G120X DRIVE by SIEMENS

ET 200SP, AI 2xU Standard, PU 1 - 6ES7134-6FB00-0BA1

INR 1
DATASHEET
In stock

Description

SIMATIC ET 200SP, Analog input module, AI 2xU Standard Pack quantity: 1 unit, suitable for BU type A0, A1, Color code CC00, Module diagnostics, 16 bit

Product type designation AI 2xU ST

HW functional status FS22 or higher

Firmware version V2.0.0

● FW update possible Yes

usable BaseUnits BU type A0, A1

Color code for module-specific color-coded label CC00

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode No

● Measuring range scalable No

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V21 HSP0493 / integrated as of V21.1

● STEP 7 configurable/integrated from version V5.7 SP3 HF3 with HSP0348 V2.0 / integrated as of V5.8

● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher

● PROFINET from GSD version/GSD revision GSDML V2.45

Operating mode

● Oversampling No

● MSI No

CiR - Configuration in RUN

Reparameterization possible in RUN Yes

Calibration possible in RUN No

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption (rated value) 33.5 mA

Current consumption, max. 37 mA

Encoder supply

24 V encoder supply

● 24 V No

Additional 24 V encoder supply

● 24 V No

Power loss

Power loss, typ. 0.9 W

Address area

Address space per module

● Address space per module, max. 4 byte; + 1 byte for QI information

Hardware configuration

Automatic encoding Yes

● Mechanical coding element Yes

● Type of mechanical coding element Type A

Selection of BaseUnit for connection variants

● 1-wire connection BU type A0, A1

● 2-wire connection BU type A0, A1

Analog inputs

Number of analog inputs 2

● For voltage measurement 2

permissible input voltage for voltage input (destruction limit), max. 30 V

Cycle time (all channels), min. 500 µs

Input ranges (rated values), voltages

● 0 to +10 V Yes; 15 bit

— Input resistance (0 to 10 V) 180 kΩ

● 1 V to 5 V Yes; 15 bit

— Input resistance (1 V to 5 V) 180 kΩ

● -10 V to +10 V Yes; 16 bit incl. sign

— Input resistance (-10 V to +10 V) 180 kΩ

● -5 V to +5 V Yes; 16 bit incl. sign

— Input resistance (-5 V to +5 V) 180 kΩ

Cable length

● shielded, max. 200 m

Analog value generation for the inputs

Measurement principle Sigma Delta

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign), max. 16 bit

● Integration time, parameterizable Yes

● Interference voltage suppression for interference frequency f1 in Hz 16.6 / 50 / 60 Hz / off

● Conversion time (per channel) 50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6 Hz, 250 µs without filter

Smoothing of measured values

● Number of smoothing levels 4

● Parameterizable Yes

● Step: None Yes; 1x conversion time

● Step: low Yes; 4x smoothing

● Step: Medium Yes; 8x smoothing

● Step: High Yes; 16x smoothing

Encoder

Connection of signal encoders

● for voltage measurement Yes

Errors/accuracies

Linearity error (relative to input range), (+/-) 0.01 %

Temperature error (relative to input range), (+/-) 0.005 %/K

Crosstalk between the inputs, min. -50 dB

Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 %

Operational error limit in overall temperature range

● Voltage, relative to input range, (+/-) 0.5 %

Basic error limit (operational limit at 25 °C)

● Voltage, relative to input range, (+/-) 0.3 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

● Series mode interference (peak value of interference < rated value of input range), min. 70 dB

● Common mode voltage, max. 10 V

● Common mode interference, min. 90 dB

Interrupts/diagnostics/status information

Diagnostics function Yes

Alarms

● Diagnostic alarm Yes

● Limit value alarm No

Diagnoses

● Monitoring the supply voltage Yes

● Wire break No

● short-circuit Yes; at 1 to 5 V

● Group error Yes

● Overflow/Underflow Yes; module-wise

Diagnostics indication LED

● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED

● Channel status display Yes; green LED

● for channel diagnostics No

● for module diagnostics Yes; green/red DIAG LED

Potential separation

Potential separation channels

● between the channels No

● between the channels and backplane bus Yes

● between the channels and the power supply of the electronics Yes

Permissible potential difference

between the inputs (UCM) 10 Vpp

Isolation

Isolation tested with 707 V DC (type test)

Standards, approvals, certificates

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 9.32 kg

— global warming potential, (during production) [CO2 eq] 4.97 kg

— global warming potential, (during operation) [CO2 eq] 4.79 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.449 kg

Specifications

--
---