SIMATIC ET 200SP, Analog input module, AI 2x U/I 2-.4-wire High Feat., suitable for BU type A0, A1, Color code CC05, channel diagnostics, 16 bit, +/-0.1%

General information

Product type designation AI 2xU/I 2-/4-wire HF

HW functional status From FS06

Firmware version

● FW update possible Yes

usable BaseUnits BU type A0, A1

Color code for module-specific color-coded label CC03

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode Yes; 250 µs

● Measuring range scalable No

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V13

● STEP 7 configurable/integrated from version V5.5 / -

● PCS 7 configurable/integrated from version V8.1 SP1

● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher

● PROFINET from GSD version/GSD revision GSDML V2.3

Operating mode

● Oversampling No

● MSI Yes

CiR - Configuration in RUN

Reparameterization possible in RUN Yes

Calibration possible in RUN Yes

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption (rated value) 39 mA; without sensor supply

Encoder supply

24 V encoder supply

● 24 V Yes

● Short-circuit protection Yes

● Output current, max. 20 mA; max. 50 mA per channel for a duration < 10 s (two-wire)

Additional 24 V encoder supply

● Short-circuit protection Yes; channel by channel

● Output current, max. 100 mA; max. 150 mA for a duration of < 10 s (four-wire)

Power loss

Power loss, typ. 0.95 W; without sensor supply

Address area

Address space per module

● Address space per module, max. 4 byte; + 4 byte for scaling of measured values, + 1 byte for QI information

Hardware configuration

Automatic encoding Yes

● Mechanical coding element Yes

● Type of mechanical coding element Type A

Selection of BaseUnit for connection variants

● 2-wire connection BU type A0, A1

● 4-wire connection BU type A0, A1

Analog inputs

Number of analog inputs 2; Differential inputs

● For current measurement 2

● For voltage measurement 2

permissible input voltage for voltage input (destruction limit), max. 30 V

permissible input current for current input (destruction limit), max. 50 mA

Analog input with oversampling No

Standardization of measured values Yes

Input ranges (rated values), voltages

● 0 to +10 V Yes; 15 bit

— Input resistance (0 to 10 V) 75 kΩ

● 1 V to 5 V Yes; 15 bit

— Input resistance (1 V to 5 V) 75 kΩ

● -10 V to +10 V Yes; 16 bit incl. sign

— Input resistance (-10 V to +10 V) 75 kΩ

● -5 V to +5 V Yes; 16 bit incl. sign

— Input resistance (-5 V to +5 V) 75 kΩ

Input ranges (rated values), currents

● 0 to 20 mA Yes; 15 bit

— Input resistance (0 to 20 mA) 130 Ω

● -20 mA to +20 mA Yes; 16 bit incl. sign

— Input resistance (-20 mA to +20 mA) 130 Ω

● 4 mA to 20 mA Yes; 15 bit

— Input resistance (4 mA to 20 mA) 130 Ω

Cable length

● shielded, max. 1 000 m; 200 m for voltage measurement

Analog value generation for the inputs

Measurement principle Sigma Delta

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign), max. 16 bit

● Integration time, parameterizable Yes

● Integration time (ms) 67.5 / 22.5 / 18.75 / 10 / 5 / 2.5 / 1.25 / 0.625 ms

● Basic conversion time, including integration time (ms) 68.03 / 22.83 / 19.03 / 10.28 / 5.23 / 2.68 / 1.43 / 0.730 ms

● Interference voltage suppression for interference frequency f1 in Hz 16.6 / 50 / 60 / 300 / 600 / 1 200 / 2 400 / 4 800

● Conversion time (per channel) 68.2 / 23 / 19.2 / 10.45 / 5.40 / 2.85 / 1.6 / 0.9 ms

● Basic execution time of the module (all channels released) 1 ms

Smoothing of measured values

● Number of smoothing levels 6; none; 2-/4-/8-/16-/32-fold

● Parameterizable Yes

Encoder

Connection of signal encoders

● for voltage measurement Yes

● for current measurement as 2-wire transducer Yes

— Burden of 2-wire transmitter, max. 650 Ω

● for current measurement as 4-wire transducer Yes

Errors/accuracies

Linearity error (relative to input range), (+/-) 0.01 %

Temperature error (relative to input range), (+/-) 0.003 %/K

Crosstalk between the inputs, min. -50 dB

Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.01 %

Operational error limit in overall temperature range

● Voltage, relative to input range, (+/-) 0.1 %

● Current, relative to input range, (+/-) 0.1 %

Basic error limit (operational limit at 25 °C)

● Voltage, relative to input range, (+/-) 0.05 %; 0.1 % at SFU 4.8 kHz

● Current, relative to input range, (+/-) 0.05 %; 0.1 % at SFU 4.8 kHz

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

● Common mode voltage, max. 35 V

● Common mode interference, min. 90 dB

Isochronous mode

Filtering and processing time (TCI), min. 800 µs

Bus cycle time (TDP), min. 1 ms

Jitter, max. 5 µs

Interrupts/diagnostics/status information

Diagnostics function Yes

Alarms

● Diagnostic alarm Yes

● Limit value alarm Yes; two upper and two lower limit values in each case

Diagnoses

● Monitoring the supply voltage Yes

● Wire break Yes; Measuring range 4 to 20 mA only

● short-circuit Yes; channel-by-channel, at 1 to 5 V or for short-circuit in encoder supply

● Group error Yes

● Overflow/Underflow Yes