ET 200SP, DI 16x24VDC SRC BA-6ES7131-6BH60-0AA0

INR 1
DATA SHEET
In stock

Description

SIMATIC ET 200SP, digital input module, DI 16x24 V DC SRC BA, input type 1 (IEC 61131), source input, (NPN, sourcing input), packing unit: 1 unit, suitable for BU type A0, color code CC00, input delay 0.05..20 ms; module diagnostics for: supply voltage

General information

Product type designation DI 16x24VDC SRC BA

Firmware version V0.0

● FW update possible No

usable BaseUnits BU type A0

Color code for module-specific color-coded label CC00

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode No

Engineering with

● STEP 7 TIA Portal configurable/integrated from version STEP 7 V19 or higher with HSP0433, integrated as of V21

● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher

● PROFINET from GSD version/GSD revision GSDML V2.43

Operating mode

● DI Yes

● Counter No

● Oversampling No

● MSI No

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption (rated value) 8 mA; rated voltage, all channels active, no load

Current consumption, max. 65 mA; worst case voltage, all channels active, max. load, no derating

Encoder supply

Short-circuit protection No

Power loss

Power loss, typ. 0.8 W; rated voltage, 50 % active channels

Address area

Address space per module

● Address space per module, max. 2 byte

● Inputs 2 byte

Hardware configuration

Automatic encoding Yes

● Mechanical coding element Yes

● Type of mechanical coding element Type A

Selection of BaseUnit for connection variants

● 1-wire connection BU type A0

● 2-wire connection BU type A0 with AUX terminals or potential distributor module

● 3-wire connection BU type A0 with AUX terminals or potential distributor module

Digital inputs

Number of digital inputs 16

Digital inputs, parameterizable Yes

Sourcing/sinking input Sourcing

Input characteristic curve in accordance with IEC 61131, type 1 Yes

Input characteristic curve in accordance with IEC 61131, type 3 Yes

Number of simultaneously controllable inputs

● Number of simultaneously controllable inputs 16

Input voltage

● Rated value (DC) 24 V

● for signal “0” 30 V to -5 V (reference potential is L+)

● for signal “1” -11 V to -30 V (reference potential is L+)

Input current

● for signal “1”, typ. 4 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length)

— at “0” to “1”, min. 0.05 ms

— at “0” to “1”, max. 20 ms

— at “1” to “0”, min. 0.05 ms

— at “1” to “0”, max. 20 ms

Cable length

● shielded, max. 1 000 m

● unshielded, max. 200 m

Encoder

Connectable encoders

● 2-wire sensor Yes

— permissible quiescent current (2-wire sensor), max. 1.5 mA

Interrupts/diagnostics/status information

Diagnostics function Yes

Alarms

● Diagnostic alarm Yes

Diagnoses

● Diagnostic information readable Yes

● Monitoring the supply voltage Yes

— parameterizable Yes

● Monitoring of encoder power supply No

● Wire break No

● Short-circuit No

● Short-circuit to ground No

● Short-circuit to L+ No

● Group error No

Diagnostics indication LED

● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED

● Channel status display Yes; green LED

● for channel diagnostics No

● for module diagnostics Yes; green/red DIAG LED

Potential separation

Potential separation channels

● between the channels No

● between the channels and backplane bus Yes

● Between the channels and load voltage L+ No

Isolation

Isolation tested with 707 V DC (type test)

Standards, approvals, certificates

Suitable for safety functions No

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 21 kg

— global warming potential, (during production) [CO2 eq] 4.25 kg

— global warming potential, (during operation) [CO2 eq] 1.75 kg

— global warming potential, (after end of life cycle) [CO2 eq]