ET 200SP, CM CAN Gateway to CAN or CANopen networks, CAN 2.0A/B, CANopen Manager to CiA301/302, CANopen Slave to CiA301/302, IP20
General information
Product type designation CM 1x CAN ST
Firmware version V1.2.x
● FW update possible Yes
usable BaseUnits BU type A0
Color code for module-specific color-coded label CC00
Product function
● I&M data Yes; I&M0 to I&M3
● Module swapping during operation (hot swapping) Yes
● Isochronous mode No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version STEP 7 V15.1 or higher
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, typ. 20 mA
Current consumption, max. 25 mA
Power loss
Power loss, typ. 0.5 W
Address area
Address space per module
● Address space per module, max. 256 byte
1. Interface
Interface type CAN according to CiA 303-1
Isolated Yes; 500 V AC or 707 V DC
Interface types
● Number of ports 1
● Design of the connection Push-in terminal
CAN
● CAN operating modes CAN Standard CAN 2.0A/B; CANopen Manager / Slave acc. to CiA
● Specification acc. to CiA CiA 301 & CiA 302
● Transmission rate, min. 10 kbit/s
● Transmission rate, max. 1 000 kbit/s
● max. number of devices 60
● Number of SDOs in parallel 16; Parallel
● Number of PDOs 128; Send / receive
Services
— Node/life-guarding Yes
— Heartbeat Yes
— SYNC Yes
Interrupts/diagnostics/status information
Alarms Yes
Diagnostics function Yes
Diagnostics indication LED
● RUN LED Yes
● ERROR LED Yes
● MAINT LED No
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
Potential separation
between backplane bus and interface Yes
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
CE mark Yes
UL approval Yes
RCM (formerly C-TICK) Yes
KC approval Yes; Reg. No.: R-R-S49-ET200SPCMCAN
EAC (formerly Gost-R) Yes
RoHS conformity Yes
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 25.2 kg
— global warming potential, (during production) [CO2 eq] 6.15 kg
— global warming potential, (during operation) [CO2 eq] 19.4 kg
— global warming potential, (after end of life cycle) [CO2 eq]