Description
SIMATIC S7-1500 Analog input module AI 8xU/I HS, 16 bit resolution, Accuracy 0.3% 8 channels in groups of 8; Common mode voltage 10 V; Diagnostics; Hardware interrupts 8 channels in 0.0625 ms Oversampling; Delivery including infeed element, shield bracket and shield terminal: Front connector (screw terminals or push-in) to be ordered separately
General information
Product type designation AI 8xU/I HS
HW functional status from FS01
Firmware version V2.1.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes
● Prioritized startup Yes
● Measuring range scalable No
● Scalable measured values No
● Adjustment of measuring range No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V14 / -
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● Oversampling Yes
● MSI Yes
CiR - Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 290 mA; with 19.2 V supply
Encoder supply
24 V encoder supply
● Short-circuit protection Yes
● Output current, max. 20 mA; Max. 47 mA per channel for a duration < 10 s
Power
Power consumption from the backplane bus 1.15 W
Power loss
Power loss, typ. 3.4 W
Address area
Address space per module
● Inputs 16 byte
● Outputs 0 byte
Analog inputs
Number of analog inputs 8
● For current measurement 8
● For voltage measurement 8
permissible input voltage for voltage input (destruction limit), max. 28.8 V
permissible input current for current input (destruction limit), max. 40 mA
Analog input with oversampling Yes
● Values per cycle, max. 16
● Resolution, min. 62.5 µs
Standardization of measured values No
Input ranges (rated values), voltages
● 0 to +5 V No
● 0 to +10 V No
● 1 V to 5 V Yes
— Input resistance (1 V to 5 V) 50 kΩ
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) 100 kΩ
● -2.5 V to +2.5 V No
● -25 mV to +25 mV No
● -250 mV to +250 mV No
● -5 V to +5 V Yes
— Input resistance (-5 V to +5 V) 50 kΩ
● -50 mV to +50 mV No
● -500 mV to +500 mV No
● -80 mV to +80 mV No
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● -20 mA to +20 mA Yes
— Input resistance (-20 mA to +20 mA) 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples
● type B No
● type C No
● Type E No
● Type J No
● Type K No
● Type L No
● Type N No
● Type R No
● Type S No
● Type T No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Cu 10 according to GOST No
● Cu 50 No
● Cu 50 according to GOST No
● Cu 100 No
● Cu 100 according to GOST No
● Ni 10 No
● Ni 10 according to GOST No
● Ni 100 No
● Ni 100 according to GOST No
● Ni 1000 No
● Ni 1000 according to GOST No
● LG-Ni 1000 No
● Ni 120 No
● Ni 120 according to GOST No
● Ni 200 No
● Ni 200 according to GOST No
● Ni 500 No
● Ni 500 according to GOST No
● Pt 10 No
● Pt 10 according to GOST No
● Pt 50 No
● Pt 50 according to GOST No
● Pt 100 No
● Pt 100 according to GOST No
● Pt 1000 No
● Pt 1000 according to GOST No
● Pt 200 No
● Pt 200 according to GOST No
● Pt 500 No
● Pt 500 according to GOST No
Input ranges (rated values), resistors
● 0 to 150 ohms No
● 0 to 300 ohms No
● 0 to 600 ohms No
● 0 to 3000 ohms No
● 0 to 6000 ohms No
● PTC No
Cable length
● shielded, max. 800 m
Analog value generation for the inputs
Measurement principle Actual value encryption
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Basic execution time of the module (all channels released) 62.5 µs; independent of number of activated channels
Smoothing of measured values
● Number of smoothing levels 4
● Parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 820 Ω
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection No
● for resistance measurement with three-wire connection No
● for resistance measurement with four-wire connection No
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.02 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, max. -60 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.02 %
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.3 %
● Current, relative to input range, (+/-) 0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.2 %
● Current, relative to input range, (+/-) 0.2 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode voltage, max. 10 V
● Common mode interference, min.