S7-1200 G1 by SIEMENS

Digital I/O SM 1223, 16DI/16DO sink-6ES7223-1BL32-1XB0

INR 1
Learn more
In stock

Description

SIMATIC S7-1200, Digital I/O SM 1223, 16 DI/16 DO, 16 DI 24 V DC; sourcing/sinking input, 16 DO, sourcing (sinking output), NPN transistor 0.5 A

General information

Product type designation SM 1223, DI 16x24 V DC, DO 16x 24 V DC Sink

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from backplane bus 5 V DC, max. 185 mA

Digital inputs

● from load voltage L+ (without load), max. 4 mA; per channel

Output voltage

Power supply to the transmitters

● present Yes

Power loss

Power loss, typ. 4.5 W

Digital inputs

Number of digital inputs 16

● in groups of 2

Input characteristic curve in accordance with IEC 61131, type 1 Yes

Number of simultaneously controllable inputs

all mounting positions

— up to 40 °C, max. 16

horizontal installation

— up to 40 °C, max. 16

— up to 50 °C, max. 16

vertical installation

— up to 40 °C, max. 16

Input voltage

● Rated value (DC) 24 V

● for signal “0” 5 V DC at 1 mA

● for signal “1” 15 V DC at 2.5 mA

Input current

● for signal “0”, max. (permissible quiescent current) 1 mA

● for signal “1”, min. 2.5 mA

● for signal “1”, typ. 4 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

for interrupt inputs

— parameterizable Yes

Cable length

● shielded, max. 500 m

● unshielded, max. 300 m

Digital outputs

Number of digital outputs 16; Transistor current sinking

● in groups of 1

Short-circuit protection Yes; 1 to 3.5 A

Limitation of inductive shutdown voltage to Typ 45 V

Switching capacity of the outputs

● with resistive load, max. 0.5 A

● on lamp load, max. 5 W

Output voltage

● Rated value (DC) 24 V

● for signal “0”, max. L+ minus 0.75 V DC with 10k Load

● for signal “1”, min. 0,5 V

Output current

● for signal “1” rated value 0.5 A

● for signal “1” permissible range, max. 0.5 A

● for signal “0” residual current, max. 75 µA

Output delay with resistive load

● “0” to “1”, max. 20 µs

● “1” to “0”, max. 350 µs

Total current of the outputs (per group)

horizontal installation

— up to 50 °C, max. 8 A; Current per mass

Relay outputs

Switching capacity of contacts

— with inductive load, max. 0.5 A

— on lamp load, max. 5 W

— with resistive load, max. 0.5 A

Cable length

● shielded, max. 500 m

● unshielded, max. 150 m

Interrupts/diagnostics/status information

Alarms

● Diagnostic alarm Yes

Diagnostics indication LED

● for status of the inputs Yes

● for status of the outputs Yes

Potential separation

Potential separation digital inputs

● between the channels, in groups of 2

Potential separation digital outputs

● between the channels, in groups of 1

● between the channels and backplane bus 500 V AC

Degree and class of protection

IP degree of protection IP20

Standards, approvals, certificates

CE mark Yes

CSA approval Yes

UL approval Yes

cULus Yes

FM approval Yes

RCM (formerly C-TICK) Yes

KC approval Yes

Marine approval Yes

Ambient conditions

Free fall

● Fall height, max. 0.3 m; five times, in product package

Ambient temperature during operation

● min. -20 °C

● max. 60 °C

● horizontal installation, min. -20 °C

● horizontal installation, max. 60 °C

● vertical installation, min. -20 °C

● vertical installation, max. 50 °C

● permissible temperature change 5°C to 55°C, 3°C / minute

Ambient temperature during storage/transportation

● min. -40 °C

● max. 70 °C

Air pressure acc. to IEC 60068-2-13

● Storage/transport, min. 660 hPa

● Storage/transport, max. 1 080 hPa

Relative humidity

● Operation at 25 ℃ without condensation, max. 95 %

Connection method

required front connector Yes

Mechanics/material

Enclosure material (front)

● Plastic Yes

Dimensions

Width 70 mm

Height 100 mm

Depth 75 mm

Weights

Weight, approx. 310 g