Description
SIMATIC S7-1500, CM PTP RS232 HF communications module for serial connection RS-232, freeport, 3964(R), USS, Modbus RTU master, device, 115200 bit/s, 9-pin D-sub plug
General information
Product type designation CM PtP RS 232 HF
Product function
● I&M data Yes; I&M 0
● Fast startup Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V18 with HSP 0367 / V19; configurable with older TIA Portal versions as 6ES7541-1AD00-0AB0
● STEP 7 configurable/integrated from version V5.5 SP2 with GSD file
● PROFIBUS from GSD version/GSD revision - / -
● PROFINET from GSD version/GSD revision GSDML V2.42
Installation type/mounting
Rail mounting Yes; S7-1500 mounting rail
Input current
Current consumption (rated value) 50 mA; From the backplane bus
Power
Power consumption from the backplane bus 0.75 W
Power loss
Power loss, typ. 0.6 W
Address area
Address space per module
● Inputs 8 byte; performance mode: 32 byte
● Outputs 0 byte; performance mode: 32 byte
Interface types
RS 232
● Transmission rate, max. 115.2 kbit/s
● Cable length, max. 15 m
● RS 232 auxiliary signals RTS, CTS, DTR, DSR, RI, DCD
Protocols
Integrated protocols
Freeport
— Telegram length, max. 4 kbyte
— Bits per character 7 or 8
— Number of stop bits 1 or 2 bit
— Parity None, even, odd, always 1, always 0, any
3964 (R)
— Telegram length, max. 4 kbyte
— Bits per character 7 or 8
— Number of stop bits 1 or 2 bit
— Parity None, even, odd, always 1, always 0, any
Modbus RTU master
— Address area 1 to 247, extended 1 to 65535
— max. number of devices 1
Modbus RTU device
— Address area 1 to 247, extended 1 to 65535
Specifications
| .. | .. |
|---|