S7-1500 by SEIIMENNS

S7-1500, DQ 16x24...48VUC/125VDC/0.5A ST-6ES7522-5EH00-0AB0

INR 1
DATA SHEET
In stock

Description

SIMATIC S7-1500, digital output module DQ16x24..48VUC/125V DC/0.5A ST; 16 channels in groups of 1; 0.5 A per group; substitute value: observe derating the module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015. front connector (screw terminals or push-in) to be ordered separately

General information

Product type designation DQ 16x24 ... 48 V UC/125 V DC/0.5 A ST

HW functional status from FS01

Firmware version from V1.0.0

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode No

● Prioritized startup Yes

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V13 SP1 / -

● STEP 7 configurable/integrated from version V5.5 SP3 / -

● PROFIBUS from GSD version/GSD revision V1.0 / V5.1

● PROFINET from GSD version/GSD revision V2.3 / -

Operating mode

● DQ Yes

● DQ with energy-saving function No

● PWM No

● Cam control (switching at comparison values) No

● Oversampling No

● MSO Yes

● Integrated operating cycle counter Yes; FW V1.1.0 or higher

Output voltage

Rated value (DC) 24 V; 48 V, 125 V

Rated value (AC) 24 V; 48 V (50 - 60 Hz)

Power

Power consumption from the backplane bus 2 W

Power loss

Power loss, typ. 3.8 W

Address area

Address space per module

● Inputs 0 byte

● Outputs 2 byte

Digital outputs

Type of digital output Transistor

Number of digital outputs 16

Current-sinking Yes

Current-sourcing Yes

Digital outputs, parameterizable Yes

Short-circuit protection No

Limitation of inductive shutdown voltage to 200 V (suppressor diode)

Controlling a digital input Yes

Digital output functions, parameterizable

● Switching tripped by comparison values No

● Freely usable digital output No

● PWM output No

● Digital output with oversampling No

Switching capacity of the outputs

● with resistive load, max. 0.5 A

● on lamp load, max. 40 W; At 125 V DC, 10 W at 48 V UC, 5 W at 24 V UC

Output voltage

● for signal “1”, min. L+ (-1.0 V)

Output current

● for signal “1” rated value 0.5 A

● for signal “1” permissible range, max. 0.6 A

Output delay with resistive load

● “0” to “1”, max. 5 ms

● “1” to “0”, max. 5 ms

Parallel switching of two outputs

● for logic links Yes

● for uprating No

● for redundant control of a load Yes

Switching frequency

● with resistive load, max. 25 Hz

● with inductive load, max. 0.5 Hz

● on lamp load, max. 10 Hz

Total current of the outputs

● Current per channel, max. 0.5 A

● Current per group, max. 0.5 A

● Current per module, max. 8 A

Cable length

● shielded, max. 1 000 m

● unshielded, max. 600 m

Interrupts/diagnostics/status information

Diagnostics function No

Substitute values connectable Yes

Alarms

● Diagnostic alarm No

● Maintenance interrupt Yes; maintenance alarm for switching cycle counter

Diagnoses

● Monitoring the supply voltage No

● Wire break No

● short-circuit No

● Group error No

Diagnostics indication LED

● RUN LED Yes; green LED

● ERROR LED Yes; red LED

● MAINT LED Yes; Yellow LED