SIMATIC ET 200SP, Analog input module, AI 2x U/I 2-.4-wire High Speed, suitable for BU type A0, A1, Color code CC00, channel diagnostics, 16 bit, +/-0.3%
General information
Product type designation AI 2xU/I 2-/4-wire HS
HW functional status from FS21
Firmware version V2.0.3
● FW update possible Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color-coded label CC00
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes; 125 µs
● Measuring range scalable No
● Scalable measured values No
● Adjustment of measuring range No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13 SP1
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher
● PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode
● Oversampling Yes; 2 channels per module
● MSI No
CiR - Configuration in RUN
Reparameterization possible in RUN No
Calibration possible in RUN No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption (rated value) 39 mA; without sensor supply
Encoder supply
24 V encoder supply
● 24 V Yes; For current measurement
● Short-circuit protection Yes
● Output current, max. 20 mA; max. 50 mA per channel for a duration < 10 s
Power loss
Power loss, typ. 0.95 W; without sensor supply
Address area
Address space per module
● Address space per module, max. 4 byte; + 1 byte for QI information (32 bytes in the oversampling operating mode)
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element Type A
Selection of BaseUnit for connection variants
● 2-wire connection BU type A0, A1
● 4-wire connection BU type A0, A1
Analog inputs
Number of analog inputs 2; Differential inputs
● For current measurement 2
● For voltage measurement 2
permissible input voltage for voltage input (destruction limit), max. 30 V
permissible input current for current input (destruction limit), max. 50 mA
Cycle time (all channels), min. 125 µs
Analog input with oversampling Yes
● Values per cycle, max. 16
● Resolution, min. 50 µs
Input ranges (rated values), voltages
● 0 to +10 V Yes; 15 bit
— Input resistance (0 to 10 V) 75 kΩ
● 1 V to 5 V Yes; 13 bit
— Input resistance (1 V to 5 V) 75 kΩ
● -10 V to +10 V Yes; 16 bit incl. sign
— Input resistance (-10 V to +10 V) 75 kΩ
● -5 V to +5 V Yes; 15 bit incl. sign
— Input resistance (-5 V to +5 V) 75 kΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes; 15 bit
— Input resistance (0 to 20 mA) 130 Ω
● -20 mA to +20 mA Yes; 16 bit incl. sign
— Input resistance (-20 mA to +20 mA) 130 Ω
● 4 mA to 20 mA Yes; 14 bit
— Input resistance (4 mA to 20 mA) 130 Ω
Cable length
● shielded, max. 1 000 m; 200 m for voltage measurement
Analog value generation for the inputs
Measurement principle Actual value encryption (successive approximation)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Interference voltage suppression for interference frequency f1 in Hz No
● Conversion time (per channel) 10 µs
Smoothing of measured values
● Number of smoothing levels 7; none; 2-/4-/8-/16-/32-/64-fold
● Parameterizable Yes
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 650 Ω
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.03 %
Temperature error (relative to input range), (+/-) 0.01 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.1 %
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.3 %
● Current, relative to input range, (+/-) 0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.2 %
● Current, relative to input range, (+/-) 0.2 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode voltage, max. 35 V
● Common mode interference, min. 90 dB
Isochronous mode
Filtering and processing time (TCI), min. 80 µs
Bus cycle time (TDP), min. 125 µs; Starting from firmware Version V2.0.1
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm Yes
● Limit value alarm Yes; two upper and two lower limit values in each case
Diagnoses
● Wire break Yes; channel-by-channel, at 4 to 20 mA only
● Short-circuit Yes; channel-by-channel, at 1 to 5 V or for current measuring ranges short-circuit in encoder supply
● Group error Yes
● Overflow/Underflow Yes; channel by channel
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; green LED
● for channel diagnostics Yes; red LED
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels Yes
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics Yes
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 9.32 kg
— global warming potential, (during production) [CO2 eq] 4.97 kg
— global warming potential, (during operation) [CO2 eq] 4.79 kg
— global warming potential, (after end of life cycle) [CO2 eq]