “1” to “0”, max. 10 ms

Relay outputs

● Number of relay outputs 16

● Rated supply voltage of relay coil L+ (DC) 24 V

— Reverse polarity protection Yes

● Current consumption of relays (coil current of all relays), max. 165 mA

Switching capacity of contacts

— with inductive load, max. 2 A

— on lamp load, max. 30 W; 30 W with DC, 200 W with AC

— with resistive load, up to 50 °C, max. 2 A

— with resistive load, up to 60 °C, max. 2 A

— with resistive load, max. 2 A

— Thermal continuous current, max. 2 A

Cable length

● shielded, max. 500 m

● unshielded, max. 150 m

Interrupts/diagnostics/status information

Diagnostics indication LED

● for status of the inputs Yes

● for status of the outputs Yes

Potential separation

Potential separation digital inputs

● between the channels Yes; Optocoupler

Potential separation digital outputs

● between the channels Yes; Relay, dry contact

Isolation

Isolation tested with 500 V AC for 1 minute for input isolation; 1500 V AC for 1 minute for output isolation

EMC

Interference immunity against discharge of static electricity

● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes; ±4 kV contact discharge (to IEC 801-2/IEC 1000-4-2; ESD), ±8 kV air discharge (to IEC 801-2/IEC 1000-4-2; ESD)

— Test voltage at air discharge 8 kV

— Test voltage at contact discharge 4 kV

Interference immunity against high-frequency electromagnetic fields

● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 Yes

— Frequency range of the RF radiation 80 to 1000 MHz, 10 V/m, 1.4 to 2.0 GHz, 3 V/m, 2.0 to 2.7 GHz, 1 V/m(In the range of 87 MHz to 187 MHz, 174 MHz to 230 MHz and 470 MHz to 790 MHz: 3V/m )

Interference immunity to cable-borne interference

● Interference immunity on supply lines acc. to IEC 61000-4-4 Yes; 2 kV acc. to IEC 61000-4-4, burst

● Interference immunity on signal cables acc. to IEC 61000-4-4 Yes; ±2 kV acc. to IEC 61000-4-4, Burst

Interference immunity against voltage surge

● Interference immunity on supply lines acc. to IEC 61000-4-5 Yes; With upstream protective element

Interference immunity against conducted variable disturbance induced by high-frequency fields

● Interference immunity against high frequency current feed acc. to IEC 61000-4-6 Yes

● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes; 10 V/m, with 80% amplitude modulation at 1 kHz

— Test voltage at 80% amplitude modulation with 1kHz in the range 9 kHz to 80 MHz 10 V

Emission of radio interference acc. to EN 55 011

● Emission of radio interference Interference emission to EN 50081-2, testing to EN 55011, Class A, Group 1

● Limit class A, for use in industrial areas Yes

Degree and class of protection

IP degree of protection IP20

Standards, approvals, certificates

CE mark Yes

Dimensions

Width 70 mm

Height 100 mm

Depth 81 mm

Weights

Weight, approx. 295.4 g