SIMATIC ET 200SP, digital output module, DQ 4x 24 V DC/2A High Speed, Pack quantity: 1 unit suitable for BU type A0, Color code CC00, 3 alternative operating modes: DQ, Oversampling, PWM Module diagnostics
General information
Product type designation DQ 4x24 V DC/2 A HS
HW functional status From FS05
Firmware version
● FW update possible Yes
usable BaseUnits BU type A0
Color code for module-specific color-coded label CC00
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes; Operating modes DQ and OVS only
Engineering with
● STEP 7 TIA Portal configurable/integrated from version STEP 7 V15.1 or higher
● STEP 7 configurable/integrated from version via GSD as of V5.6 HF4
● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher
● PROFINET from GSD version/GSD revision GSDML V2.33
Operating mode
● DQ Yes
● DQ with energy-saving function Yes; Valve control
● PWM Yes
● Cam control (switching at comparison values) Yes; Via MtM (module-to-module communication)
● Oversampling Yes
● MSO No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 50 mA; without load
Output voltage
Rated value (DC) 24 V
Power loss
Power loss, typ. 2.5 W; at 24 V, 25 °C, DQ mode, 2 A per channel
Address area
Address space per module
● Inputs 1 byte; Max. 14 bytes in the cam control operating mode
● Outputs 1 byte; Max. 16 bytes in the oversampling operating mode
Hardware configuration
Automatic encoding Yes
● Mechanical coding element Yes
● Type of mechanical coding element Type A
Selection of BaseUnit for connection variants
● 2-wire connection BU type A0
● 3-wire connection BU type A0 with AUX terminals or potential distributor module
● 4-wire connection BU type A0 + Potential distributor module
Digital outputs
Type of digital output Source output (PNP, current-sourcing)
Number of digital outputs 4
Current-sinking No
Current-sourcing Yes; Push-pull output
Digital outputs, parameterizable Yes
Short-circuit protection Yes
● Response threshold, typ. 6 A
Limitation of inductive shutdown voltage to M (-1 V)
Controlling a digital input No
Digital output functions, parameterizable
● Switching tripped by comparison values Yes
— Number of cam tracks, max. 4
— Number of cams per module, max. 16
— Number of cams per track, max. 16
— Supported axis types Linear axes and rotary axes with modulo function
— Hysteresis Yes
— Pulsed cam output Yes
— Range of values for comparison values, max. -2,147,483,648 to 2,147,483,647 (user-specific within this range)
● Freely usable digital output Yes
● PWM output Yes
— Number, max. 4
— Cycle duration, parameterizable Yes; 0 ms, 0.2 ms, 0.4 ms, 0.93 ms, 1.33 ms, 4.27 ms, 10.67 ms, 21.33 ms, 34.13 ms, 59.73 ms
— Resolution of the duty cycle 0.1 %
● Digital output with oversampling Yes
— Number, max. 4
— Values per cycle, max. 32
— Resolution, min. 100 µs
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 10 W
Load resistance range
● lower limit 12 Ω
● upper limit 3 400 Ω
Output current
● for signal “1” rated value 2 A
● for signal “0” residual current, max. 0.1 mA
Output delay with resistive load
● “0” to “1”, max. 1 µs
● “1” to “0”, max. 1 µs
Parallel switching of two outputs
● for uprating No
Switching frequency
● with resistive load, max. 5 kHz
● with inductive load, max. 5 kHz
● on lamp load, max. 5 kHz
Total current of the outputs
● Current per channel, max. 2 A
● Current per module, max. 8 A
Total current of the outputs (per module)
horizontal installation
— up to 30 °C, max. 8 A; DQ mode
— up to 40 °C, max. 6.9 A; DQ mode
— up to 50 °C, max. 4.7 A; DQ mode
— up to 60 °C, max. 2.5 A; DQ mode
vertical installation
— up to 30 °C, max. 7.2 A; DQ mode
— up to 40 °C, max. 5.6 A; DQ mode
— up to 50 °C, max. 4 A; DQ mode
Cable length
● shielded, max. 50 m
● unshielded, max. 50 m
Isochronous mode
Execution and activation time (TCO), min. 40 µs
Bus cycle time (TDP), min. 125 µs
Jitter, max. 1 µs
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Diagnostic information readable Yes
● Monitoring the supply voltage Yes
● Wire break No
● short-circuit Yes; module-wise
● Group error Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; green LED
● for channel diagnostics No
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions No
Suitable for safety-related tripping of standard modules No
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 29.3 kg
— global warming potential, (during production) [CO2 eq] 3.98 kg
— global warming potential, (during operation) [CO2 eq] 25.6 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.245 kg
Specifications
| - | - |
|---|---|
| - | - |