Description
SIMATIC S7-1500 Analog input module AI 4xU/I/RTD/TC ST, 16 bit resolution, Accuracy 0.3%, 4 channels in groups of 4; 2 channels for RTD measurement; Common mode voltage 10 V; Diagnostics; Hardware interrupts; Delivery including push-in front connector, infeed element, shield bracket, and shield terminal
General information
Product type designation AI 4xU/I/RTD/TC ST
HW functional status from FS01
Firmware version V1.0.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Prioritized startup No
● Measuring range scalable No
● Scalable measured values No
● Adjustment of measuring range No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13 / V13.0.2
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● Oversampling No
● MSI Yes
CiR - Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 165 mA; with 19.2 V supply
Encoder supply
24 V encoder supply
● Short-circuit protection Yes
● Output current, max. 20 mA; Max. 47 mA per channel for a duration < 10 s
Power
Power consumption from the backplane bus 0.7 W
Power loss
Power loss, typ. 2.3 W
Address area
Address space per module
● Inputs 8 byte
● Outputs 0 byte
Analog inputs
Number of analog inputs 4
● For current measurement 4
● For voltage measurement 4
● For resistance/resistance thermometer measurement 2
● For thermocouple measurement 4
permissible input voltage for voltage input (destruction limit), max. 28.8 V
permissible input current for current input (destruction limit), max. 40 mA
Constant measurement current for resistance-type transmitter, typ. 150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm, Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA
Technical unit for temperature measurement adjustable Yes; °C/°F/K
Analog input with oversampling No
Standardization of measured values No
Input ranges (rated values), voltages
● 0 to +5 V No
● 0 to +10 V No
● 1 V to 5 V Yes
— Input resistance (1 V to 5 V) 100 kΩ
● -1 V to +1 V Yes
— Input resistance (-1 V to +1 V) 10 MΩ
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) 100 kΩ
● -2.5 V to +2.5 V Yes
— Input resistance (-2.5 V to +2.5 V) 10 MΩ
● -25 mV to +25 mV No
● -250 mV to +250 mV Yes
— Input resistance (-250 mV to +250 mV) 10 MΩ
● -5 V to +5 V Yes
— Input resistance (-5 V to +5 V) 100 kΩ
● -50 mV to +50 mV Yes
— Input resistance (-50 mV to +50 mV) 10 MΩ
● -500 mV to +500 mV Yes
— Input resistance (-500 mV to +500 mV) 10 MΩ
● -80 mV to +80 mV Yes
— Input resistance (-80 mV to +80 mV) 10 MΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● -20 mA to +20 mA Yes
— Input resistance (-20 mA to +20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples
● type B Yes
— Input resistance (Type B) 10 MΩ
● type C No
● Type E Yes
— Input resistance (Type E) 10 MΩ
● Type J Yes
— Input resistance (type J) 10 MΩ
● Type K Yes
— Input resistance (Type K) 10 MΩ
● Type L No
● Type N Yes
— Input resistance (Type N) 10 MΩ
● Type R Yes
— Input resistance (Type R) 10 MΩ
● Type S Yes
— Input resistance (Type S) 10 MΩ
● Type T Yes
— Input resistance (Type T) 10 MΩ
● Type U No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Cu 10 according to GOST No
● Cu 50 No
● Cu 50 according to GOST No
● Cu 100 No
● Cu 100 according to GOST No
● Ni 10 No
● Ni 10 according to GOST No
● Ni 100 Yes; Standard/climate
— Input resistance (Ni 100) 10 MΩ
● Ni 100 according to GOST No
● Ni 1000 Yes; Standard/climate
— Input resistance (Ni 1000) 10 MΩ
● Ni 1000 according to GOST No
● LG-Ni 1000 Yes; Standard/climate
— Input resistance (LG-Ni 1000) 10 MΩ
● Ni 120 No
● Ni 120 according to GOST No
● Ni 200 No
● Ni 200 according to GOST No
● Ni 500 No
● Ni 500 according to GOST No
● Pt 10 No
● Pt 10 according to GOST No
● Pt 50 No
● Pt 50 according to GOST No
● Pt 100 Yes; Standard/climate
— Input resistance (Pt 100) 10 MΩ
● Pt 100 according to GOST No
● Pt 1000 Yes; Standard/climate
— Input resistance (Pt 1000) 10 MΩ
● Pt 1000 according to GOST No
● Pt 200 Yes; Standard/climate
— Input resistance (Pt 200) 10 MΩ
● Pt 200 according to GOST No
● Pt 500 Yes; Standard/climate
— Input resistance (Pt 500) 10 MΩ
● Pt 500 according to GOST No
Input ranges (rated values), resistors
● 0 to 150 ohms Yes
— Input resistance (0 to 150 ohms) 10 MΩ
● 0 to 300 ohms Yes
— Input resistance (0 to 300 ohms) 10 MΩ
● 0 to 600 ohms Yes
— Input resistance (0 to 600 ohms) 10 MΩ
● 0 to 3000 ohms No
● 0 to 6000 ohms Yes
— Input resistance (0 to 6000 ohms) 10 MΩ
● PTC Yes
— Input resistance (PTC) 10 MΩ
Thermocouple (TC)
Temperature compensation
— Parameterizable Yes
— internal temperature compensation Yes
— external temperature compensation via RTD Yes
— Compensation for 0 °C reference point temperature Yes; fixed value can be set
— Reference channel of the module No
Cable length
● shielded, max.