Description
SIMATIC S7-200 SMART, Digital input EM DI16, 16 DI, 24V DC, Sink/Source
General information
Product type designation SM DI16, DI 16x24 V DC
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
Current consumption, typ. 4 mA; Current for 24 V DC input per channel
Current consumption, max. 5 mA; Current for 30 V DC input per channel
from backplane bus 5 V DC, typ. 85 mA; For 5 V DC from CPU module
from backplane bus 5 V DC, max. 105 mA; For 5 V DC from CPU module
Digital inputs
Number of digital inputs 16
● in groups of 4
Parallel switching of inputs Yes
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 16
horizontal installation
— up to 50 °C, max. 16
vertical installation
— up to 40 °C, max. 16
Input voltage
● Type of input voltage DC
● Rated value (DC) 24 V
● for signal “0” < 5 V DC
● for signal “1” +15 to +30 V
Input current
● for signal “0”, max. (permissible quiescent current) 1 mA
● for signal “1”, min. 2.5 mA
● for signal “1”, max. 5.5 mA
● for signal “1”, typ. 4 mA
Input delay (for rated value of input voltage)
for standard inputs
— at “0” to “1”, max. 200 µs
— at “1” to “0”, max. 200 µs
Cable length
● shielded, max. 500 m
● unshielded, max. 300 m
Digital outputs
Number of digital outputs 0
Cable length
● shielded, max. 500 m
● unshielded, max. 300 m
Interrupts/diagnostics/status information
Diagnostics indication LED
● for status of the inputs Yes
Potential separation
Potential separation digital inputs
● between the channels Yes; Optocoupler
● between the channels, in groups of 4
Isolation
Isolation tested with 1 500 V AC for 1 minute
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes; ±4 kV contact discharge (to IEC 801-2/IEC 1000-4-2; ESD), ±8 kV air discharge (to IEC 801-2/IEC 1000-4-2; ESD)
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 4 kV
Interference immunity against high-frequency electromagnetic fields
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 Yes; 10 V/m, 80 to 1 000 MHz (to IEC 61000-4-3); 10 V/m, 900 MHz, 1.89 GHz, 50% ED (to IEC 61000-4-3)
— Frequency range of the RF radiation 80 to 1000 MHz, 10 V/m, 1.4 to 2.0 GHz, 3 V/m, 2.0 to 2.7 GHz, 1 V/m
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to IEC 61000-4-4 Yes; ±2 kV acc. to IEC 61000-4-4, burst; surge measurements with additional protective elements
● Interference immunity on signal cables acc. to IEC 61000-4-4 Yes; ±2 kV acc. to IEC 61000-4-4, Burst
Interference immunity against voltage surge
● Interference immunity on supply lines acc. to IEC 61000-4-5 Yes; Surge measurements with additional protection elements: ±1 kV (to IEC 61000-4-5; µs pulse / line to line);±2 kV (to IEC 61000-4-5; µs pulse / line to ground)
● asymmetric interference ±2 kV acc. to IEC 61000-4-5, surge asymmetric
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high frequency current feed acc. to IEC 61000-4-6 Yes; 10 V, 150 kHz to 80 MHz (to IEC 61000-4-6)
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes; 10 V/m, with 80% amplitude modulation at 1 kHz, 10 kHz to 80 MHz (acc. to IEC 61000-4-6)
— Test voltage at 80% amplitude modulation with 1kHz in the range 9 kHz to 80 MHz 10 V
Emission of radio interference acc. to EN 55 011
● Emission of radio interference Interference emission to EN 50081-2, testing to EN 55011, Class A, Group 1
● Limit class A, for use in industrial areas Yes; EN 61000-6-4, interference emission: Intended for use in industrial areas.
Degree and class of protection
IP degree of protection IP20
Standards, approvals, certificates
CE mark Yes; CE marking / EC Declaration of Conformity