S7-1500 by SIEMENS

S7-1500, AI 4x U/I/RTD/TC/AQ 2x U/I ST-6ES7534-7QE00-0AB0

INR 1
DATA SHEET
In stock

Description

SIMATIC S7-1500 Analog input/output module AI 4x U/I/R/RTD/TC ST; 4 channels in groups of 4; Hardware interrupts; Diagnostics AQ 2x U/I ST; 2 channels in groups of 2; Substitute value; Diagnostics Common mode voltage approx. 10 V 16 bit; Accuracy 0.3%; Delivery including push-in front connector, infeed element, shield bracket and shield terminal

General information

Product type designation AI 4xU/I/RTD/TC /AQ 2xU/I ST

HW functional status from FS01

Firmware version V1.0.0

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode No

● Prioritized startup No

● Measuring range scalable No

● Scalable measured values No

● Adjustment of measuring range No

● Output range scalable No

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V13 / V13.0.2

● STEP 7 configurable/integrated from version V5.5 SP3 / -

● PROFIBUS from GSD version/GSD revision V1.0 / V5.1

● PROFINET from GSD version/GSD revision V2.3 / -

Operating mode

● Oversampling No

● MSI Yes

● MSO Yes

CiR - Configuration in RUN

Reparameterization possible in RUN Yes

Calibration possible in RUN Yes

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption, max. 200 mA

Encoder supply

24 V encoder supply

● Short-circuit protection Yes

● Output current, max. 20 mA; Max. 47 mA per channel for a duration < 10 s

Power

Power consumption from the backplane bus 0.7 W

Power loss

Power loss, typ. 3.3 W

Analog inputs

Number of analog inputs 4

● For current measurement 4

● For voltage measurement 4

● For resistance/resistance thermometer measurement 2

● For thermocouple measurement 4

permissible input voltage for voltage input (destruction limit), max. 28.8 V

permissible input current for current input (destruction limit), max. 40 mA

Constant measurement current for resistance-type transmitter, typ. 150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm, Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA

Technical unit for temperature measurement adjustable Yes; °C/°F/K

Analog input with oversampling No