S7-1200 G1 by siemens

Digital I/O SM 1223, 8DI/8DO-6ES7223-1PH32-0XB0

INR 1
Learn more
In stock

Description

SIMATIC S7-1200, Digital I/O SM 1223, 8 DI/8 DO, 8 DI 24 V DC, Sink/Source, 8 DO, relay 2 A

General information

Product type designation SM 1223, DI 8x24 V DC, DQ 8x relay

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from backplane bus 5 V DC, max. 145 mA

Digital inputs

● from load voltage L+ (without load), max. 4 mA/input 11 mA/relay

Output voltage

Power supply to the transmitters

● present Yes

Power loss

Power loss, typ. 5.5 W

Digital inputs

Number of digital inputs 8

● in groups of 2

Input characteristic curve in accordance with IEC 61131, type 1 Yes

Number of simultaneously controllable inputs

all mounting positions

— up to 40 °C, max. 8

horizontal installation

— up to 40 °C, max. 8

— up to 50 °C, max. 8

vertical installation

— up to 40 °C, max. 8

Input voltage

● Rated value (DC) 24 V

● for signal “0” 5 V DC at 1 mA

● for signal “1” 15 V DC at 2.5 mA

Input current

● for signal “0”, max. (permissible quiescent current) 1 mA

● for signal “1”, min. 2.5 mA

● for signal “1”, typ. 4 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

for interrupt inputs

— parameterizable Yes

Cable length

● shielded, max. 500 m

● unshielded, max. 300 m

Digital outputs

Number of digital outputs 8

● in groups of 2

Short-circuit protection No; to be provided externally

Switching capacity of the outputs

● with resistive load, max. 2 A

● on lamp load, max. 30 W with DC, 200 W with AC

Output voltage

● Rated value (DC) 5 V DC to 30 V DC

● Rated value (AC) 5 V AC to 250 V AC

Output current

● for signal “1” rated value 2 A

● for signal “1” permissible range, max. 2 A

Output delay with resistive load

● “0” to “1”, max. 10 ms

● “1” to “0”, max. 10 ms

Total current of the outputs (per group)

horizontal installation

— up to 50 °C, max. 10 A; Current per mass

Relay outputs

● Number of relay outputs 8

● Rated supply voltage of relay coil L+ (DC) 24 V

● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000

Switching capacity of contacts

— with inductive load, max. 2 A

— on lamp load, max. 30 W with DC, 200 W with AC

— with resistive load, max. 2 A

Cable length

● shielded, max. 500 m

● unshielded, max. 150 m

Interrupts/diagnostics/status information

Alarms

● Diagnostic alarm Yes

Diagnostics indication LED

● for status of the inputs Yes

● for status of the outputs Yes

Potential separation

Potential separation digital inputs

● between the channels, in groups of 2

Potential separation digital outputs

● between the channels Relays

● between the channels, in groups of 2

● between the channels and backplane bus 1 500 V AC for 1 minute

Permissible potential difference

between different circuits 750 V AC for 1 minute

Degree and class of protection

IP degree of protection IP20

Standards, approvals, certificates

CE mark Yes

CSA approval Yes

UL approval Yes

cULus Yes

FM approval Yes

RCM (formerly C-TICK) Yes

KC approval Yes

Marine approval Yes

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 123 kg

— global warming potential, (during production) [CO2 eq] 12.1 kg

— global warming potential, (during operation) [CO2 eq] 111 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.434 kg