Description
SIMATIC S7-1500, digital output module DQ16x24..48VUC/125V DC/0.5A ST; 16 channels in groups of 1; 0.5 A per group; substitute value: observe derating the module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015. front connector (screw terminals or push-in) to be ordered separately
General information
Product type designation DQ 16x24 ... 48 V UC/125 V DC/0.5 A ST
HW functional status from FS01
Firmware version from V1.0.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Prioritized startup Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13 SP1 / -
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Cam control (switching at comparison values) No
● Oversampling No
● MSO Yes
● Integrated operating cycle counter Yes; FW V1.1.0 or higher
Output voltage
Rated value (DC) 24 V; 48 V, 125 V
Rated value (AC) 24 V; 48 V (50 - 60 Hz)
Power
Power consumption from the backplane bus 2 W
Power loss
Power loss, typ. 3.8 W
Address area
Address space per module
● Inputs 0 byte
● Outputs 2 byte
Digital outputs
Type of digital output Transistor
Number of digital outputs 16
Current-sinking Yes
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection No
Limitation of inductive shutdown voltage to 200 V (suppressor diode)
Controlling a digital input Yes
Digital output functions, parameterizable
● Switching tripped by comparison values No
● Freely usable digital output No
● PWM output No
● Digital output with oversampling No
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 40 W; At 125 V DC, 10 W at 48 V UC, 5 W at 24 V UC
Output voltage
● for signal “1”, min. L+ (-1.0 V)
Output current
● for signal “1” rated value 0.5 A
● for signal “1” permissible range, max. 0.6 A
Output delay with resistive load
● “0” to “1”, max. 5 ms
● “1” to “0”, max. 5 ms
Parallel switching of two outputs
● for logic links Yes
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 25 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 10 Hz
Total current of the outputs
● Current per channel, max. 0.5 A
● Current per group, max. 0.5 A
● Current per module, max. 8 A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostics function No
Substitute values connectable Yes
Alarms
● Diagnostic alarm No
● Maintenance interrupt Yes; maintenance alarm for switching cycle counter
Diagnoses
● Monitoring the supply voltage No
● Wire break No
● short-circuit No
● Group error No
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED Yes; Yellow LED