Description
SIMATIC S7-1500, analog output module AQ 8xHART HF, 16-bit resolution, accuracy 0.2%, 8 channels in groups of 8 diagnostics, substitute values, delivery including infeed element, shielding bracket and shield terminal; front connector (screw terminals or push-in) to be ordered separately
General information
Product type designation AQ 8xHART HF
HW functional status from FS01
Firmware version V1.0.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Prioritized startup No
● Output range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V18 and V19 with HSP0423
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V 2.43 / -
Operating mode
● Oversampling No
● MSO Yes
CiR - Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption (rated value) 280 mA; 8x 20 mA with 750 ohm load resistance
Current consumption, max. 370 mA
Power
Power consumption from the backplane bus 0.6 W
Power loss
Power loss, typ. 4.8 W; 8x 20 mA with 750 ohm load resistance
Analog outputs
Number of analog outputs 8
Voltage output, short-circuit protection Yes
Current output, no-load voltage, max. 30 V
Cycle time (all channels), min. 5 ms; independent of number of activated channels
Analog output with oversampling No
Output ranges, current
● 0 to 10 mA No
● 0 to 20 mA Yes
● -20 mA to +20 mA No
● 4 mA to 20 mA Yes
Connection of actuators
● for voltage output two-wire connection No
● for voltage output four-wire connection No
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with current outputs, max. 750 Ω
● with current outputs, inductive load, max. 10 mH
Cable length
● shielded, max. 800 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
Settling time
● for resistive load 3 ms; see additional description in the manual
● for inductive load 3 ms; see additional description in the manual
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) 0.02 %
Linearity error (relative to output range), (+/-) 0.02 %
Temperature error (relative to output range), (+/-) 0.002 %/K
Crosstalk between the outputs, max. -100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) 0.02 %
note regarding accuracy at temperatures below 0 °C, the figures for operating error and temperature error are doubled
Operational error limit in overall temperature range
● Current, relative to output range, (+/-) 0.2 %
Basic error limit (operational limit at 25 °C)
● Current, relative to output range, (+/-) 0.1 %
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire break Yes
● Short-circuit Yes
● Overflow/Underflow Yes
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● Monitoring of the supply voltage (PWR-LED) Yes; green LED
● Channel status display Yes; green LED
● for channel diagnostics Yes; red LED
● for module diagnostics Yes; red LED
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 8
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Permissible potential difference
between different circuits 60 V DC/30 V AC
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
Suitable for safety-related tripping of standard modules No
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 37.6 kg
— global warming potential, (during production) [CO2 eq] 11.1 kg
— global warming potential, (during operation) [CO2 eq] 26.8 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.364 kg
Security
signed firmware update Yes
safely removing data No
data integrity No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C
● vertical installation, max. 40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Absolute humidity
● dew point, min. -60 °C; suitable for dry room applications
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 300 g
Other