ET 200SP by SIEMENS

ET 200SP, DQ 4x24VDC/2A High Speed, PU 1 -6ES7132-6BD20-0DA0

INR 1
DATASHEET
In stock

Description

SIMATIC ET 200SP, digital output module, DQ 4x 24 V DC/2A High Speed, Pack quantity: 1 unit suitable for BU type A0, Color code CC00, 3 alternative operating modes: DQ, Oversampling, PWM Module diagnostics

General information

Product type designation DQ 4x24 V DC/2 A HS

HW functional status From FS05

Firmware version

● FW update possible Yes

usable BaseUnits BU type A0

Color code for module-specific color-coded label CC00

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode Yes; Operating modes DQ and OVS only

Engineering with

● STEP 7 TIA Portal configurable/integrated from version STEP 7 V15.1 or higher

● STEP 7 configurable/integrated from version via GSD as of V5.6 HF4

● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher

● PROFINET from GSD version/GSD revision GSDML V2.33

Operating mode

● DQ Yes

● DQ with energy-saving function Yes; Valve control

● PWM Yes

● Cam control (switching at comparison values) Yes; Via MtM (module-to-module communication)

● Oversampling Yes

● MSO No

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption, max. 50 mA; without load

Output voltage

Rated value (DC) 24 V

Power loss

Power loss, typ. 2.5 W; at 24 V, 25 °C, DQ mode, 2 A per channel

Address area

Address space per module

● Inputs 1 byte; Max. 14 bytes in the cam control operating mode

● Outputs 1 byte; Max. 16 bytes in the oversampling operating mode

Hardware configuration

Automatic encoding Yes

● Mechanical coding element Yes

● Type of mechanical coding element Type A

Selection of BaseUnit for connection variants

● 2-wire connection BU type A0

● 3-wire connection BU type A0 with AUX terminals or potential distributor module

● 4-wire connection BU type A0 + Potential distributor module

Digital outputs

Type of digital output Source output (PNP, current-sourcing)

Number of digital outputs 4

Current-sinking No

Current-sourcing Yes; Push-pull output

Digital outputs, parameterizable Yes

Short-circuit protection Yes

● Response threshold, typ. 6 A

Limitation of inductive shutdown voltage to M (-1 V)

Controlling a digital input No

Digital output functions, parameterizable

● Switching tripped by comparison values Yes

— Number of cam tracks, max. 4

— Number of cams per module, max. 16

— Number of cams per track, max. 16

— Supported axis types Linear axes and rotary axes with modulo function

— Hysteresis Yes

— Pulsed cam output Yes

— Range of values for comparison values, max. -2,147,483,648 to 2,147,483,647 (user-specific within this range)

● Freely usable digital output Yes

● PWM output Yes

— Number, max. 4

— Cycle duration, parameterizable Yes; 0 ms, 0.2 ms, 0.4 ms, 0.93 ms, 1.33 ms, 4.27 ms, 10.67 ms, 21.33 ms, 34.13 ms, 59.73 ms

— Resolution of the duty cycle 0.1 %

● Digital output with oversampling Yes

— Number, max. 4

— Values per cycle, max. 32

— Resolution, min. 100 µs

Switching capacity of the outputs

● with resistive load, max. 2 A

● on lamp load, max. 10 W

Load resistance range

● lower limit 12 Ω

● upper limit 3 400 Ω

Output current

● for signal “1” rated value 2 A

● for signal “0” residual current, max. 0.1 mA

Output delay with resistive load

● “0” to “1”, max. 1 µs

● “1” to “0”, max. 1 µs

Parallel switching of two outputs

● for uprating No

Switching frequency

● with resistive load, max. 5 kHz

● with inductive load, max. 5 kHz

● on lamp load, max. 5 kHz

Total current of the outputs

● Current per channel, max. 2 A

● Current per module, max. 8 A

Total current of the outputs (per module)

horizontal installation

— up to 30 °C, max. 8 A; DQ mode

— up to 40 °C, max. 6.9 A; DQ mode

— up to 50 °C, max. 4.7 A; DQ mode

— up to 60 °C, max. 2.5 A; DQ mode

vertical installation

— up to 30 °C, max. 7.2 A; DQ mode

— up to 40 °C, max. 5.6 A; DQ mode

— up to 50 °C, max. 4 A; DQ mode

Cable length

● shielded, max. 50 m

● unshielded, max. 50 m

Isochronous mode

Execution and activation time (TCO), min. 40 µs

Bus cycle time (TDP), min. 125 µs

Jitter, max. 1 µs

Interrupts/diagnostics/status information

Diagnostics function Yes

Substitute values connectable Yes

Alarms

● Diagnostic alarm Yes

Diagnoses

● Diagnostic information readable Yes

● Monitoring the supply voltage Yes

● Wire break No

● short-circuit Yes; module-wise

● Group error Yes

Diagnostics indication LED

● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED

● Channel status display Yes; green LED

● for channel diagnostics No

● for module diagnostics Yes; green/red DIAG LED

Potential separation

Potential separation channels

● between the channels No

● between the channels and backplane bus Yes

Isolation

Isolation tested with 707 V DC (type test)

Standards, approvals, certificates

Suitable for safety functions No

Suitable for safety-related tripping of standard modules No

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 29.3 kg

— global warming potential, (during production) [CO2 eq] 3.98 kg

— global warming potential, (during operation) [CO2 eq] 25.6 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.245 kg

Specifications

--
--