S7-1500 by SEIMENS

S7-1500, DQ 16x230VAC/2A ST (Relay)-6ES7522-5HH00-0AB0

INR 1
DATA SHEET
In stock

Description

SIMATIC S7-1500, digital output module DQ 16x 230V AC/2A ST; relay 16 channels in groups of 2; 4 A per group; switching cycle counter for integrated relay, diagnostics; substitute value: the module supports the safety-oriented shutdown of load groups up to SIL1 according to EN IEC 62061:2021 and Category 2 / PL c according to EN ISO 13849-1:2015. front connector (screw terminals or push-in) to be ordered separately

General information

Product type designation DQ 16x 230 V AC/2 A ST (relay)

HW functional status FS01

Firmware version V1.1.0

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode No

● Prioritized startup Yes

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V13 SP1 / -

● STEP 7 configurable/integrated from version V5.5 SP3 / -

● PROFIBUS from GSD version/GSD revision V1.0 / V5.1

● PROFINET from GSD version/GSD revision V2.3 / -

Operating mode

● DQ Yes

● DQ with energy-saving function No

● PWM No

● Cam control (switching at comparison values) No

● Oversampling No

● MSO Yes

● Integrated operating cycle counter Yes; FW V1.1.0 or higher

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption, max. 185 mA

Output voltage

Rated value (AC) 230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC

Power

Power consumption from the backplane bus 0.8 W

Power loss

Power loss, typ. 5 W

Address area

Address space per module

● Inputs 0 byte; typical, maximum 14 bytes, see manual for details

● Outputs 2 byte

Digital outputs

Type of digital output Relays

Number of digital outputs 16

Current-sinking Yes

Current-sourcing Yes

Digital outputs, parameterizable Yes

Short-circuit protection No

Controlling a digital input Yes

Size of motor starters according to NEMA, max. 5

Digital output functions, parameterizable

● Switching tripped by comparison values No

● Freely usable digital output No

● PWM output No

● Digital output with oversampling No

Switching capacity of the outputs

● with resistive load, max. 2 A

● on lamp load, max. 50 W (230 V AC), 5 W (24 V DC)

Output current

● for signal “1” rated value 2 A

● for signal “1” permissible range, min. 10 mA; 10 V

● for signal “1” permissible range, max. 2 A; thermal continuous current

● for signal “0” residual current, max. 0 A

Parallel switching of two outputs

● for logic links Yes

● for uprating No

● for redundant control of a load Yes

Switching frequency

● with resistive load, max. 1 Hz

● with inductive load, max. 0.5 Hz

● on lamp load, max. 1 Hz

Total current of the outputs

● Current per channel, max. 2 A; see additional description in the manual

● Current per group, max. 4 A; see additional description in the manual

● Current per module, max. 32 A; see additional description in the manual

Relay outputs

● Number of relay outputs 16

● Rated supply voltage of relay coil L+ (DC) 24 V

● Current consumption of relays (coil current of all relays), typ. 150 mA

● external protection for relay outputs Miniature circuit breaker B10 / B16

● Contact connection (internal) No

● Number of operating cycles, max. see additional description in the manual

Switching capacity of contacts

— with inductive load, max. 2 A; see additional description in the manual

— with resistive load, max. 2 A; see additional description in the manual

Cable length

● shielded, max. 1 000 m

● unshielded, max. 600 m

Interrupts/diagnostics/status information

Diagnostics function No

Substitute values connectable Yes

Alarms

● Diagnostic alarm Yes

● Maintenance interrupt Yes; maintenance alarm for switching cycle counter

Diagnoses

● Monitoring the supply voltage Yes

● Wire break No

● short-circuit No

● Group error No

Diagnostics indication LED

● RUN LED Yes; green LED

● ERROR LED Yes; red LED

● MAINT LED Yes; Yellow LED

● Monitoring of the supply voltage (PWR-LED) Yes; green LED

● Channel status display Yes; green LED

● for channel diagnostics No

● for module diagnostics Yes; red LED

Potential separation

Potential separation channels

● between the channels No

● between the channels, in groups of 2

● between the channels and backplane bus Yes

● Between the channels and load voltage L+ Yes

Permissible potential difference

between different circuits 250 V AC between the channels and the supply voltage L+; 250 V AC between the channels and the backplane bus; 500 V AC between the channels

Isolation

Isolation tested with Between channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test)

Standards, approvals, certificates

Siemens Eco Profile (SEP) Siemens EcoTech

Suitable for safety functions No

Suitable for safety-related tripping of standard modules Yes; From FS02

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 43.8 kg

— global warming potential, (during production) [CO2 eq] 9.5 kg

— global warming potential, (during operation) [CO2 eq] 34.5 kg

— global warming potential, (after end of life cycle) [CO2 eq]