Description

SIMATIC S7-1200, Digital input SM 1226, F-DI 16X 24 V DC, PROFIsafe, 70 mm overall width, up to PL E (ISO 13849-1)/ SIL3 (IEC 61508)

General information

Product type designation SM 1226, F-DI 16x24 V DC

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

power supply according to NEC Class 2 required No

Input current

from backplane bus 5 V DC, max. 155 mA; Current consumption (SM Bus, 5 V DC): 155 mA

Digital inputs

● from load voltage L+ (without load), max. 130 mA; 130 mA + 6 mA / input used + any Vs1/Vs2 current used

Power loss

Power loss, typ. 7 W

Digital inputs

Number of digital inputs 16; 16 (1oo1) or 8 (1oo2); Note: You can individually assign each pair of inputs “a.x” and “b.x” as a single (1oo2)-channel or as 2 separate (1oo1)-channels

Number of simultaneously controllable inputs

horizontal installation

— up to 50 °C, max. 16; 16 inputs at 55 °C horizontal

vertical installation

— up to 40 °C, max. 16; 16 inputs at 45 °C vertical

Input voltage

● for signal “0” -30 V DC to +5 V DC

● for signal “1” 15 V DC to 30 V DC

Input current

● for signal “0”, max. (permissible quiescent current) 0.5 mA

● for signal “1”, typ. 5 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable Yes; 0.8 / 1.6 / 3.2 / 6.4 / 12.8 ms

Cable length

● shielded, max. 200 m; unshielded with input filter time of 1.6 ms to 12.6 ms (With an input delay of 0.8 ms, shielded cables must be used for the digital inputs and the sensor supply)

● unshielded, max. 200 m; Shielded with input filter time of 0.8 ms to 12.6 s (With an input delay of 0.8 ms, shielded cables must be used for the digital inputs and the sensor supply)

Interrupts/diagnostics/status information

Diagnostics indication LED

● for status of the inputs Yes

Degree and class of protection

IP degree of protection IP20

Standards, approvals, certificates

CE mark Yes

cULus Yes

FM approval Yes

Highest safety class achievable in safety mode

● Performance level according to ISO 13849-1 1-channel, Category 3, PL d; 2-channel, Category 3 or 4, PL e

● SIL acc. to IEC 61508 SIL 2 (single-channel), SIL 3 (two-channel)

Probability of failure (for service life of 20 years and repair time of 100 hours)

— Low demand mode: PFDavg in accordance with SIL2 < 5.00E-04

— Low demand mode: PFDavg in accordance with SIL3 < 1.00E-05

— High demand/continuous mode: PFH in accordance with SIL2 < 1.00E-08 1/h

— High demand/continuous mode: PFH in accordance with SIL3 < 1.00E-10 1/h

Ambient conditions

Free fall

● Fall height, max. 0.3 m; five times, in product package

Ambient temperature during operation

● min. 0 °C

● max. 55 °C

● permissible temperature change 5°C to 55°C, 3°C / minute

Ambient temperature during storage/transportation

● min. -40 °C

● max. 70 °C

Air pressure acc. to IEC 60068-2-13

● Storage/transport, min. 660 hPa

● Storage/transport, max. 1 080 hPa

Relative humidity

● Operation at 25 ℃ without condensation, max. 95 %

Mechanics/material

Enclosure material (front)

● plastic Yes

Dimensions

Width 70 mm

Height 100 mm

Depth 75 mm

Weights

Weight, approx. 250 g