S7-1500 by siemens

S7-1500, AI 8xU/I HF-6ES7531-7NF00-0AB0

INR 1
Learn more
In stock

Description

SIMATIC S7-1500 analog input module AI 8xU/I HF, up to 24 bit resolution, accuracy 0.1%, 8 channels in groups of 1; common mode voltage: 30 V AC/60 V DC, Diagnostics; Hardware interrupts Measured values ​​scalable, measuring range adjustment, Calibrate in RUN; Delivery including infeed element, shield bracket and shield terminal: Front connector (screw terminals or push-in) to be ordered separately

General information

Product type designation AI 8xU/I HF

HW functional status from FS01

Firmware version V1.1.0

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode No

● Prioritized startup Yes

● Measuring range scalable No

● Scalable measured values Yes

● Adjustment of measuring range Yes

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V14 / -

● STEP 7 configurable/integrated from version V5.5 SP3 / -

● PROFIBUS from GSD version/GSD revision V1.0 / V5.1

● PROFINET from GSD version/GSD revision V2.3 / -

Operating mode

● Oversampling No

● MSI Yes

CiR - Configuration in RUN

Reparameterization possible in RUN Yes

Calibration possible in RUN Yes

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption, max. 55 mA; with 19.2 V supply

Power

Power consumption from the backplane bus 0.85 W

Power loss

Power loss, typ. 1.9 W

Address area

Address space per module

● Inputs 16 byte

● Outputs 0 byte

Analog inputs

Number of analog inputs 8

● For current measurement 8

● For voltage measurement 8

permissible input voltage for voltage input (destruction limit), max. 28.8 V

permissible input current for current input (destruction limit), max. 40 mA

Analog input with oversampling No

Standardization of measured values Yes; See manual for details

Input ranges (rated values), voltages

● 0 to +5 V No

● 0 to +10 V No

● 1 V to 5 V Yes

— Input resistance (1 V to 5 V) 100 kΩ

● -10 V to +10 V Yes

— Input resistance (-10 V to +10 V) 100 kΩ

● -2.5 V to +2.5 V Yes

— Input resistance (-2.5 V to +2.5 V) 100 kΩ

● -25 mV to +25 mV No

● -250 mV to +250 mV No

● -5 V to +5 V Yes

— Input resistance (-5 V to +5 V) 100 kΩ

● -50 mV to +50 mV No

● -500 mV to +500 mV No

● -80 mV to +80 mV No

Input ranges (rated values), currents

● 0 to 20 mA Yes

— Input resistance (0 to 20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC

● -20 mA to +20 mA Yes

— Input resistance (-20 mA to +20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC

● 4 mA to 20 mA Yes

— Input resistance (4 mA to 20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC

Input ranges (rated values), thermocouples

● type B No

● type C No

● Type E No

● Type J No

● Type K No

● Type L No

● Type N No

● Type R No

● Type S No

● Type T No

● Type TXK/TXK(L) to GOST No

Input ranges (rated values), resistance thermometer

● Cu 10 No

● Cu 10 according to GOST No

● Cu 50 No

● Cu 50 according to GOST No

● Cu 100 No

● Cu 100 according to GOST No

● Ni 10 No

● Ni 10 according to GOST No

● Ni 100 No

● Ni 100 according to GOST No

● Ni 1000 No

● Ni 1000 according to GOST No

● LG-Ni 1000 No

● Ni 120 No

● Ni 120 according to GOST No

● Ni 200 No

● Ni 200 according to GOST No

● Ni 500 No

● Ni 500 according to GOST No

● Pt 10 No

● Pt 10 according to GOST No

● Pt 50 No

● Pt 50 according to GOST No

● Pt 100 No

● Pt 100 according to GOST No

● Pt 1000 No

● Pt 1000 according to GOST No

● Pt 200 No

● Pt 200 according to GOST No

● Pt 500 No

● Pt 500 according to GOST No

Input ranges (rated values), resistors

● 0 to 150 ohms No

● 0 to 300 ohms No

● 0 to 600 ohms No

● 0 to 3000 ohms No

● 0 to 6000 ohms No

● PTC No

Cable length

● shielded, max. 800 m

Analog value generation for the inputs

Measurement principle integrating

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign), max. 24 bit; When using the function “Scaling of the measured values” or “Measuring range adaptation” (32 bit REAL format); 16 bit when using the S7 format (16 bit INTEGER)

