S7-1500 by SIEMENS

S7-1500, DQ 16x24V DC/0.5A HF--6ES7522-1BH01-0AB0

INR 1
DATA SHEET
In stock

Description

SIMATIC S7-1500, digital output module DQ16x24 V DC/0.5A HF; 16 channels in groups of 8; 4 A per group; single-channel diagnostics; substitute value: switching cycle counter for connected actuators. the module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015. front connector (screw terminals or push-in) to be ordered separately

General information

Product type designation DQ 16x24VDC/0.5A HF

HW functional status From FS02

Firmware version V1.1.0

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode Yes

● Prioritized startup Yes

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V13 SP1 / -

● STEP 7 configurable/integrated from version V5.5 SP3 / -

● PROFIBUS from GSD version/GSD revision V1.0 / V5.1

● PROFINET from GSD version/GSD revision V2.3 / -

Operating mode

● DQ Yes

● DQ with energy-saving function No

● PWM No

● Cam control (switching at comparison values) No

● Oversampling No

● MSO Yes

● Integrated operating cycle counter Yes

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes; through internal protection with 7 A per group

Input current

Current consumption, max. 30 mA

Output voltage

Rated value (DC) 24 V

Power

Power consumption from the backplane bus 1.1 W

Power loss

Power loss, typ. 2 W

Address area

Address space per module

● Inputs 0 byte

● Outputs 2 byte

Digital outputs

Type of digital output Transistor

Number of digital outputs 16

Current-sinking No

Current-sourcing Yes

Digital outputs, parameterizable Yes

output type acc. to IEC 61131, type 0.5 Yes

Short-circuit protection Yes; Clocked electronically

● Response threshold, typ. 1 A

Limitation of inductive shutdown voltage to L+ (-53 V)

Controlling a digital input Yes

Digital output functions, parameterizable

● Switching tripped by comparison values No

● Freely usable digital output No

● PWM output No

● Digital output with oversampling No

Switching capacity of the outputs

● with resistive load, max. 0.5 A

● on lamp load, max. 5 W

Load resistance range

● lower limit 48 Ω

● upper limit 12 kΩ

Output voltage

● for signal “1”, min. L+ (-0.8 V)

Output current

● for signal “1” rated value 0.5 A

● for signal “1” permissible range, max. 0.5 A

● for signal “0” residual current, max. 0.5 mA

Output delay with resistive load

● “0” to “1”, max. 100 µs

● “1” to “0”, max. 500 µs

Parallel switching of two outputs

● for logic links Yes

● for uprating No

● for redundant control of a load Yes

Switching frequency

● with resistive load, max. 100 Hz

● with inductive load, max. 0.5 Hz; According to IEC 60947-5-1, DC-13

● on lamp load, max. 10 Hz

Total current of the outputs

● Current per channel, max. 0.5 A; see additional description in the manual

● Current per group, max. 4 A; see additional description in the manual

● Current per module, max. 8 A; see additional description in the manual

Cable length

● shielded, max. 1 000 m

● unshielded, max. 600 m

Isochronous mode

Execution and activation time (TCO), min. 70 µs

Bus cycle time (TDP), min. 250 µs

Interrupts/diagnostics/status information

Diagnostics function Yes

Substitute values connectable Yes

Alarms

● Diagnostic alarm Yes

● Maintenance interrupt maintenance alarm for switching cycle counter

Diagnoses

● Monitoring the supply voltage Yes

● Wire break Yes

● Short-circuit Yes

● Group error Yes

Diagnostics indication LED

● RUN LED Yes; green LED

● ERROR LED Yes; red LED

● MAINT LED Yes; Yellow LED

● Monitoring of the supply voltage (PWR-LED) Yes; green LED

● Channel status display Yes; green LED

● for channel diagnostics Yes; red LED

● for module diagnostics Yes; red LED

Potential separation

Potential separation channels

● between the channels No

● between the channels, in groups of 8

● between the channels and backplane bus Yes

Isolation

Isolation tested with 707 V DC (type test)

Standards, approvals, certificates

Siemens Eco Profile (SEP) Siemens EcoTech

Suitable for safety functions No

Suitable for safety-related tripping of standard modules Yes; From FS02

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 43.8 kg

— global warming potential, (during production) [CO2 eq] 9.5 kg

— global warming potential, (during operation) [CO2 eq] 34.5 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.231 kg

Highest safety class achievable for safety-related tripping of standard modules

● Performance level according to ISO 13849-1 PL d

● Category according to ISO 13849-1 Cat. 3

● SIL acc. to IEC 62061 SIL 2

● remark on safety-oriented shutdown