Description
SIMATIC ET 200SP, Analog input module, AI 2x U/I 2-.4-wire High Feat., suitable for BU type A0, A1, Color code CC05, channel diagnostics, 16 bit, +/-0.1%
General information
Product type designation AI 2xU/I 2-/4-wire HF
HW functional status From FS06
Firmware version
● FW update possible Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color-coded label CC03
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes; 250 µs
● Measuring range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13
● STEP 7 configurable/integrated from version V5.5 / -
● PCS 7 configurable/integrated from version V8.1 SP1
● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher
● PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode
● Oversampling No
● MSI Yes
CiR - Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption (rated value) 39 mA; without sensor supply
Encoder supply
24 V encoder supply
● 24 V Yes
● Short-circuit protection Yes
● Output current, max. 20 mA; max. 50 mA per channel for a duration < 10 s (two-wire)
Additional 24 V encoder supply
● Short-circuit protection Yes; channel by channel
● Output current, max. 100 mA; max. 150 mA for a duration of < 10 s (four-wire)
Power loss
Power loss, typ. 0.95 W; without sensor supply
Address area
Address space per module
● Address space per module, max. 4 byte; + 4 byte for scaling of measured values, + 1 byte for QI information
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element Type A
Selection of BaseUnit for connection variants
● 2-wire connection BU type A0, A1
● 4-wire connection BU type A0, A1
Analog inputs
Number of analog inputs 2; Differential inputs
● For current measurement 2
● For voltage measurement 2
permissible input voltage for voltage input (destruction limit), max. 30 V
permissible input current for current input (destruction limit), max. 50 mA
Analog input with oversampling No
Standardization of measured values Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes; 15 bit
— Input resistance (0 to 10 V) 75 kΩ
● 1 V to 5 V Yes; 15 bit
— Input resistance (1 V to 5 V) 75 kΩ
● -10 V to +10 V Yes; 16 bit incl. sign
— Input resistance (-10 V to +10 V) 75 kΩ
● -5 V to +5 V Yes; 16 bit incl. sign
— Input resistance (-5 V to +5 V) 75 kΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes; 15 bit
— Input resistance (0 to 20 mA) 130 Ω
● -20 mA to +20 mA Yes; 16 bit incl. sign
— Input resistance (-20 mA to +20 mA) 130 Ω
● 4 mA to 20 mA Yes; 15 bit
— Input resistance (4 mA to 20 mA) 130 Ω
Cable length
● shielded, max. 1 000 m; 200 m for voltage measurement
Analog value generation for the inputs
Measurement principle Sigma Delta
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Integration time (ms) 67.5 / 22.5 / 18.75 / 10 / 5 / 2.5 / 1.25 / 0.625 ms
● Basic conversion time, including integration time (ms) 68.03 / 22.83 / 19.03 / 10.28 / 5.23 / 2.68 / 1.43 / 0.730 ms
● Interference voltage suppression for interference frequency f1 in Hz 16.6 / 50 / 60 / 300 / 600 / 1 200 / 2 400 / 4 800
● Conversion time (per channel) 68.2 / 23 / 19.2 / 10.45 / 5.40 / 2.85 / 1.6 / 0.9 ms
● Basic execution time of the module (all channels released) 1 ms
Smoothing of measured values
● Number of smoothing levels 6; none; 2-/4-/8-/16-/32-fold
● Parameterizable Yes
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 650 Ω
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.003 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.01 %
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.1 %
● Current, relative to input range, (+/-) 0.1 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.05 %; 0.1 % at SFU 4.8 kHz
● Current, relative to input range, (+/-) 0.05 %; 0.1 % at SFU 4.8 kHz
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode voltage, max. 35 V
● Common mode interference, min. 90 dB
Isochronous mode
Filtering and processing time (TCI), min. 800 µs
Bus cycle time (TDP), min. 1 ms
Jitter, max. 5 µs
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm Yes; two upper and two lower limit values in each case
Diagnoses
● Monitoring the supply voltage Yes
● Wire break Yes; Measuring range 4 to 20 mA only
● short-circuit Yes; channel-by-channel, at 1 to 5 V or for short-circuit in encoder supply
● Group error Yes
● Overflow/Underflow Yes