S7-1500 by siemens

S7-1500, AI 8xU/I HS-6ES7531-7NF10-0AB0

INR 1
Learn more
In stock

Description

SIMATIC S7-1500 Analog input module AI 8xU/I HS, 16 bit resolution, Accuracy 0.3% 8 channels in groups of 8; Common mode voltage 10 V; Diagnostics; Hardware interrupts 8 channels in 0.0625 ms Oversampling; Delivery including infeed element, shield bracket and shield terminal: Front connector (screw terminals or push-in) to be ordered separately

General information

Product type designation AI 8xU/I HS

HW functional status from FS01

Firmware version V2.1.0

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode Yes

● Prioritized startup Yes

● Measuring range scalable No

● Scalable measured values No

● Adjustment of measuring range No

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V14 / -

● STEP 7 configurable/integrated from version V5.5 SP3 / -

● PROFIBUS from GSD version/GSD revision V1.0 / V5.1

● PROFINET from GSD version/GSD revision V2.3 / -

Operating mode

● Oversampling Yes

● MSI Yes

CiR - Configuration in RUN

Reparameterization possible in RUN Yes

Calibration possible in RUN Yes

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption, max. 290 mA; with 19.2 V supply

Encoder supply

24 V encoder supply

● Short-circuit protection Yes

● Output current, max. 20 mA; Max. 47 mA per channel for a duration < 10 s

Power

Power consumption from the backplane bus 1.15 W

Power loss

Power loss, typ. 3.4 W

Address area

Address space per module

● Inputs 16 byte

● Outputs 0 byte

Analog inputs

Number of analog inputs 8

● For current measurement 8

● For voltage measurement 8

permissible input voltage for voltage input (destruction limit), max. 28.8 V

permissible input current for current input (destruction limit), max. 40 mA

Analog input with oversampling Yes

● Values per cycle, max. 16

● Resolution, min. 62.5 µs

Standardization of measured values No

Input ranges (rated values), voltages

● 0 to +5 V No

● 0 to +10 V No

● 1 V to 5 V Yes

— Input resistance (1 V to 5 V) 50 kΩ

● -10 V to +10 V Yes

— Input resistance (-10 V to +10 V) 100 kΩ

● -2.5 V to +2.5 V No

● -25 mV to +25 mV No

● -250 mV to +250 mV No

● -5 V to +5 V Yes

— Input resistance (-5 V to +5 V) 50 kΩ

● -50 mV to +50 mV No

● -500 mV to +500 mV No

● -80 mV to +80 mV No

Input ranges (rated values), currents

● 0 to 20 mA Yes

— Input resistance (0 to 20 mA) 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC

● -20 mA to +20 mA Yes

— Input resistance (-20 mA to +20 mA) 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC

● 4 mA to 20 mA Yes

— Input resistance (4 mA to 20 mA) 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC

Input ranges (rated values), thermocouples

● type B No

● type C No

● Type E No

● Type J No

● Type K No

● Type L No

● Type N No

● Type R No

● Type S No

● Type T No

● Type TXK/TXK(L) to GOST No

Input ranges (rated values), resistance thermometer

● Cu 10 No

● Cu 10 according to GOST No

● Cu 50 No

● Cu 50 according to GOST No

● Cu 100 No

● Cu 100 according to GOST No

● Ni 10 No

● Ni 10 according to GOST No

● Ni 100 No

● Ni 100 according to GOST No

● Ni 1000 No

● Ni 1000 according to GOST No

● LG-Ni 1000 No

● Ni 120 No

● Ni 120 according to GOST No

● Ni 200 No

● Ni 200 according to GOST No

● Ni 500 No

● Ni 500 according to GOST No

● Pt 10 No

● Pt 10 according to GOST No

● Pt 50 No

● Pt 50 according to GOST No

● Pt 100 No

● Pt 100 according to GOST No

● Pt 1000 No

● Pt 1000 according to GOST No

● Pt 200 No

● Pt 200 according to GOST No

● Pt 500 No

● Pt 500 according to GOST No

Input ranges (rated values), resistors

● 0 to 150 ohms No

● 0 to 300 ohms No

● 0 to 600 ohms No

● 0 to 3000 ohms No

● 0 to 6000 ohms No

● PTC No

Cable length

● shielded, max. 800 m

Analog value generation for the inputs

Measurement principle Actual value encryption

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign), max. 16 bit

● Basic execution time of the module (all channels released) 62.5 µs; independent of number of activated channels

Smoothing of measured values

● Number of smoothing levels 4

● Parameterizable Yes

● Step: None Yes

● Step: low Yes

● Step: Medium Yes

● Step: High Yes

Encoder

Connection of signal encoders

● for voltage measurement Yes

● for current measurement as 2-wire transducer Yes

— Burden of 2-wire transmitter, max. 820 Ω

● for current measurement as 4-wire transducer Yes

● for resistance measurement with two-wire connection No

● for resistance measurement with three-wire connection No

● for resistance measurement with four-wire connection No

Errors/accuracies

Linearity error (relative to input range), (+/-) 0.02 %

Temperature error (relative to input range), (+/-) 0.005 %/K

Crosstalk between the inputs, max. -60 dB

Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.02 %

Operational error limit in overall temperature range

● Voltage, relative to input range, (+/-) 0.3 %

● Current, relative to input range, (+/-) 0.3 %

Basic error limit (operational limit at 25 °C)

● Voltage, relative to input range, (+/-) 0.2 %

● Current, relative to input range, (+/-) 0.2 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

● Common mode voltage, max. 10 V

● Common mode interference, min.