ET 200SP by SIEMENS

ET 200SP, DI 8x 24V DC ST, PU 1 - 6ES7131-6BF01-0BA0

INR 1
DATASHEET
In stock

Description

SIMATIC ET 200SP, Digital input module, DI 8x 24V DC Standard, type 3 (IEC 61131), sink input, (PNP, P-reading), Packing unit: 1 piece, fits to BU-type A0, Colour Code CC01, input delay time 0,05..20ms, module diagnostics for: short-circuit of sensor supply, wire break, supply voltage

Product type designation DI 8x24 VDC ST

HW functional status From FS02

Firmware version V0.0

● FW update possible No

usable BaseUnits BU type A0

Color code for module-specific color-coded label CC01

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode No

● suitable for operation on PROFINET R1 IMs Yes

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V14

● STEP 7 configurable/integrated from version V5.5 SP3 or higher

● PCS 7 configurable/integrated from version V8.1 SP1

● PCS neo can be configured/integrated from version V3.1

● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher

● PROFINET from GSD version/GSD revision GSDML V2.3

Operating mode

● DI Yes

● Counter No

● Oversampling No

● MSI No

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption, max. 50 mA; All channels are supplied from the encoder supply

Encoder supply

Number of outputs 8

Output voltage, min. 19.2 V

Short-circuit protection Yes; per module

24 V encoder supply

● 24 V Yes

● Short-circuit protection Yes

● Output current, max. 700 mA

● Output current per channel, max. 700 mA

● Output current per module, max. 700 mA

Power loss

Power loss, typ. 1 W; 24 V, 8 inputs supplied via encoder supply

Address area

Address space per module

● Inputs 1 byte; + 1 byte for QI information

Hardware configuration

Automatic encoding Yes

● Mechanical coding element Yes

● Type of mechanical coding element Type A

Selection of BaseUnit for connection variants

● 1-wire connection BU type A0

● 2-wire connection BU type A0

● 3-wire connection BU type A0 with AUX terminals or potential distributor module

● 4-wire connection BU type A0 + Potential distributor module

Digital inputs

Number of digital inputs 8

Digital inputs, parameterizable Yes

Sourcing/sinking input P-reading

Input characteristic curve in accordance with IEC 61131, type 3 Yes

Input voltage

● Rated value (DC) 24 V

● for signal “0” -30 to +5 V

● for signal “1” +11 to +30V

Input current

● for signal “1”, typ. 2.5 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length)

— at “0” to “1”, min. 0.05 ms

— at “0” to “1”, max. 20 ms

— at “1” to “0”, min. 0.05 ms

— at “1” to “0”, max. 20 ms

Cable length

● shielded, max. 1 000 m

● unshielded, max. 600 m

Encoder

Connectable encoders

● 2-wire sensor Yes

— permissible quiescent current (2-wire sensor), max. 1.5 mA

Interrupts/diagnostics/status information

Diagnostics function Yes

Alarms

● Diagnostic alarm Yes

Diagnoses

● Diagnostic information readable Yes

● Monitoring the supply voltage Yes

— parameterizable Yes

● Monitoring of encoder power supply Yes; Module-by-module, optional protective circuit for preventing wire-break diagnostics in the case of simple encoder contacts: 25 kOhm to 45 kOhm

● Wire break Yes; module-wise

● Short-circuit Yes; module-wise

Diagnostics indication LED

● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED

● Channel status display Yes; green LED

● for channel diagnostics No

● for module diagnostics Yes; green/red DIAG LED

Potential separation

Potential separation channels

● between the channels No

● between the channels and backplane bus Yes

● between the channels and the power supply of the electronics No

Isolation

Isolation tested with 707 V DC (type test)

Standards, approvals, certificates

Suitable for safety functions No

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 15.9 kg

— global warming potential, (during production) [CO2 eq] 3.69 kg

— global warming potential, (during operation) [CO2 eq] 12.7 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.495 kg

Ambient conditions

Ambient temperature during operation

● horizontal installation, min. -30 °C; < 0 °C as of FS02

● horizontal installation, max. 60 °C

● vertical installation, min. -30 °C; < 0 °C as of FS02

● vertical installation, max. 50 °C

Altitude during operation relating to sea level

● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual

Absolute humidity

● dew point, min. -60 °C; suitable for dry room applications

Specifications

--
--