Description
SIMATIC S7-1500, digital output module, DQ32xDC 24V/0.5A BA, 32 channels in groups of 8, 4 A per group; the module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015. delivery incl. front connector push-in
General information
Product type designation DQ 32x24VDC/0.5A BA
HW functional status from FS01
Firmware version V1.0.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Prioritized startup Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13 / V13
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Cam control (switching at comparison values) No
● Oversampling No
● MSO Yes
● Integrated operating cycle counter No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes; through internal protection with 7 A per group
Input current
Current consumption, max. 60 mA
Output voltage
Rated value (DC) 24 V
Power
Power consumption from the backplane bus 1.15 W
Power loss
Power loss, typ. 3.8 W
Address area
Address space per module
● Inputs 0 byte; typical, maximum 28 bytes, see manual for details
● Outputs 4 byte
Digital outputs
Type of digital output Transistor
Number of digital outputs 32
Current-sinking No
Current-sourcing Yes
Digital outputs, parameterizable No
output type acc. to IEC 61131, type 0.5 Yes
Short-circuit protection Yes
● Response threshold, typ. 1 A
Limitation of inductive shutdown voltage to L+ (-53 V)
Controlling a digital input Yes
Digital output functions, parameterizable
● Switching tripped by comparison values No
● Freely usable digital output No
● PWM output No
● Digital output with oversampling No
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 12 kΩ
Output voltage
● for signal “1”, min. L+ (-0.8 V)
Output current
● for signal “1” rated value 0.5 A
● for signal “1” permissible range, max. 0.5 A
● for signal “0” residual current, max. 0.5 mA
Output delay with resistive load
● “0” to “1”, max. 100 µs
● “1” to “0”, max. 500 µs
Parallel switching of two outputs
● for logic links Yes
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz; According to IEC 60947-5-1, DC-13
● on lamp load, max. 10 Hz
Total current of the outputs
● Current per channel, max. 0.5 A; see additional description in the manual
● Current per group, max. 4 A; see additional description in the manual
● Current per module, max. 16 A; see additional description in the manual
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostics function No
Substitute values connectable No
Alarms
● Diagnostic alarm No
● Maintenance interrupt No
Diagnoses
● Monitoring the supply voltage No
● Wire break No
● Short-circuit No
● Group error No
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED No
● Monitoring of the supply voltage (PWR-LED) Yes; green LED
● Channel status display Yes; green LED
● for channel diagnostics No
● for module diagnostics No
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 8
● between the channels and backplane bus Yes
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
Suitable for safety functions No
Suitable for safety-related tripping of standard modules Yes; From FS02
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 43.8 kg
— global warming potential, (during production) [CO2 eq] 9.5 kg
— global warming potential, (during operation) [CO2 eq] 34.5 kg
— global warming potential, (after end of life cycle) [CO2 eq]