Description
SIMATIC ET 200SP, digital output module, DQ 4x 24..230V AC/2A Standard suitable for BU type B1, Color code CC41, Module diagnostics
General information
Product type designation DQ 4x24 ... 230 V AC/2 A ST
HW functional status From FS05
Firmware version V1.0
● FW update possible Yes
usable BaseUnits BU type B1
Color code for module-specific color-coded label CC41
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13 / V13
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision GSD Revision 5
● PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Oversampling No
● MSO No
Supply voltage
Rated value (AC) 230 V
permissible range, lower limit (AC) 20.4 V
permissible range, upper limit (AC) 264 V
Input current
Current consumption (rated value) 11.5 mA
Output voltage
Rated value (AC) 230 V; 24V AC to 230V AC
Power loss
Power loss, typ. 9 W; Active power, load voltage 230 V, all outputs loaded with 2 A, 50 Hz
Address area
Address space per module
● Address space per module, max. 1 byte; + 1 byte for QI information
● Inputs 1 byte; With QI
● Outputs 1 byte
Hardware configuration
Automatic encoding
● Type of mechanical coding element type C
Digital outputs
Type of digital output Triac with zero point detection
Number of digital outputs 4
Current-sinking No
Current-sourcing Yes
Digital outputs, parameterizable No
Short-circuit protection No; When using BU type B1, a miniature, quick-response fuse with 10 A tripping current must be provided
Controlling a digital input Yes
Size of motor starters according to NEMA, max. 5
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 100 W
Output voltage
● for signal “1”, min. 20.4 V
Output current
● for signal “1” rated value 2 A
● for signal “1” permissible range, min. 10 mA
● for signal “1” permissible range, max. 2 A
● for signal “0” residual current, max. 460 µA
Output delay with resistive load
● “0” to “1”, max. 10 ms
● “1” to “0”, max. 10 ms
Parallel switching of two outputs
● for logic links No
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 10 Hz
● with inductive load, max. 0.5 Hz; Higher frequencies are possible, see Equipment Manual / Product Information
● on lamp load, max. 1 Hz
Total current of the outputs
● Current per channel, max. 2 A
● Current per module, max. 8 A
Total current of the outputs (per module)
horizontal installation
— up to 40 °C, max. 8 A
— up to 50 °C, max. 6 A
— up to 60 °C, max. 4 A
vertical installation
— up to 30 °C, max. 8 A
— up to 40 °C, max. 6 A
— up to 50 °C, max. 4 A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Specifications
| - | - |
|---|---|
| - | - |