Description
POWER SUPPLY-SITOP PSU6200/1AC/24VDC/20A-6EP33367SB003AX0
SITOP PSU6200 24 V/20 A stabilized power supply input: 120 - 240 V AC (110 - 240 V DC) output: 24 V DC/20 A with diagnostic interface
INPUT
type of the power supply network 1-phase AC or DC
supply voltage at AC
● minimum rated value 120 V
● maximum rated value 240 V
● initial value 85 V
● full-scale value 264 V
supply voltage at DC 110 ... 240 V
input voltage at DC 85 ... 275 V
wide range input Yes
overvoltage overload capability 300 V AC for 30 s
buffering time for rated value of the output current in the event of power failure minimum 25 ms
operating condition of the mains buffering at Vin = 240 V
line frequency 50/60 Hz
line frequency 47 ... 63 Hz
input current
● at rated input voltage 120 V 4.4 A
● at rated input voltage 240 V 2.2 A
current limitation of inrush current at 25 °C maximum 12 A
fuse protection type 10 A
fuse protection type in the feeder Circuit breaker from 6 A characteristic B to 16 A characteristic C or circuit breaker 3RV2011-1HA10 (setting 8A) or 3RV2711-1HD10 (UL 489)
output
voltage curve at output Controlled, isolated DC voltage
number of outputs 1
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
output voltage adjustable Yes; via potentiometer
adjustable output voltage 24 ... 28 V; max. 480 W (576 W up to 45°C)
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.2 %
● on slow fluctuation of ohm loading 0.2 %
residual ripple
● maximum 80 mV
● typical 50 mV
voltage peak
● maximum 100 mV
● typical 60 mV
display version for normal operation Green LED for 24 V OK
type of signal at output Electronic contact (NO contact, contact rating 30 V DC/0.1 A) for DC O.K. or diagnostic interface
behavior of the output voltage when switching on Overshoot of Vout approx. 3 %
response delay maximum 0.5 s
voltage increase time of the output voltage
● typical 100 ms
output current
● rated value 20 A
● rated range 0 ... 20 A; 24 A up to +45°C; +60 ... +70 °C: Derating 3%/K
supplied active power typical 480 W
short-term overload current
● on short-circuiting during the start-up typical 30 A
● at short-circuit during operation typical 30 A
parallel switching of outputs can be set with DIP switch
bridging of equipment Yes; switchable characteristic
number of parallel-switched equipment resources for increasing the power 2