S7-1200 G1 by SIEMENS

Digital Output SM1222, 16 DO, 24V DC-6ES7222-1BH32-0XB0

INR 1
DATA SHEET
In stock

Description

SIMATIC S7-1200, Digital output SM 1222, 16 DO, 24 V DC, transistor 0.5 A

General information

Product type designation SM 1222, DQ 16x24 V DC/0.5 A

Supply voltage

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from backplane bus 5 V DC, max. 140 mA

Power loss

Power loss, typ. 2.5 W

Digital outputs

Number of digital outputs 16

● in groups of 1

Short-circuit protection No; to be provided externally

Limitation of inductive shutdown voltage to typ. (L+) -48 V

Switching capacity of the outputs

● with resistive load, max. 0.5 A

● on lamp load, max. 5 W

Output voltage

● Rated value (DC) 24 V

● for signal “0”, max. 0.1 V; with 10 kOhm load

● for signal “1”, min. 20 V DC

Output current

● for signal “1” rated value 0.5 A

● for signal “0” residual current, max. 10 µA

Output delay with resistive load

● “0” to “1”, max. 50 µs

● “1” to “0”, max. 200 µs

Total current of the outputs (per group)

horizontal installation

— up to 50 °C, max. 8 A; Current per mass

Cable length

● shielded, max. 500 m

● unshielded, max. 150 m

Interrupts/diagnostics/status information

Alarms

● Diagnostic alarm Yes

Diagnostics indication LED

● for status of the outputs Yes

Potential separation

Potential separation digital outputs

● between the channels, in groups of 1

● between the channels and backplane bus 500 V AC

Degree and class of protection

IP degree of protection IP20

Standards, approvals, certificates

CE mark Yes

CSA approval Yes

UL approval Yes

cULus Yes

FM approval Yes

RCM (formerly C-TICK) Yes

KC approval Yes

Marine approval Yes

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 68.6 kg

— global warming potential, (during production) [CO2 eq] 8.16 kg

— global warming potential, (during operation) [CO2 eq] 60.7 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.334 kg

Ambient conditions

Free fall

● Fall height, max. 0.3 m; five times, in product package

Ambient temperature during operation

● min. -20 °C

● max. 60 °C

● horizontal installation, min. -20 °C

● horizontal installation, max. 60 °C

● vertical installation, min. -20 °C

● vertical installation, max. 50 °C

● permissible temperature change 5°C to 55°C, 3°C / minute

Ambient temperature during storage/transportation

● min. -40 °C

● max. 70 °C

Air pressure acc. to IEC 60068-2-13

● Storage/transport, min. 660 hPa

● Storage/transport, max. 1 080 hPa

Relative humidity

● Operation at 25 ℃ without condensation, max. 95 %

Connection method

required front connector Yes

Mechanics/material

Enclosure material (front)

● plastic Yes

Dimensions

Width 45 mm

Height 100 mm

Depth 75 mm

Weights

Weight, approx. 220 g