Description

SIMATIC ET 200SP, digital output module DQ 4x 24..230V AC/2A HF packaging unit: 1 piece, two alternative modes: DQ and power control, fits to BU-Type U0, color code CC20, channel diagnosis

General information

Product type designation DQ 4x24 ... 230 V AC/2 A HF

HW functional status From FS03

Firmware version

● FW update possible Yes

usable BaseUnits BU type U0

Color code for module-specific color-coded label CC20

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode No

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V14

● STEP 7 configurable/integrated from version STEP 7 V5.5 or higher

● PROFIBUS from GSD version/GSD revision GSD as of Revision 5

● PROFINET from GSD version/GSD revision GSDML V2.3

Operating mode

● DQ Yes

● DQ with energy-saving function Yes

● PWM No

● Oversampling No

● MSO No

● Phase control Yes; Control area: 8.5 ... 100% of the phase angle

● Trailing-edge phase No

● Half-wave Yes

● Full-wave Yes

Supply voltage

Rated value (AC) 230 V; 47 ... 63 Hz, max. rate of change of frequency 1 mHz/s

permissible range, lower limit (AC) 20.4 V

permissible range, upper limit (AC) 264 V

Input current

Current consumption (rated value) 8 mA; without load

Output voltage

Rated value (AC) 230 V; 24V AC to 230V AC

Power loss

Power loss, typ. 9 W; Active power, load voltage 230 V, all outputs loaded with 2 A, 50 Hz

Address area

Address space per module

● Inputs + 1 byte for QI information

● Outputs 8 byte

Hardware configuration

Automatic encoding Yes

● Mechanical coding element Yes

● Type of mechanical coding element type C

Selection of BaseUnit for connection variants

● 1-wire connection BU type U0

● 2-wire connection BU type U0

● 3-wire connection BU type U0 + Potential distributor module

Digital outputs

Type of digital output Triac

Number of digital outputs 4

Current-sinking No

Current-sourcing Yes

Digital outputs, parameterizable Yes

Short-circuit protection No; external fusing necessary

Open-circuit detection Yes; channel by channel

● Response threshold, typ. 1 mA; 40 V AC or more

Overload protection No; A miniature fuse with 10 tripping current and tripping characteristic “quick response” must be provided in the module supply

Controlling a digital input Yes

Switching capacity of the outputs

● with resistive load, max. 2 A; Max. 4 A, see additional description in manual

● with inductive load, max. 2 A

● on lamp load, max. 100 W; Tungsten rating in accordance with UL; for thermistors with higher power ratings, see the notes in the manual

Output voltage

● for signal “1”, min. 20.4 V

Output current

● for signal “1” rated value 2 A

● for signal “1” permissible range, min. 10 mA

● for signal “1” permissible range, max. 4 A; note derating data in the manual

● for signal “0” residual current, max. 3 mA

Output delay with resistive load

● “0” to “1”, max. 40 ms; 2 AC cycles

● “1” to “0”, max. 20 ms; 1 AC cycle

Parallel switching of two outputs

● for logic links No

● for uprating No

● for redundant control of a load Yes

Switching frequency

● with resistive load, max. 10 Hz; Applies to DQ mode; limited by line frequency in PC mode

● with inductive load (acc. to IEC 60947-5-1, AC15), max. 10 Hz; Applies to DQ mode; limited by line frequency in PC mode

● on lamp load, max. 1 Hz; Applies to DQ mode; limited by line frequency in PC mode

Total current of the outputs

● Current per channel, max. 2 A; Max. 4 A, see additional description in manual

● Current per module, max. 8 A

Total current of the outputs (per module)

horizontal installation

— up to 40 °C, max. 8 A

— up to 50 °C, max. 6 A

— up to 60 °C, max. 4 A

vertical installation

— up to 30 °C, max. 8 A

— up to 40 °C, max. 6 A

— up to 50 °C, max. 4 A

Cable length

● shielded, max. 1 000 m

● unshielded, max. 600 m

Interrupts/diagnostics/status information

Diagnostics function Yes

Substitute values connectable Yes

Alarms

● Diagnostic alarm Yes

Diagnoses

● Diagnostic information readable Yes

● Monitoring the supply voltage Yes

● Wire break Yes; channel by channel

● short-circuit No

● Group error Yes

Diagnostics indication LED

● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED

● Channel status display Yes; green LED

● for channel diagnostics Yes; red Fn LED

● for module diagnostics Yes; green/red DIAG LED

Potential separation

Potential separation channels

● between the channels No

● between the channels and backplane bus Yes

● between the channels and the power supply of the electronics No

Isolation

Isolation tested with 2 545 V DC/2 s (routine test)

Standards, approvals, certificates

Suitable for safety functions No

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 13.9 kg

— global warming potential, (during production) [CO2 eq] 5.53 kg

— global warming potential, (during operation) [CO2 eq] 8.71 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.359 kg

Specifications

--
--