ET 200SP by SEIMENS

ET 200SP AI 2 X U/I 2-, 4-Wire HS-6ES7134-6HB00-0DA1

INR 1
DATA SHEET
In stock

Description

SIMATIC ET 200SP, Analog input module, AI 2x U/I 2-.4-wire High Speed, suitable for BU type A0, A1, Color code CC00, channel diagnostics, 16 bit, +/-0.3%

General information

Product type designation AI 2xU/I 2-/4-wire HS

HW functional status from FS21

Firmware version V2.0.3

● FW update possible Yes

usable BaseUnits BU type A0, A1

Color code for module-specific color-coded label CC00

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode Yes; 125 µs

● Measuring range scalable No

● Scalable measured values No

● Adjustment of measuring range No

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V13 SP1

● STEP 7 configurable/integrated from version V5.5 SP3 / -

● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher

● PROFINET from GSD version/GSD revision GSDML V2.3

Operating mode

● Oversampling Yes; 2 channels per module

● MSI No

CiR - Configuration in RUN

Reparameterization possible in RUN No

Calibration possible in RUN No

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption (rated value) 39 mA; without sensor supply

Encoder supply

24 V encoder supply

● 24 V Yes; For current measurement

● Short-circuit protection Yes

● Output current, max. 20 mA; max. 50 mA per channel for a duration < 10 s

Power loss

Power loss, typ. 0.95 W; without sensor supply

Address area

Address space per module

● Address space per module, max. 4 byte; + 1 byte for QI information (32 bytes in the oversampling operating mode)

Hardware configuration

Automatic encoding Yes

● Mechanical coding element Yes

● Type of mechanical coding element Type A

Selection of BaseUnit for connection variants

● 2-wire connection BU type A0, A1

● 4-wire connection BU type A0, A1

Analog inputs

Number of analog inputs 2; Differential inputs

● For current measurement 2

● For voltage measurement 2

permissible input voltage for voltage input (destruction limit), max. 30 V

permissible input current for current input (destruction limit), max. 50 mA

Cycle time (all channels), min. 125 µs

Analog input with oversampling Yes

● Values per cycle, max. 16

● Resolution, min. 50 µs

Input ranges (rated values), voltages

● 0 to +10 V Yes; 15 bit

— Input resistance (0 to 10 V) 75 kΩ

● 1 V to 5 V Yes; 13 bit

— Input resistance (1 V to 5 V) 75 kΩ

● -10 V to +10 V Yes; 16 bit incl. sign

— Input resistance (-10 V to +10 V) 75 kΩ

● -5 V to +5 V Yes; 15 bit incl. sign

— Input resistance (-5 V to +5 V) 75 kΩ

Input ranges (rated values), currents

● 0 to 20 mA Yes; 15 bit

— Input resistance (0 to 20 mA) 130 Ω

● -20 mA to +20 mA Yes; 16 bit incl. sign

— Input resistance (-20 mA to +20 mA) 130 Ω

● 4 mA to 20 mA Yes; 14 bit

— Input resistance (4 mA to 20 mA) 130 Ω

Cable length

● shielded, max. 1 000 m; 200 m for voltage measurement

Analog value generation for the inputs

Measurement principle Actual value encryption (successive approximation)

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign), max. 16 bit

● Interference voltage suppression for interference frequency f1 in Hz No

● Conversion time (per channel) 10 µs

Smoothing of measured values

● Number of smoothing levels 7; none; 2-/4-/8-/16-/32-/64-fold

● Parameterizable Yes

Encoder

Connection of signal encoders

● for voltage measurement Yes

● for current measurement as 2-wire transducer Yes

— Burden of 2-wire transmitter, max. 650 Ω

● for current measurement as 4-wire transducer Yes

Errors/accuracies

Linearity error (relative to input range), (+/-) 0.03 %

Temperature error (relative to input range), (+/-) 0.01 %/K

Crosstalk between the inputs, min. -50 dB

Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.1 %

Operational error limit in overall temperature range

● Voltage, relative to input range, (+/-) 0.3 %

● Current, relative to input range, (+/-) 0.3 %

Basic error limit (operational limit at 25 °C)

● Voltage, relative to input range, (+/-) 0.2 %

● Current, relative to input range, (+/-) 0.2 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

● Common mode voltage, max. 35 V

● Common mode interference, min. 90 dB

Isochronous mode

Filtering and processing time (TCI), min. 80 µs

Bus cycle time (TDP), min. 125 µs; Starting from firmware Version V2.0.1

Interrupts/diagnostics/status information

Alarms

● Diagnostic alarm Yes

● Limit value alarm Yes; two upper and two lower limit values in each case

Diagnoses

● Wire break Yes; channel-by-channel, at 4 to 20 mA only

● Short-circuit Yes; channel-by-channel, at 1 to 5 V or for current measuring ranges short-circuit in encoder supply

● Group error Yes

● Overflow/Underflow Yes; channel by channel

Diagnostics indication LED

● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED

● Channel status display Yes; green LED

● for channel diagnostics Yes; red LED

● for module diagnostics Yes; green/red DIAG LED

Potential separation

Potential separation channels

● between the channels Yes

● between the channels and backplane bus Yes

● between the channels and the power supply of the electronics Yes

Isolation

Isolation tested with 707 V DC (type test)

Standards, approvals, certificates

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 9.32 kg

— global warming potential, (during production) [CO2 eq] 4.97 kg

— global warming potential, (during operation) [CO2 eq] 4.79 kg

— global warming potential, (after end of life cycle) [CO2 eq]