Description
SIMATIC ET 200SP, digital output module DQ 4x 24..230V AC/2A HF packaging unit: 1 piece, two alternative modes: DQ and power control, fits to BU-Type U0, color code CC20, channel diagnosis
General information
Product type designation DQ 4x24 ... 230 V AC/2 A HF
HW functional status From FS03
Firmware version
● FW update possible Yes
usable BaseUnits BU type U0
Color code for module-specific color-coded label CC20
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V14
● STEP 7 configurable/integrated from version STEP 7 V5.5 or higher
● PROFIBUS from GSD version/GSD revision GSD as of Revision 5
● PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode
● DQ Yes
● DQ with energy-saving function Yes
● PWM No
● Oversampling No
● MSO No
● Phase control Yes; Control area: 8.5 ... 100% of the phase angle
● Trailing-edge phase No
● Half-wave Yes
● Full-wave Yes
Supply voltage
Rated value (AC) 230 V; 47 ... 63 Hz, max. rate of change of frequency 1 mHz/s
permissible range, lower limit (AC) 20.4 V
permissible range, upper limit (AC) 264 V
Input current
Current consumption (rated value) 8 mA; without load
Output voltage
Rated value (AC) 230 V; 24V AC to 230V AC
Power loss
Power loss, typ. 9 W; Active power, load voltage 230 V, all outputs loaded with 2 A, 50 Hz
Address area
Address space per module
● Inputs + 1 byte for QI information
● Outputs 8 byte
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element type C
Selection of BaseUnit for connection variants
● 1-wire connection BU type U0
● 2-wire connection BU type U0
● 3-wire connection BU type U0 + Potential distributor module
Digital outputs
Type of digital output Triac
Number of digital outputs 4
Current-sinking No
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection No; external fusing necessary
Open-circuit detection Yes; channel by channel
● Response threshold, typ. 1 mA; 40 V AC or more
Overload protection No; A miniature fuse with 10 tripping current and tripping characteristic “quick response” must be provided in the module supply
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max. 2 A; Max. 4 A, see additional description in manual
● with inductive load, max. 2 A
● on lamp load, max. 100 W; Tungsten rating in accordance with UL; for thermistors with higher power ratings, see the notes in the manual
Output voltage
● for signal “1”, min. 20.4 V
Output current
● for signal “1” rated value 2 A
● for signal “1” permissible range, min. 10 mA
● for signal “1” permissible range, max. 4 A; note derating data in the manual
● for signal “0” residual current, max. 3 mA
Output delay with resistive load
● “0” to “1”, max. 40 ms; 2 AC cycles
● “1” to “0”, max. 20 ms; 1 AC cycle
Parallel switching of two outputs
● for logic links No
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 10 Hz; Applies to DQ mode; limited by line frequency in PC mode
● with inductive load (acc. to IEC 60947-5-1, AC15), max. 10 Hz; Applies to DQ mode; limited by line frequency in PC mode
● on lamp load, max. 1 Hz; Applies to DQ mode; limited by line frequency in PC mode
Total current of the outputs
● Current per channel, max. 2 A; Max. 4 A, see additional description in manual
● Current per module, max. 8 A
Total current of the outputs (per module)
horizontal installation
— up to 40 °C, max. 8 A
— up to 50 °C, max. 6 A
— up to 60 °C, max. 4 A
vertical installation
— up to 30 °C, max. 8 A
— up to 40 °C, max. 6 A
— up to 50 °C, max. 4 A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Diagnostic information readable Yes
● Monitoring the supply voltage Yes
● Wire break Yes; channel by channel
● short-circuit No
● Group error Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; green LED
● for channel diagnostics Yes; red Fn LED
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics No
Isolation
Isolation tested with 2 545 V DC/2 s (routine test)
Standards, approvals, certificates
Suitable for safety functions No
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 13.9 kg
— global warming potential, (during production) [CO2 eq] 5.53 kg
— global warming potential, (during operation) [CO2 eq] 8.71 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.359 kg
Specifications
| - | - |
|---|---|
| - | - |