Description
SIMATIC S7-1500 Analog input/output module AI 4x U/I/R/RTD/TC ST; 4 channels in groups of 4; Hardware interrupts; Diagnostics AQ 2x U/I ST; 2 channels in groups of 2; Substitute value; Diagnostics Common mode voltage approx. 10 V 16 bit; Accuracy 0.3%; Delivery including push-in front connector, infeed element, shield bracket and shield terminal
General information
Product type designation AI 4xU/I/RTD/TC /AQ 2xU/I ST
HW functional status from FS01
Firmware version V1.0.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Prioritized startup No
● Measuring range scalable No
● Scalable measured values No
● Adjustment of measuring range No
● Output range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13 / V13.0.2
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● Oversampling No
● MSI Yes
● MSO Yes
CiR - Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 200 mA
Encoder supply
24 V encoder supply
● Short-circuit protection Yes
● Output current, max. 20 mA; Max. 47 mA per channel for a duration < 10 s
Power
Power consumption from the backplane bus 0.7 W
Power loss
Power loss, typ. 3.3 W
Analog inputs
Number of analog inputs 4
● For current measurement 4
● For voltage measurement 4
● For resistance/resistance thermometer measurement 2
● For thermocouple measurement 4
permissible input voltage for voltage input (destruction limit), max. 28.8 V
permissible input current for current input (destruction limit), max. 40 mA
Constant measurement current for resistance-type transmitter, typ. 150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm, Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA
Technical unit for temperature measurement adjustable Yes; °C/°F/K
Analog input with oversampling No