ET 200SP by SIEMENS

ET 200SP, AQ 2 X U/I High Feature - 6ES7135-6HB00-0CA1

INR 1
DATASHEET
In stock

Description

SIMATIC ET 200SP, Analog output module, AQ 2x U/I High Feature suitable for BU type A0, A1, Color code CC00, channel diagnostics, 16 bit, +/-0.1%

Product type designation AQ 2xU/I HF

HW functional status from FS21

Firmware version V1.0.3

● FW update possible Yes

usable BaseUnits BU type A0, A1

Color code for module-specific color-coded label CC00

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode Yes; 250 µs

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V13 / V13

● STEP 7 configurable/integrated from version V5.5 SP3 / -

● PCS 7 configurable/integrated from version V8.1 SP1

● PROFIBUS from GSD version/GSD revision GSD Revision 5

● PROFINET from GSD version/GSD revision GSDML V2.3

Operating mode

● Oversampling No

● MSO No

CiR - Configuration in RUN

Reparameterization possible in RUN No

Calibration possible in RUN No

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption (rated value) 45 mA; without load

Current consumption, max. 90 mA; 2 channels current output 20 mA

Power loss

Power loss, typ. 0.9 W

Address area

Address space per module

● Address space per module, max. 4 byte; + 1 byte for QI information

Hardware configuration

Automatic encoding Yes

● Mechanical coding element Yes

● Type of mechanical coding element Type A

Analog outputs

Number of analog outputs 2

Voltage output, short-circuit protection Yes

Voltage output, short-circuit current, max. 45 mA

Cycle time (all channels), min. 750 µs

Output ranges, voltage

● 0 to 10 V Yes; 15 bit

● 1 V to 5 V Yes; 13 bit

● -5 V to +5 V Yes; 15 bit incl. sign

● -10 V to +10 V Yes; 16 bit incl. sign

Output ranges, current

● 0 to 20 mA Yes; 15 bit

● -20 mA to +20 mA Yes; 16 bit incl. sign

● 4 mA to 20 mA Yes; 14 bit

Connection of actuators

● for voltage output two-wire connection Yes

● for voltage output four-wire connection Yes

● for current output two-wire connection Yes

Load impedance (in rated range of output)

● with voltage outputs, min. 2 kΩ

● with voltage outputs, capacitive load, max. 1 µF

● with current outputs, max. 500 Ω

● with current outputs, inductive load, max. 1 mH

Destruction limits against externally applied voltages and currents

● Voltages at the outputs 30 V

Cable length

● shielded, max. 1 000 m; 200 m for voltage output

Analog value generation for the outputs

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign), max. 16 bit

Settling time

● for resistive load 0.05 ms

● for capacitive load 0.05 ms; Max. 47 nF and 20 m cable length

● for inductive load 0.05 ms

Errors/accuracies

Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) 0.02 %

Linearity error (relative to output range), (+/-) 0.03 %

Temperature error (relative to output range), (+/-) 0.003 %/K

Crosstalk between the outputs, max. -50 dB

Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) 0.03 %

Operational error limit in overall temperature range

● Voltage, relative to output range, (+/-) 0.2 %

● Current, relative to output range, (+/-) 0.2 %

Basic error limit (operational limit at 25 °C)

● Voltage, relative to output range, (+/-) 0.1 %

● Current, relative to output range, (+/-) 0.1 %

Isochronous mode

Execution and activation time (TCO), min. 500 µs

Bus cycle time (TDP), min. 750 µs

Jitter, max. 5 µs

Interrupts/diagnostics/status information

Diagnostics function Yes

Substitute values connectable Yes

Alarms

● Diagnostic alarm Yes

Diagnoses

● Monitoring the supply voltage Yes

● Wire break Yes; channel-by-channel, only for output type “current”

● Short-circuit Yes; channel-by-channel, only for output type “voltage”

● Group error Yes

● Overflow/Underflow Yes; channel by channel

Diagnostics indication LED

● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED

● Channel status display Yes; green LED

● for channel diagnostics Yes; red LED

● for module diagnostics Yes; green/red DIAG LED

Potential separation

Potential separation channels

● between the channels No

● between the channels and backplane bus Yes

● between the channels and the power supply of the electronics Yes

Isolation

Isolation tested with 707 V DC (type test)

Standards, approvals, certificates

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 28.6 kg

— global warming potential, (during production) [CO2 eq] 5.33 kg

— global warming potential, (during operation) [CO2 eq] 23.6 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.343 kg

Ambient conditions

Ambient temperature during operation

● horizontal installation, min. -30 °C; < 0 °C as of FS04

● horizontal installation, max. 60 °C

● vertical installation, min. -30 °C; < 0 °C as of FS04

● vertical installation, max. 50 °C

Altitude during operation relating to sea level

● Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP System Manual

Specifications

--
--