● Integration time, parameterizable Yes

● Integration time (ms) Fast mode: 2.5 / 16.67 / 20 / 100 ms, standard mode: 7.5 / 50 / 60 / 300 ms

● Basic conversion time, including integration time (ms) Fast mode: 4 / 18 / 22 / 102 ms; Standard mode: 9 / 52 / 62 / 302 ms

● Interference voltage suppression for interference frequency f1 in Hz 400 / 60 / 50 / 10 Hz

● Basic execution time of the module (all channels released) Corresponds to the channel with the highest basic conversion time

Smoothing of measured values

● Number of smoothing levels 4

● Parameterizable Yes

● Step: None Yes

● Step: low Yes

● Step: Medium Yes

● Step: High Yes

Encoder

Connection of signal encoders

● for voltage measurement Yes

● for current measurement as 2-wire transducer Yes; with external transmitter supply

● for current measurement as 4-wire transducer Yes

● for resistance measurement with two-wire connection No

● for resistance measurement with three-wire connection No

● for resistance measurement with four-wire connection No

Errors/accuracies

Linearity error (relative to input range), (+/-) 0.02 %

Temperature error (relative to input range), (+/-) 0.005 %/K

Crosstalk between the inputs, max. -80 dB

Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.02 %

note regarding accuracy at temperatures below 0 °C, the figures for operating error and temperature error are doubled

Operational error limit in overall temperature range

● Voltage, relative to input range, (+/-) 0.1 %

● Current, relative to input range, (+/-) 0.1 %

Basic error limit (operational limit at 25 °C)

● Voltage, relative to input range, (+/-) 0.05 %

● Current, relative to input range, (+/-) 0.05 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

● Series mode interference (peak value of interference < rated value of input range), min. 80 dB; in the Standard operating mode, 40 dB in the Fast operating mode

● Common mode voltage, max. 60 V DC/30 V AC

● Common mode interference, min. 80 dB

Interrupts/diagnostics/status information

Diagnostics function Yes

Alarms

● Diagnostic alarm Yes

● Limit value alarm Yes; two upper and two lower limit values in each case

Diagnoses

● Monitoring the supply voltage Yes

● Wire break Yes; only for 1 ... 5 V and 4 ... 20 mA

● short-circuit No

● Group error No

● Overflow/Underflow Yes

Diagnostics indication LED

● RUN LED Yes; green LED

● ERROR LED Yes; red LED

● MAINT LED No

● Monitoring of the supply voltage (PWR-LED) Yes; green LED

● Channel status display Yes; green LED

● for channel diagnostics Yes; red LED

● for module diagnostics Yes; red LED

Potential separation

Potential separation channels

● between the channels Yes

● between the channels, in groups of 1

● between the channels and backplane bus Yes

● between the channels and the power supply of the electronics Yes

Permissible potential difference

between different circuits 60 V DC/30 V AC; insulation rated for 120 V AC basic insulation: between the channels and the supply voltage L+; between the channels and the backplane bus; between the channels

Isolation

Isolation tested with 2 000 V DC between the channels and the supply voltage L+; 2 000 V DC between the channels and the backplane bus; 2 000 V DC between the channels; 707 V DC (type test) between the supply voltage L+ and the backplane bus

Standards, approvals, certificates

Siemens Eco Profile (SEP) Siemens EcoTech

Suitable for applications according to AMS 2750 No

Suitable for applications according to CQI-9 No

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 38.6 kg

— global warming potential, (during production) [CO2 eq] 14.4 kg

— global warming potential, (during operation) [CO2 eq] 24.6 kg

— global warming potential, (after end of life cycle) [CO2 eq]