General information

Product type designation SM DR16, DI 8x24 V DC, DQ 8x relay/2 A

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

Current consumption, typ. 80 mA; Current for 24 V DC input power

from backplane bus 5 V DC, typ. 115 mA; For 5 V DC from CPU module

Digital inputs

Number of digital inputs 8

● in groups of 2

Parallel switching of inputs Yes

Input characteristic curve in accordance with IEC 61131, type 1 Yes

Number of simultaneously controllable inputs

horizontal installation

— up to 50 °C, max. 8

vertical installation

— up to 40 °C, max. 8

Input voltage

● Type of input voltage DC

● Rated value (DC) 24 V

● for signal “0” < 5 V DC

● for signal “1” +15 to +30 V

Input current

● for signal “0”, max. (permissible quiescent current) 1 mA

● for signal “1”, min. 2.5 mA

● for signal “1”, max. 5 mA

● for signal “1”, typ. 4 mA

Input delay (for rated value of input voltage)

for standard inputs

— at “0” to “1”, max. 200 µs

— at “1” to “0”, max. 200 µs

Cable length

● shielded, max. 500 m

● unshielded, max. 300 m

Digital outputs

Number of digital outputs 8

Short-circuit protection No

Output current

● for signal “1” rated value 2 A

Output delay with resistive load

● “0” to “1”, max. 10 ms

● “1” to “0”, max. 10 ms

Parallel switching of two outputs

● for logic links No

● for uprating No

● for redundant control of a load No

Relay outputs

● Number of relay outputs 8

● Rated supply voltage of relay coil L+ (DC) 24 V

— Reverse polarity protection Yes

● Current consumption of relays (coil current of all relays), max. 80 mA

Switching capacity of contacts

— with inductive load, max. 2 A

— on lamp load, max. 30 W; 30 W with DC, 200 W with AC

— with resistive load, up to 50 °C, max. 2 A

— with resistive load, up to 60 °C, max. 2 A

— with resistive load, max. 2 A

— Thermal continuous current, max. 2 A

Cable length

● shielded, max. 500 m

● unshielded, max. 150 m

Interrupts/diagnostics/status information

Diagnostics indication LED

● for status of the inputs Yes

● for status of the outputs Yes

Potential separation

Potential separation digital inputs

● between the channels Yes; Optocoupler

Potential separation digital outputs

● between the channels Yes; Relay, dry contact

Isolation

Isolation tested with 500 V AC for 1 minute for input isolation; 1500 V AC for 1 minute for output isolation

EMC

Interference immunity against discharge of static electricity

● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes; ±4 kV contact discharge (to IEC 801-2/IEC 1000-4-2; ESD), ±8 kV air discharge (to IEC 801-2/IEC 1000-4-2; ESD)

— Test voltage at air discharge 8 kV

— Test voltage at contact discharge 4 kV

Interference immunity against high-frequency electromagnetic fields

● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 Yes

— Frequency range of the RF radiation 80 to 1000 MHz, 10 V/m, 1.4 to 2.0 GHz, 3 V/m, 2.0 to 2.7 GHz, 1 V/m(In the range of 87 MHz to 187 MHz, 174 MHz to 230 MHz and 470 MHz to 790 MHz: 3V/m )

Interference immunity to cable-borne interference

● Interference immunity on supply lines acc. to IEC 61000-4-4 Yes; 2 kV acc. to IEC 61000-4-4, burst

● Interference immunity on signal cables acc. to IEC 61000-4-4 Yes; ±2 kV acc. to IEC 61000-4-4, Burst

Interference immunity against voltage surge

● Interference immunity on supply lines acc. to IEC 61000-4-5 Yes; With upstream protective element

Interference immunity against conducted variable disturbance induced by high-frequency fields

● Interference immunity against high frequency current feed acc. to IEC 61000-4-6 Yes

● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes; 10 V/m, with 80% amplitude modulation at 1 kHz

— Test voltage at 80% amplitude modulation with 1kHz in the range 9 kHz to 80 MHz 10 V

Emission of radio interference acc. to EN 55 011

● Emission of radio interference Interference emission to EN 50081-2, testing to EN 55011, Class A, Group 1

● Limit class A, for use in industrial areas Yes

Degree and class of protection

IP degree of protection IP20

Standards, approvals, certificates

CE mark Yes

Ambient conditions

Relative humidity

● Operation at 25 ℃ without condensation, max. 95 %

Dimensions

Width 45 mm

Height 100 mm

Depth 81 mm

Weights

Weight, approx. 201.9 g