S7-1500 by SIEMENS

S7-1500, DI 32x24VDC BA--6ES7521-1BL10-0AA0

INR 1
Learn more
In stock

Description

SIMATIC S7-1500 Digital input module, DI 32x24 V DC BA, 32 channels in groups of 16, Input delay typ. 3.2 ms, Input type 3 (IEC 61131); Delivery incl. front connector Push-in

General information

Product type designation DI 32x24VDC BA

HW functional status from FS01

Firmware version V1.0.0

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode No

● Prioritized startup Yes

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V13 / V13

● STEP 7 configurable/integrated from version V5.5 SP3 / -

● PROFIBUS from GSD version/GSD revision V1.0 / V5.1

● PROFINET from GSD version/GSD revision V2.3 / -

Operating mode

● DI Yes

● Counter No

● Oversampling No

● MSI Yes

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Power

Power consumption from the backplane bus 1.05 W

Power loss

Power loss, typ. 3 W

Address area

Address space per module

● Inputs 4 byte; typical, maximum 32 bytes, see manual for details

● Outputs 0 byte

Digital inputs

Number of digital inputs 32

Digital inputs, parameterizable No

Sourcing/sinking input P-reading

Input characteristic curve in accordance with IEC 61131, type 3 Yes

Pulse extension No

Edge evaluation No

Signal change flutter No

Flutter observation window No

Number of simultaneously controllable inputs

● Number of simultaneously controllable inputs 32

Digital input functions, parameterizable

● Freely usable digital input Yes

● Counter No

● Digital input with oversampling No

Input voltage

● Rated value (DC) 24 V

● for signal “0” -30 to +5 V

● for signal “1” +11 to +30V

Input current

● for signal “1”, typ. 2.7 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable No

— at “0” to “1”, min. 3 ms

— at “0” to “1”, max. 4 ms

— at “1” to “0”, min. 3 ms

— at “1” to “0”, max. 4 ms

for interrupt inputs

— parameterizable No

for technological functions

— parameterizable No

Cable length

● shielded, max. 1 000 m

● unshielded, max. 600 m

Encoder

Connectable encoders

● 2-wire sensor Yes

— permissible quiescent current (2-wire sensor), max. 1.5 mA

Interrupts/diagnostics/status information

Diagnostics function No

Alarms

● Diagnostic alarm No

● Hardware interrupt No

Diagnoses

● Monitoring the supply voltage No

● Wire break No

● Short-circuit No

Diagnostics indication LED

● RUN LED Yes; green LED

● ERROR LED Yes; red LED

● Monitoring of the supply voltage (PWR-LED) No

● Channel status display Yes; green LED

● for channel diagnostics No

● for module diagnostics No

Potential separation

Potential separation channels

● between the channels No

● between the channels, in groups of 16

● between the channels and backplane bus Yes

● between the channels and the power supply of the electronics No

Isolation

Isolation tested with 707 V DC (type test)

Standards, approvals, certificates

Siemens Eco Profile (SEP) Siemens EcoTech

Suitable for safety functions No

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 18.9 kg

— global warming potential, (during production) [CO2 eq] 12.1 kg

— global warming potential, (during operation) [CO2 eq] 7.66 kg

— global warming potential, (after end of life cycle) [CO2 eq]