ET 200SP by SEIMENS

ET 200SP, DQ 16X24VDC/0,5A BA, PU 1-ET 200SP, DQ 16X24VDC/0,5A BA, PU 1

INR 1
DATA SHEET
In stock

Description

SIMATIC ET 200SP, digital output module, DQ 16x 24VDC/0.5A Basic, Pack quantity: 1 unit, suitable for BU type A0, Color code CC00, Module diagnostics

General information

Product type designation DQ 16x24VDC/0.5A BA

HW functional status From FS03

Firmware version V0.0

● FW update possible No

usable BaseUnits BU type A0

Color code for module-specific color-coded label CC00

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode No

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V14

● STEP 7 configurable/integrated from version STEP 7 V5.5 or higher

● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher

● PROFINET from GSD version/GSD revision GSDML V2.3

Operating mode

● DQ Yes

● DQ with energy-saving function No

● PWM No

● Oversampling No

● MSO No

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption, max. 55 mA; without load

Output voltage

Rated value (DC) 24 V

Power loss

Power loss, typ. 1 W

Address area

Address space per module

● Outputs 2 byte

Hardware configuration

Automatic encoding Yes

● Mechanical coding element Yes

● Type of mechanical coding element Type A

Selection of BaseUnit for connection variants

● 1-wire connection BU type A0

● 2-wire connection BU type A0 + Potential distributor module

● 3-wire connection BU type A0 + Potential distributor module

● 4-wire connection BU type A0 + Potential distributor module

Digital outputs

Type of digital output Source output (PNP, current-sourcing)

Number of digital outputs 16

Current-sinking No

Current-sourcing Yes

Digital outputs, parameterizable Yes

Short-circuit protection Yes

● Response threshold, typ. 1.4 A; 0.7 to 1.9 A

Open-circuit detection No

Limitation of inductive shutdown voltage to Typ. L+ (-53 V)

Controlling a digital input Yes

Switching capacity of the outputs

● with resistive load, max. 0.5 A

● on lamp load, max. 5 W

Load resistance range

● lower limit 48 Ω

● upper limit 100 kΩ

Output current

● for signal “1” rated value 0.5 A

● for signal “0” residual current, max. 30 µA

Output delay with resistive load

● “0” to “1”, typ. 80 µs; at rated load

● “0” to “1”, max. 150 µs; at rated load

● “1” to “0”, typ. 100 µs; at rated load

● “1” to “0”, max. 200 µs; at rated load

Parallel switching of two outputs

● for uprating No

● for redundant control of a load Yes

Switching frequency

● with resistive load, max. 100 Hz

● with inductive load, max. 2 Hz

● on lamp load, max. 10 Hz

Total current of the outputs

● Current per channel, max. 0.5 A

● Current per module, max. 8 A

Total current of the outputs (per module)

horizontal installation

— up to 60 °C, max. 8 A

vertical installation

— up to 50 °C, max. 8 A

Cable length

● shielded, max. 1 000 m

● unshielded, max. 600 m

Interrupts/diagnostics/status information

Diagnostics function Yes

Substitute values connectable Yes

Alarms

● Diagnostic alarm Yes

Diagnoses

● Monitoring the supply voltage Yes

● Wire break No

● Short-circuit No

● Group error Yes

Diagnostics indication LED

● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED

● Channel status display Yes; green LED

● for channel diagnostics No

● for module diagnostics Yes; green/red DIAG LED

Potential separation

Potential separation channels

● between the channels No

● between the channels and backplane bus Yes

Isolation

Isolation tested with 707 V DC (type test)

Standards, approvals, certificates

Suitable for safety functions No

Suitable for safety-related tripping of standard modules No

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 29.3 kg

— global warming potential, (during production) [CO2 eq] 3.98 kg

— global warming potential, (during operation) [CO2 eq] 25.6 kg

— global warming potential, (after end of life cycle) [CO2 eq]