ET 200SP by SIEMENS

ET 200SP, IM 155-6 PN R1 - 6ES7155-6AU00-0HM0

INR 1
DATASHEET
In stock

Description

SIMATIC ET 200SP, PROFINET, 2-port interface module IM 155-6 PN R1, 1 slot for BusAdapter, max. 64 I/O modules R1 redundancy, multi hot swap, 1 ms, PN security class 1

Product type designation IM 155-6 PN R1

HW functional status From FS03

Firmware version V6.1

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M4

● Module swapping during operation (hot swapping) Yes; Multi-hot swapping

● Isochronous mode No

● IRT No

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V19

● STEP 7 configurable/integrated from version use GSD file

● PROFINET from GSD version/GSD revision GSDML V2.45

Configuration control

via dataset No

CiR - Configuration in RUN

Reparameterization possible in RUN Yes

reconfiguration possible in RUN Yes

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Short-circuit protection Yes

Mains buffering

● Mains/voltage failure stored energy time 10 ms

Input current

Current consumption, max. 700 mA

Inrush current, max. 5 A

I²t 0.36 A²·s

Power loss

Power loss, typ. 2.4 W

Address area

Address space per module

● Address space per module, max. 288 byte; For input and output data respectively

Address space per station

● Address space per station, max. 1 440 byte

Hardware configuration

Rack

● Quantity of operable ET 200SP modules, max. 64

● Quantity of operable ET 200AL modules, max. 0

Submodules

● Number of submodules per station, max. 256

Interfaces

Transmission procedure 100BASE-TX

Number of PROFINET interfaces 1; 2 ports (switch)

1. Interface

Interface types

● RJ 45 (Ethernet) Yes; with BusAdapter

● Number of ports 2; with BusAdapter

● integrated switch Yes

● BusAdapter (PROFINET) Yes; BA 2x RJ45, BA 2x M12, BA 2x FC, BA 2x SCRJ, BA SCRJ/RJ45, BA SCRJ/FC, BA 2x LC, BA LC/RJ45, BA LC/FC, BA 2x LC-LD, BA LC-LD/RJ45, BA LC-LD/M12