S7-1500 by SIEMENS

S7-1500, AQ 4xU/I HF-6ES7532-5ND00-0AB0

INR 1
DATA SHEET
In stock

Description

SIMATIC S7-1500, analog output module AQ 4xU/I HF, 16-bit resolution accuracy 0.1%, 4 channels in groups of 1, common mode voltage: 30 V AC/60 V DC, diagnostics; substitute value, isochronous mode; the module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015. delivery including infeed element, shielding bracket and shield terminal: front connector (screw terminals or push-in) to be ordered separately

General information

Product type designation AQ 4xU/I HF

HW functional status from FS01

Firmware version V1.1.0

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode Yes

● Prioritized startup Yes

● Output range scalable No

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V14 / -

● STEP 7 configurable/integrated from version V5.5 SP3 / -

● PROFIBUS from GSD version/GSD revision V1.0 / V5.1

● PROFINET from GSD version/GSD revision V2.3 / -

Operating mode

● Oversampling No

● MSO Yes

CiR - Configuration in RUN

Reparameterization possible in RUN Yes

Calibration possible in RUN Yes

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption, max. 160 mA

Power

Power consumption from the backplane bus 0.95 W

Power loss

Power loss, typ. 5 W

Analog outputs

Number of analog outputs 4

Voltage output, short-circuit protection Yes

Voltage output, short-circuit current, max. 24 mA

Current output, no-load voltage, max. 22 V

Cycle time (all channels), min. 125 µs; independent of number of activated channels

Analog output with oversampling No

Output ranges, voltage

● 0 to 10 V Yes

● 1 V to 5 V Yes

● -5 V to +5 V No

● -10 V to +10 V Yes

Output ranges, current

● 0 to 20 mA Yes

● -20 mA to +20 mA Yes

● 4 mA to 20 mA Yes

Connection of actuators

● for voltage output two-wire connection Yes

● for voltage output four-wire connection Yes

● for current output two-wire connection Yes

Load impedance (in rated range of output)

● with voltage outputs, min. 1 kΩ; 0.5 kOhm at 1 to 5 V

● with voltage outputs, capacitive load, max. 1 µF

● with current outputs, max. 750 Ω

● with current outputs, inductive load, max. 10 mH

Cable length

● shielded, max. 800 m; for current, 200 m for voltage

Analog value generation for the outputs

Integration and conversion time/resolution per channel

● Resolution with overrange (bit including sign), max. 16 bit

● Conversion time (per channel) 125 µs; independent of number of activated channels

Settling time

● for resistive load 0.2 ms; see additional description in the manual

● for capacitive load 1.8 ms; see additional description in the manual

● for inductive load 2 ms; see additional description in the manual

Errors/accuracies

Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) 0.02 %

Linearity error (relative to output range), (+/-) 0.015 %

Temperature error (relative to output range), (+/-) 0.002 %/K

Crosstalk between the outputs, max. -100 dB

Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) 0.005 %

note regarding accuracy at temperatures below 0 °C, the figures for operating error and temperature error are doubled

Operational error limit in overall temperature range

● Voltage, relative to output range, (+/-) ±10 V; 0 V to 10 V: ±0.12%; 1 V to 5 V: ±0.1%

● Current, relative to output range, (+/-) ±20 mA; 0 mA to 20 mA: ±0.2%; 4 mA to 20 mA: ±0.12%

Basic error limit (operational limit at 25 °C)

● Voltage, relative to output range, (+/-) 0.06 %

● Current, relative to output range, (+/-) 0.1 %

Isochronous mode

Execution and activation time (TCO), min. 100 µs

Bus cycle time (TDP), min. 250 µs

Interrupts/diagnostics/status information

Diagnostics function Yes

Substitute values connectable Yes

Alarms

● Diagnostic alarm Yes

Diagnoses

● Monitoring the supply voltage Yes

● Wire break Yes; Only for output type “current”

● Short-circuit Yes; Only for output type “voltage”

● Overflow/Underflow Yes

Diagnostics indication LED

● RUN LED Yes; green LED

● ERROR LED Yes; red LED

● Monitoring of the supply voltage (PWR-LED) Yes; green LED

● Channel status display Yes; green LED

● for channel diagnostics Yes; red LED

● for module diagnostics Yes; red LED

Potential separation

Potential separation channels

● between the channels Yes

● between the channels, in groups of 1

● between the channels and backplane bus Yes

● Between the channels and load voltage L+ Yes

Permissible potential difference

between different circuits 60 V DC/30 V AC; insulation rated for 120 V AC basic insulation: between the channels and the supply voltage L+; between the channels and the backplane bus; between the channels

Isolation

Isolation tested with 2 000 V DC between the channels and the supply voltage L+; 2 000 V DC between the channels and the backplane bus; 2 000 V DC between the channels; 707 V DC (type test) between the supply voltage L+ and the backplane bus

Standards, approvals, certificates

Siemens Eco Profile (SEP) Siemens EcoTech

Suitable for safety-related tripping of standard modules Yes; From FS03

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 37.6 kg

— global warming potential, (during production) [CO2 eq] 11.1 kg

— global warming potential, (during operation) [CO2 eq] 26.8 kg

— global warming potential, (after end of life cycle) [CO2 eq]