SIMATIC ET 200SP, Analog output module, AQ 2x U/I High Feature suitable for BU type A0, A1, Color code CC00, channel diagnostics, 16 bit, +/-0.1%
Product type designation AQ 2xU/I HF
HW functional status from FS21
Firmware version V1.0.3
● FW update possible Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color-coded label CC00
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes; 250 µs
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13 / V13
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PCS 7 configurable/integrated from version V8.1 SP1
● PROFIBUS from GSD version/GSD revision GSD Revision 5
● PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode
● Oversampling No
● MSO No
CiR - Configuration in RUN
Reparameterization possible in RUN No
Calibration possible in RUN No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption (rated value) 45 mA; without load
Current consumption, max. 90 mA; 2 channels current output 20 mA
Power loss
Power loss, typ. 0.9 W
Address area
Address space per module
● Address space per module, max. 4 byte; + 1 byte for QI information
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element Type A
Analog outputs
Number of analog outputs 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 45 mA
Cycle time (all channels), min. 750 µs
Output ranges, voltage
● 0 to 10 V Yes; 15 bit
● 1 V to 5 V Yes; 13 bit
● -5 V to +5 V Yes; 15 bit incl. sign
● -10 V to +10 V Yes; 16 bit incl. sign
Output ranges, current
● 0 to 20 mA Yes; 15 bit
● -20 mA to +20 mA Yes; 16 bit incl. sign
● 4 mA to 20 mA Yes; 14 bit
Connection of actuators
● for voltage output two-wire connection Yes
● for voltage output four-wire connection Yes
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 2 kΩ
● with voltage outputs, capacitive load, max. 1 µF
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 1 mH
Destruction limits against externally applied voltages and currents
● Voltages at the outputs 30 V
Cable length
● shielded, max. 1 000 m; 200 m for voltage output
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
Settling time
● for resistive load 0.05 ms
● for capacitive load 0.05 ms; Max. 47 nF and 20 m cable length
● for inductive load 0.05 ms
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) 0.02 %
Linearity error (relative to output range), (+/-) 0.03 %
Temperature error (relative to output range), (+/-) 0.003 %/K
Crosstalk between the outputs, max. -50 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) 0.03 %
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-) 0.2 %
● Current, relative to output range, (+/-) 0.2 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-) 0.1 %
● Current, relative to output range, (+/-) 0.1 %
Isochronous mode
Execution and activation time (TCO), min. 500 µs
Bus cycle time (TDP), min. 750 µs
Jitter, max. 5 µs
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire break Yes; channel-by-channel, only for output type “current”
● Short-circuit Yes; channel-by-channel, only for output type “voltage”
● Group error Yes
● Overflow/Underflow Yes; channel by channel
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; green LED
● for channel diagnostics Yes; red LED
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics Yes
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 28.6 kg
— global warming potential, (during production) [CO2 eq] 5.33 kg
— global warming potential, (during operation) [CO2 eq] 23.6 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.343 kg
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; < 0 °C as of FS04
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C; < 0 °C as of FS04
● vertical installation, max. 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP System Manual